Skip to main content

ORIGINAL RESEARCH article

Front. Energy Res., 03 April 2024
Sec. Smart Grids

Research on additional damping control strategy of flexible distribution transformer

Guowei GuoGuowei Guo1Jinfeng WangJinfeng Wang2Ximei ZhanXimei Zhan1Zhu LiuZhu Liu3Dehuang GongDehuang Gong4Aihong Tang
Aihong Tang5*Yufei ShangYufei Shang5Zihan WangZihan Wang5
  • 1Foshan Power Supply Bureau of Guangdong Power Grid Co. Ltd., Foshan, China
  • 2Electric Power Research Institute of Guangdong Power Grid Co. Ltd., Guangzhou, China
  • 3Guangdong Power Grid Co. Ltd., Guangzhou, China
  • 4Qingyuan Power Supply Bureau of Guangdong Power Grid Co. Ltd., Qingyuan, China
  • 5Automation School, Wuhan University of Technology, Wuhan, China

Disturbances to the power system may lead to relative swing between synchronous generator rotors, causing low-frequency oscillation problems in the absence of damping. In this article, based on the single-machine infinity system containing flexible distribution transformer and synchronous generator, the linearized state equations of the system is deduced by the small-signal modeling. The mechanism of flexible distribution transformer on the rotor speed of synchronous generator is analyzed. The influence factors of flexible distribution transformer on the rotor speed of synchronous generator are analyzed. The equation of the additional damping provided by the flexible distribution transformer to this system is constructed. It was concluded that by controlling the output voltage of the regulating converter in the flexible distribution transformer, the rotor speed of the synchronous generator can be varied to increase the system damping. An additional damping control strategy for flexible distribution transformer is proposed. The simulation verifies that the proposed control strategy can effectively suppress the oscillation amplitude of each electrical quantity and shorten the oscillation duration when the system is subjected to large and small perturbations. The proposed additional damping control strategy of flexible distribution transformer can effectively improve the damping of the system and alleviate the problem of low frequency oscillation.

1 Introduction

With the increasing proportion of new energy such as wind power and photovoltaic in the power grid, the structure and operational characteristics of the power system have changed significantly. A large number of power electronic power sources replace the original synchronous generator, resulting in the gradual reduction of rotary mechanical inertia and frequency damping effect provided by the rotor, and the new power system presents low inertia characteristics. Furthermore, the system with low inertia is prone to continuous oscillation after being disturbed, which leads to low frequency oscillation, and seriously affects the safe and stable operation of power system (Zhang et al., 2019; Wang et al., 2022; Wang et al., 2023).

Combined with high reliability of traditional distribution transformers and flexible regulation of voltage source converters, flexible distribution transformer (FDT) can realize voltage regulation, reactive power compensation, harmonic suppression and other functions with smaller capacity voltage source converters in order to meet many regulation requirements in different scenarios of power systems (Tang et al., 2021; Tang et al., 2022a; Tang et al., 2022b; Tang et al., 2024). The power electronic converter in the hybrid power transformer can be selected as AC/DC converter, AC/AC converter, AC/DC/AC back-to-back converter, etc. In the case of high voltage occasions, cascaded or modular converter structure can be selected, and when it comes to high current occasions, based on the current level of development of the power electronics, the power can be enhanced by the parallel connection of multiple sets of converter units to enhance the power and transmission capacity of the output current (Liang et al., 2019; Yang et al., 2022; Zheng et al., 2022).

