Skip to main content

ORIGINAL RESEARCH article

Front. Energy Res.
Sec. Energy Efficiency
Volume 12 - 2024 | doi: 10.3389/fenrg.2024.1448416
This article is part of the Research Topic Energy Management, Energy Efficiency Policies, and Energy System Studies View all articles

Simulation of low-load operation for a 350MW supercritical unit

Provisionally accepted
Shiming Xu Shiming Xu 1Bo Yu Bo Yu 1*Qiang Zhou Qiang Zhou 2Xiangyu Zhang Xiangyu Zhang 3Fujun Wang Fujun Wang 4Huaichun Zhou Huaichun Zhou 1
  • 1 China University of Mining and Technology, Xuzhou, China
  • 2 Other, Baotou, China
  • 3 Xi'an Thermal Power Research Institute Co., Ltd., Xi’an, China
  • 4 Other, Jilin, China

The final, formatted version of the article will be published soon.

    Currently, there is a scarcity of studies exploring the safe operating parameters for coalfired power units at loads below 30%.To accurately understand the operating characteristics of coalfired units under low load conditions, and to provide a design basis for flexibility modifications, a simulation model coupled with boiler and turbine was established, which includes the flue gas and air system, steam and water system, steam turbine, and steam extraction heat recovery system, and the iterative calculation strategy for low load conditions was proposed. The simulation calculation was performed on a 350MW supercritical coal-fired unit, with the model results showing a high degree of alignment with the unit's design and operational parameters. Under the condition of 269MW, the maximum calculation error between the model's predicted exit flue gas temperature of the air preheater and the actual operational results was 8.84%. This discrepancy was due to a sudden increase in the operating flue gas temperature, which may be associated with a blockage in the air preheater. And the simulation results under low load conditions indicate that when the unit load is below 20%, the furnace total airflow is controlled to no less than 30% of the airflow at Maximum  Corresponding author.  Corresponding author.Continuous Rating (BMCR) and the minimum feedwater flow rate can be reduced to 20% of that in Turbine Heat Acceptance (THA) load, and the unit switches to wet state operation around 20% load.As the unit load decreases, the coal consumption rate for power generation and steam turbine heat consumption rate both increase significantly. The coal consumption rate for power generation at 30% load is increased by 13.3% compared to BMCR load, and it is increased by 32.5% at 15% load which is operated in wet state. Under low load conditions, the coal consumption rate of the unit can be reduced by decreasing the oxygen content in the flue gas, reducing the minimum feedwater flow rate, and implementing boiler water recirculation.

    Keywords: boiler, low load, wet operation, simulation, boiler water circulation, Flexibility

    Received: 13 Jun 2024; Accepted: 19 Aug 2024.

    Copyright: © 2024 Xu, Yu, Zhou, Zhang, Wang and Zhou. This is an open-access article distributed under the terms of the Creative Commons Attribution License (CC BY). The use, distribution or reproduction in other forums is permitted, provided the original author(s) or licensor are credited and that the original publication in this journal is cited, in accordance with accepted academic practice. No use, distribution or reproduction is permitted which does not comply with these terms.

    * Correspondence: Bo Yu, China University of Mining and Technology, Xuzhou, China

    Disclaimer: All claims expressed in this article are solely those of the authors and do not necessarily represent those of their affiliated organizations, or those of the publisher, the editors and the reviewers. Any product that may be evaluated in this article or claim that may be made by its manufacturer is not guaranteed or endorsed by the publisher.