In order to guarantee the operational reliability and stability of FDT, scholars at home and abroad have conducted in-depth research on its topology and control strategy. The topology of the voltage source converter in the FDT can be selected depending on the application and functional requirements. The scientific reference (Li et al., 2021) suggests a diode-clamped three-level power electronic hybrid transformer topology for power management in medium and high voltage distribution networks, which has advantages in voltage withstanding level and harmonic elimination compared to the conventional two-level inverter. In the reference (Deng et al., 2019), two-stage matrix converters are used in flexible power transformers and predictive control strategies are proposed for this topology, which allows the flexible power transformer to compensate for voltage amplitude peaks and troughs as well as voltage phase angle variations during transmission of power. Reference (Firouzi et al., 2010) proposes a topology that combines a bridge fault current limiter and a power converter. Although this device also improves power quality, unlike FDTs, this topology employs a diode bridge circuit and has less regulation flexibility than FDTs. The control method of the voltage source converter also affects the performance of the system and the regulation function of FDTs. Reference (Zhang et al., 2010; Harnefors et al., 2022; Xiao et al., 2024) describes a constructive network type control strategy for voltage source converters, which simulates the internal synchronisation mechanism of the AC system and avoids the control instability problem caused by the conventional phase-locked loops in weak grids. In the reference (Li et al., 2019), a combination of a fuzzy controller and a traditional PI controller is proposed as a robust fuzzy control strategy for FDT, but the fuzzy control is prone to cause small-scale oscillations near the operating point. Aiming at the problems of voltage swell/sag and frequency fluctuation in the power system. Reference (Zhang et al., 2022) proposes a hybrid distribution transformer with local and remote cooperative control that can solve the problem of voltage fluctuation and load distortion. Comprehensive analysis of the above, the existing FDT control strategies mostly focus on power system voltage oscillation, frequency fluctuation, harmonic control and improving the robustness of the controller. However, few studies have been carried out on FDT damping control strategy for the problem of low-frequency oscillations in power systems. As a consequence, it is urgent to carry out relevant research to provide an effective control scheme for the safe and stable operation of power system.

Aiming at the problem of low frequency oscillation in the new power system with high power electronization, a lot of researches have been carried out on the suppression measures of low frequency oscillation. Reference (Wang et al., 2023) analyzes the damping mechanism of distributed power flow controller on the system, proposes the damping control strategy of distributed power flow controller, and uses artificial fish swarm algorithm to solve the optimal parameters of the damping controller. In Reference (Li et al., 2022), considering the grid-connected and isolated operation modes respectively, a new phase feedforward damping controller is used to replace the traditional frequency deviation feedback path, and a new phase feedforward damping virtual synchronous generator control method is proposed. In reference (Li et al., 2022), a feedback control loop with time delay is established, a new DC voltage feedback active damping control method is proposed, and an oversampling method is proposed to reduce the digital control delay time and improve the damping current accuracy. In the reference (Guo et al., 2023), in order to suppress the low-frequency oscillations of a modular multilevel converter-based high-voltage direct current transmission system (MMC) under low-inertia conditions, a detailed small-signal model considering the dynamics of both the MMC and the synchronous generator is developed, a complementary damping control method is proposed, and the parameters of the method are tuned by using a pole assignment method. However, the above control strategies are more complex, need to adjust more parameters, and there are weak robustness problems. Therefore, an FDT damping control strategy is proposed in this paper, which can always provide fixed damping to the power system with fewer parameters to be adjusted. Moreover, when FDT is applied to suppress the low-frequency oscillation instability of the system, it can not only improve the system damping and solve the low-frequency oscillation problem through the proposed control strategy, but also realize various flexible control functions to improve the power quality of the system (Perez et al., 2021; Xiao et al., 2023).

In this paper, small signal model method is used to analyze the damping characteristics of FDT in order to study the mechanism of FDT suppressing low frequency oscillation in medium and high voltage distribution system. The additional torque and constraint regulation provided by the flexible distribution transformer to the single-machine infinite bus system are derived, and the additional damping control strategy of FDT is proposed. Through the regulation function of the FDT damping controller, the system damping can be effectively improved and the low-frequency oscillation caused by the disturbance can be suppressed.

2 Damping characterisation of FDT

The FDT is composed of three components: the main transformer, the energy taking converter, and the regulating converter. And the topology is demonstrated in Figure 1.

Figure 1
www.frontiersin.org

Figure 1. The FDT topology.

The primary transformer is a traditional three-phase, three-winding distribution transformer responsible for the transmission of power and voltage level conversion. The voltages of primary side windings W1a, W1b, W1c of the main transformer are U1a, U1b, and U1c, and the secondary side windings W2a, W2b, W2c are U2a, U2b and U2c. A third winding W3a, W3b, W3c is set up inside the main transformer for providing power support to the energy taking converter and the regulating converter. Therefore, the third winding of the main transformer is named as the energy taking winding, and U3a, U3b and U3c are the voltage of the energy taking winding. The energy taking converter is primarily utilised for sustaining the stability of DC capacitor voltage, and its structure is a three-phase bridge voltage source converter which is connected in parallel with the energy taking winding of the primary transformer via an L-type filter. In Figure 1, Lsh represents the filter inductance on the AC side of the energy taking converter while Rsh denotes the equivalent energy dissipation resistance on the same side. The regulating converter comprises three single-phase full-bridge voltage source converters, connected in series to the neutral point side of the secondary winding of the main transformer via the isolation transformer. Through manipulation of output voltage Usea, Useb, and Usec of the regulating converter, the FDT can achieve a variety of control functions. The isolation transformer is mainly responsible for electrical isolation and a small part of power transmission. Its structure is a three-phase two-winding transformer, with windings W4a, W4b, and W4c on the primary side and windings W5a, W5b and W5c on the secondary side. In addition, the active power is exchanged between the energy taking converter and the regulating converter through a DC capacitor connection.

In order to analyze the damping characteristics of the FDT, a single-machine infinite-bus system with a FDT and a synchronous generator is constructed as shown in Figure 2. The system consists of synchronous generators, step-up transformers, transmission lines, FDT, and an infinite power supply. Consider the main transformer and the isolation transformer as ideal transformers, without regard for the power electronic switching losses in the energy taking converter and regulating converter. In Figure 2, UG represents the terminal voltage of the synchronous generator, U1 represents the voltage at the primary side of the FDT, Us represents the voltage at the infinite power bus, IL is the current in the transmission line, XTG is the leakage reactance of the step-up transformer, and XL is the impedance of the transmission line.

Figure 2
www.frontiersin.org

Figure 2. Single machine infinity system with FDT and synchronous generator.

A third order classical model is used for the synchronous generator in a single machine infinity system as shown in Figure 2. In order to simplify the order of the differential equations of the synchronous generator, assuming that the excitation potential and mechanical power of the synchronous generator remain constant, and ignoring the stator winding resistance of the synchronous generator, the rotor motion equation of the synchronous generator in the d-q rotor rotating coordinate system is

dδdt=ω1ω0dωdt=12HPmPeDω1deqdt=1Td0eqxdxdid+Efd(1)

where δ represents the rotor swing angle, which is expressed as the angle of the synchronous generator d-q rotor rotation coordinate system relative to the d0-q0 synchronous rotation coordinate system. ω is the angular velocity of rotor. ω0 is the synchronised electrical angular velocity. H is the inertia time constant of the synchronous generator. Pm is the mechanical power input to the synchronous generator. Pe is the electromagnetic power output from the synchronous generator. D is the mechanical damping factor for synchronous generators. eq is the q-axis transient potential of the synchronous generator. Td0 is the d-axis open-circuit transient time constant of the synchronous generator. xd is the d-axis synchronous reactance of the synchronous generator; xd is the d-axis transient reactance of the synchronous generator. xd is the d-axis transient reactance of the synchronous generator. id is the d-axis component of the synchronous generator output current. Efd is the excitation potential of the synchronous generator.

In the d-q rotor rotating coordinate system, the electrical circuit equation of the synchronous generator is

ud=rid+xqiquq=riqxdid+eqPe=eqiq+xqxdidiq(2)

where ud is the d-axis component of the terminal voltage of synchronous generator. r is the stator winding resistance. xq is the q-axis synchronous reactance of synchronous generator. iq is the q-axis component of the output current of synchronous generator. uq is the q-axis component of the synchronous generator terminal voltage.

The d0-q0 synchronous rotating coordinate system is established using Us as the reference voltage. As depicted in Figure 2, the following circuit equations can be derived

UGdUGq=UsedUseq+XTG+XL+XT1+XT2ILqILd+Usd0(3)

where UGd and UGq are the d-axis and q-axis components of UG in the d0-q0 synchronous rotating coordinate system respectively. Used and Useq are the d-axis and q-axis components of Use in the d0-q0 synchronous rotating coordinate system respectively. ILd and ILq are the d-axis and q-axis components of IL in the d0-q0 synchronous rotating coordinate system respectively. Usd is the d-axis component of Us in d0-q0 synchronous rotating coordinate system. XT1 and XT2 are the primary and secondary winding leakage reactance of FDT respectively.

The electrical quantity of the d0-q0 synchronous rotating coordinate system is converted to the d-q rotor rotating coordinate system by using the coordinate transformation matrix. The coordinate transformation matrix is shown as (Eq. 4)

P=sinδcosδcosδsinδ(4)

By left-multiplying (Eq. 4) by (Eq. 3) and combining (Eq. 2), the expression of the output current of the synchronous generator in the d-q rotor rotating coordinate system is obtained as follows:

id=Usd+UsedcosδUseqsinδ+eqxdΣiq=Usd+UsedsinδUseqcosδxqΣ(5)

where xdΣ=XTG+XL+XT1+XT2+xd and xqΣ=XTG+XL+XT1+XT2+xq.

From (Eqs. 1, 2, 5), it can be seen that the state equation of single machine infinite bus system with FDT is a nonlinear equation. In order to linearize the state equation of the system, the perturbation method will be used to solve the small signal model of the state equation of the system.

Assuming that the internal state variable of the single machine infinite bus system with FDT is x and the input variable is u, then there is

xT=δωequT=UsedUseq(6)

From (Eq. 6), the output voltage of the regulating converter is 0 in steady state, then there is

x0T=δ01eq0u0T=00(7)

where the subscript 0 denotes the value of each variable in the steady state, same as below.

Substituting (Eq. 7) into Eqs 1, 5, the following equations can be obtained

eq0xdxdid0+Efd0=0Pm0eq0iq0xqxdid0iq0=0id0=1xdΣUsd0cosδ0+eq0iq0=1xqΣUsd0sinδ0(8)

Assuming that the small perturbations of the state variable and the input variable are x^ and u^ respectively, then x^ and u^ can be expressed as follows

x^T=δ^ω^e^qu^T=U^sedU^seq(9)

From (Eq. 7) and (Eq. 9), it can be obtained that the state variables and input variables are as shown in (Eq. 10) when considering the presence of small perturbations

xT=x0T+x^TuT=u0T+u^T(10)

The equation of the output current of the synchronous generator in the presence of small disturbances can be deduced as following

idiq=id0iq0+i^di^q(11)

Substituting (Eq. 8) into (Eq. 11), the small disturbance i^d and i^q of the output current of the synchronous generator are expressed as follows

i^di^q=Usd0sinδ0xdΣ01xdΣUsd0cosδ0xqΣ00x^+cosδ0xdΣsinδ0xdΣsinδ0xqΣcosδ0xqΣu^(12)

Substituting (Eqs. 10, 11) into (Eq. 1), the expression of the state equation in the presence of small disturbances is acquired:

ddtx^=0ω000D2Hiq02H001Tdox^+00xqxdiq02Hxqxdid0eq02HxdxdTdo0i^di^q(13)

By combining (Eqs. 12, 13), the small signal model of the state equation of the single machine infinite bus system with FDT can be deduced as:

ddtx^=Ax^+Bu^(14)

where A is the system matrix of the state equation, B is the input matrix of the state equation.

In (Eq. 14), A and B as shown as follows

A=0ω00Usd02cos2δ0Usd0eq0cosδ02HxdΣUsd02cos2δ02HxqΣD2HUsd0sinδ02HxdΣxdxdUsd0sinδ0xdΣTdo0xd+xdxdΣTdoxdΣB=00Usd0sin2δ0eq0sinδ02HxdΣUsd0sin2δ02HxqΣUsd0cos2δ0+eq0cosδ02HxdΣ+Usd0cos2δ02HxqΣxdxdcosδ0TdoxdΣxdxdsinδ0TdoxdΣ(15)

Based on the above analysis, by controlling the output voltage 1 and 2 of the regulating converter in the FDT, 4,5 and 6 of the state variables of the synchronous generator can be changed, so that the FDT has a certain damping effect on the power system.

3 Additional damping control strategy of FDT

Based on the analysis of the damping characteristics of FDT in Section 1, this paper proposes an additional damping control strategy for FDT. The energy taking converter and regulating converter perform a regulatory function in the FDT, and the two devices have distinct roles within the additional damping control strategy. The energy taking converter draws active power from the system to sustain the stability of the DC capacitor voltage. Additionally, the regulating converter serves as the primary controlling device for the additional damping control. Through controlling the output voltage, the regulating converter offers supplementary damping for the power system, enhancing the system’s transient stability, and affecting the rotor speed of the synchronous generator.

The following specific analysis of the additional damping control effect of the regulating converter in the FDT on the power system. The motion equation of synchronous generator rotor speed ω can be approximately expressed as

2Hddtω^=a1δ^Dω^+a2e^q+b1U^sed+b2U^seqa1=Usd02cos2δ0Usd0eq0cosδ0xdΣUsd02cos2δ0xqΣa2=Usd0sinδ0xdΣb1=Usd0sin2δ0eq0sinδ0xdΣUsd0sin2δ0xqΣb2=Usd0cos2δ0+eq0cosδ0xdΣ+Usd0cos2δ0xqΣ(16)

In Equation 16, a1δ^Dω^+a2e^q represents the inherent damping of a single-machine infinite-bus system with FDT and synchronous generators. When subjected to small disturbances, a stable system can maintain stable operation through its own inherent damping. Additionally, b1U^sed+b2U^seq represents the additional damping supplied by the FDT in the single-machine infinite-bus system. What’s more, the additional damping enhances the system damping based on the inherent damping of the system, thereby boosting the power system’s capacity to suppress low-frequency oscillation during disturbances.

From the above analysis, the extra torque provided by the FDT to the single machine infinite bus system can be defined as follows

Tsub=xqxdxdΣxqΣUsd0U^sedsin2δ0U^seqcos2δ0eq0xdΣsinδ0U^sedU^seqcosδ0(17)

To ensure that the extra torque supplied by the FDT to this single machine infinity system always maintains a positive damping effect on the rotor speed of the synchronous generator, the additional torque of the FDT should satisfy the following constraints

Tsub=Dsubω^Dsub>0(18)

where Dsub indicates the additional damping provided by the FDT to the single machine infinite bus system.

Assuming that the transfer functions of the d-axis component Used and the q-axis component Useq of the output voltage of the regulating converter with respect to the rotor speed variation of the synchronous generator are h1s and h2s respectively, then there are

Used=h1scosδ0ω^Useq=h1ssinδ0ω^h1s=h2ssinδ0(19)

Substituting (Eq. 19) into (Eq. 17), the equation for the additional damping provided by the FDT to this single infinity system is obtained as

Dsub=xqxdxdΣxqΣUsd0h2s(20)

From (Eq. 20), it is only necessary to ensure that transfer function h2s is always positive, so that the additional damping provided by the FDT to this single infinity system is always positive. Considering the use of a single proportional sector for the transfer function h2s, the d-axis and q-axis components of the output voltage of the regulating converter are obtained as follows.

Used=kh1ωcotδ0Useq=kh1ω(21)

where kh is the gain of the proportional sector.

Therefore, the damping control strategy of FDT is obtained as follows

Dsub=xqxdxdΣxqΣUsd0kh(22)

From Equation 22, it can be seen that the additional damping is affected by the gain kh. And by choosing a suitable value for the gain kh, the system damping can be increased, thus improving the stability of the system operation.

Combining the above analyses, the additional damping control strategy of the FDT proposed in this paper is as follows: (i) The rotor electrical angle θGen of the synchronous generator is calculated from ω, and the phase angle θs of the secondary side bus voltage of the FDT is obtained through a phase-locked loop. Then, the difference between θGen and θs yields the rotor swing angle; (ii) calculate Used and Useq by substituting ω and δ0 into Equation 21; (iii) taking θs as a reference, Used and Useq are converted to sinusoidal modulated waveforms by Park inverter, and the trigger signal of the regulating converter is obtained by SPWM. Therefore, the control block diagram of the additional damping control strategy for the FDT is shown in Figure 3.

Figure 3
www.frontiersin.org

Figure 3. Block diagram of additional damping control strategy for flexible distribution transformer.

The control strategy of the energy taking converter is analysed below. From Figure 1, the loop equations of the energy taking converter in the d0-q0 synchronous rotation coordinate system can be obtained as follows

Urshd=UshdLshdIshddtRshIshd+ωfLshIshqUrshq=UshqLshdIshqdtRshIshqωfLshIshd(23)

where Urshd and Urshq are the d-axis component and q-axis component of the modulation voltage output by the energy taking converter in the d0-q0 synchronous rotating coordinate system respectively. Ushd and Ushq are the d-axis and q-axis components of the energy-taking winding voltage in the d0-q0 synchronous rotating coordinate system respectively. Ishd and Ishq are the d-axis component and q-axis component of the output current of the energy taking converter in the d0-q0 synchronous rotating coordinate system, respectively. ωf is the industrial angular frequency.

The Laplace transform of (Eq. 23) yields the transfer functions of Urshd, Urshq, Ishdand Ishq as

Urshd=Rsh+sLshIshd+ωfLshIshq+UshdUrshq=Rsh+sLshIshqωfLshIshd+Ushq(24)

From (Eq. 24), it can be seen that there is a coupling relationship between the d-axis component and the q-axis component of the output current, so the feed-forward decoupling control method is used. If the controller is a PI controller, the current inner-loop control strategy of the energy taking converter is

Urshd=kp1+ki1sIshd*Ishd+ωfLshIshq+UshdUrshq=kp2+ki2sIshq*IshqωfLshIshd+Ushq(25)

where Ishd* and Ishq* are the command values for the d-axis component and q-axis component of the output current of the energy taking converter respectively. kp1 and ki1 are the proportional and integral coefficients of the d-axis control loop PI controller respectively. kp2 and ki2 are the proportional and integral coefficients of the q-axis control loop PI controller respectively.

In order to maintain the stability of the DC capacitor voltage, the outer loop control strategy of the energy taking converter is shown in Equation 26. When there is no additional control requirement, the q-axis component of the output current of the energy taking converter is usually set to 0, so there is

Ishd*=kp3+ki3sUdc*UdcIshq*=0(26)

where Udc and Udc* are the actual value and the command value of the DC capacitor voltage respectively. kp3 and ki3 are the proportional coefficient and integral coefficient of the d-axis control loop PI controller respectively.

In summary, (Eqs. 25, 26) are used as the inner-loop and outer-loop control strategies of the energy taking converter respectively, to form a block diagram of the control strategy of the energy taking converter of the FDT as shown in Figure 4. In Eq. 25, the modulation voltage of SVPWM is obtained by three-phase Park inverse transformation of Urshd and Urshq, and then the trigger pulse is output to the power electronic switch of the energy taking converter, so that the energy taking converter outputs Ish.

Figure 4
www.frontiersin.org

Figure 4. Block diagram of control strategy for FDT energy taking converter.

4 Simulation analysis

In order to verify the effectiveness of the proposed additional damping control strategy for FDT, the simulation test system shown in Figure 2 is constructed in the PSCAD/EMTDC software, and the proposed additional damping control strategy for FDT is verified through the three-phase short-circuit fault condition and load surge condition. The main parameters of the simulation test system are shown in Table 1.

(1) Three-phase short-circuit fault condition

Table 1
www.frontiersin.org

Table 1. Main parameter settings of the simulation test system.

The proposed control strategy is verified by simulation under the condition of three-phase short-circuit fault. The simulation settings are as follows: the total duration of the simulation is 10 s. At the moment of 0.3 s the synchronous generator changes from a constant speed operation mode to a rotor free running mode. At the moment of 0.5 s the FDT energy taking converter is put into operation, and at the moment of 0.8 s the FDT regulating converter is put into operation. A three-phase short-circuit ground fault occurs in the line between the primary side of the FDT and the secondary side of the step-up transformer at the moment of 1s, with a fault duration of 0.05 s.

The waveforms of synchronous generator electromagnetic torque, synchronous generator frequency, line active power, and line reactive power after the occurrence of three-phase short-circuit ground fault are shown in Figure 5. It can be seen from the simulation waveform that if there is no additional damping controller for the FDT, the electromagnetic torque of the synchronous generator, the frequency of the synchronous generator and the line power flow will oscillate rapidly after the three-phase short-circuit ground fault occurs. The electromagnetic torque of the synchronous generator is still 1.02 (pu) at 10 s, and the maximum amplitude of the frequency oscillation of the synchronous generator is 50.37 Hz, and the frequency amplitude is still 50.03 Hz at 10 s. If the additional damping controller of the FDT is put into operation, the electromagnetic torque of the synchronous generator, the frequency of the synchronous generator and the oscillation amplitude of the line power flow can be quickly attenuated, and the oscillation duration is about 4.5 s to restore stable operation.

Figure 5
www.frontiersin.org

Figure 5. Electromagnetic torque, frequency and line power waveforms of synchronous generator when system disturbance occurs.

The waveforms of the capacitive voltage on the DC side of the FDT and the output voltage of the regulating converter after the occurrence of a three-phase short-circuit ground fault are shown in Figure 6. It can be seen from the simulation waveform that the energy taking converter of the FDT completes the uncontrolled rectification and controllable inverter process during 0.5–1.0 s, so that the DC capacitor voltage is stabilized at the command value of 20 kV. The three-phase short-circuit grounding fault occurs at 1.5 s, and the DC voltage fluctuates about 2.7 s to restore the command value operation. In the additional damping control of the FDT, regulating the output voltage of the regulating converterr can invert the corresponding voltage to provide additional damping for the system during the oscillation process of the system and suppress the low-frequency oscillation of the system.

Figure 6
www.frontiersin.org

Figure 6. DC voltage of FDT and output voltage waveform of regulating converter when large disturbance occurs in the system.

The above analyses show that when a large disturbance such as a short-circuit fault occurs in the system, the electrical quantity of the system rises abruptly at the instant of the fault. Under the additional damping control of the FDT, the regulating converter can invert the corresponding output voltage for the change of rotor swing angle to provide additional damping for the system, so that the electromagnetic torque, frequency, and line current amplitude of the synchronous generator can be significantly suppressed to significantly shorten the duration of the oscillation of the system after a large disturbance, and the system electrical quantities can be quickly restored to a stable value. Therefore, the proposed additional damping control strategy for FDT has the function of improving the damping of the power system, and can effectively suppress the low-frequency oscillations generated by the system after being perturbed.

(2) Load surge condition

Through the load input system to simulate the occurrence of small disturbances in the system, the simulation settings are as follows: the simulation length of 10 s, 0.2 s time synchronous generator from the constant speed mode of operation into the rotor free operation mode, 0.5 s time flexible distribution transformer energy converter into operation, 0.8 s time FPT control converter into operation, 1.5 s time 150 MW load into the system.

After the load is put into the system, the synchronous generator electromagnetic torque, frequency, output active power, output reactive power waveforms are shown in Figure 7. From the simulation waveforms, it can be seen that if the FPT does not carry out additional damping control, the synchronous generator electromagnetic torque, frequency and power rapidly generate oscillations after the load is put into the system. Among them, the oscillation amplitude of electromagnetic torque is 1.42 (pu) at the moment of 3.2 s, and the oscillation amplitude is still 1.12 (pu) at the moment of 10s. The synchronous generator frequency oscillation amplitude is 50.56 Hz after the load is put into operation, and the oscillation amplitude is still 50.11 Hz at 10 s. If the FPT additional damping controller is put into operation, the electromagnetic torque oscillation amplitude is 1.11 (pu) at 3.2 s, and the duration of the oscillation is about 3 s and then returns to stability. The synchronous generator frequency oscillation amplitude is 50.26 Hz at maximum, and the frequency amplitude remains at 50.01 Hz after the oscillation duration of about 3.5 s.

Figure 7
www.frontiersin.org

Figure 7. Synchronous generator electromagnetic torque, frequency, line active power and reactive power waveforms after load input occurs.

Comprehensive analysis of the above can be seen, in the flexible distribution transformer additional damping control strategy, the control converter can provide the corresponding additional damping for the system, the synchronous generator electromagnetic torque, frequency, line active power, line reactive power and line voltage oscillation amplitude to the obvious suppression of the oscillation duration is significantly reduced, so the proposed additional damping control strategy of the flexible distribution transformer can effectively improve the system Therefore, the proposed flexible distribution transformer additional damping control strategy can effectively improve the system damping and reduce the low-frequency oscillations generated after the system is subjected to small disturbances.

5 Conclusion

In this paper, aiming at the problem of low frequency oscillation caused by disturbance, the damping characteristics of FDT are analyzed, and an additional damping control strategy of FDT is proposed. The control strategy is verified by simulation, and the following conclusions are obtained:

(1) In this paper, the linearised equation of state of a single machine infinity system containing a FDT and a synchronous generator is derived based on the small-signal modelling method, and based on this linear equation of state, the influence path of the FDT on the rotor speed of the synchronous generator is analysed. The additional damping provided by the FDT is affected by the gain kh, and as the gain kh increases, the damping of the system gradually increases, and the suppression ability of the FDT on the low-frequency oscillations of the system increases. Therefore, the attenuation of low-frequency oscillations and the stability of operation can be improved by choosing a suitable value of gain kh after the system has been perturbed;

(2) In this paper, a FDT additional damping control strategy is proposed, and the simulation results show that, under the effect of additional damping control, the synchronous generator electromagnetic torque and frequency return to stable operation after the system has a three-phase short-circuit ground fault with an oscillation duration of about 4.5 s. After a load surge occurs in the system, the synchronous generator electromagnetic torque and frequency return to stability after about 3 s of oscillation. Therefore, the proposed additional damping control strategy of FDT can invert the corresponding output voltage to the system according to the change of rotor swing angle, provide additional damping for the system on the basis of the inherent damping, effectively reduce the amplitude of the oscillation of various electrical quantities of the system after being disturbed, and reduce the duration of the system oscillation, and improve the transient stability of the power system.

Data availability statement

The original contributions presented in the study are included in the article/supplementary material, further inquiries can be directed to the corresponding author.

Author contributions

GG: Writing–original draft, Validation, Supervision, Methodology, Funding acquisition, Conceptualization. JW: Writing–original draft, Validation, Supervision, Methodology, Funding acquisition. XZ: Writing–review and editing, Project administration, Investigation, Funding acquisition, Data curation. ZL: Writing–original draft, Investigation, Funding acquisition, Data curation. DG: Writing–original draft, Funding acquisition, Formal Analysis, Data curation. AT: Writing–review and editing, Writing–original draft, Validation, Supervision, Project administration, Methodology, Investigation, Funding acquisition, Data curation, Conceptualization. YS: Writing–original draft, Validation, Software, Investigation, Data curation. ZW: Writing–original draft, Investigation, Data curation.

Funding

The author(s) declare financial support was received for the research, authorship, and/or publication of this article. All authors are grateful to the China Southern Power Grid. The work received funding from the “China Southern Power Grid” through the project “Research on New Distributed Power Flow Control and New Flexible Distribution Transformer Technology” project number is GDKJXM20222475.

Acknowledgments

This article is grateful to China Southern Power Grid Power Grid Project for funding.

Conflict of interest

Authors GG and XZ were employed by Foshan Power Supply Bureau of Guangdong Power Grid Co. Author JW was employed by Electric Power Research Institute of Guangdong Power Grid Co. Author ZL was employed by Guangdong Power Grid Co. Author DG was employed by Qingyuan Power Supply Bureau of Guangdong Power Grid Co.

The remaining authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest.

The authors declare that this study received funding from the China Southern Power Grid. The funder had the following involvement in the study: methodology, project administration, data collection and analysis, decision to publish.

Publisher’s note

All claims expressed in this article are solely those of the authors and do not necessarily represent those of their affiliated organizations, or those of the publisher, the editors and the reviewers. Any product that may be evaluated in this article, or claim that may be made by its manufacturer, is not guaranteed or endorsed by the publisher.

References

Deng, W., Yang, Y., Guo, Y., and Li, L. (2019). Research on predictive control of TSMC hybrid transformer. Power Syst. Prot. Control 47 (11), 71–78. doi:10.19783/j.cnki.pspc.180728

CrossRef Full Text | Google Scholar

Firouzi, M., B Gharehpetian, G., and Pishvaie, M. (2010). Proposed new structure for fault current limiting and power quality improving functions. Int. Conf. Renew. Energies Power Qual. (ICREPQ’10) 1 (8), 47–52. doi:10.24084/repqj08.216

CrossRef Full Text | Google Scholar

Guo, C., Xu, L., Yang, S., and Jiang, W. (2023). A supplementary damping control for MMC-HVDC system to mitigate the low-frequency oscillation under low inertia condition. IEEE Trans. Power Deliv. 38 (1), 287–298. doi:10.1109/TPWRD.2022.3186940

CrossRef Full Text | Google Scholar

Harnefors, L., Schweizer, M., Kukkola, J., Routimo, M., Hinkkanen, M., and Wang, X. (2022). Generic PLL-based grid-forming control. IEEE Trans. Power Electron 37 (2), 1201–1204. doi:10.1109/TPEL.2021.3106045

CrossRef Full Text | Google Scholar

Li, D., Liang, D., Gao, Y., Zhang, M., Zhang, L., Qi, B., et al. (2019). NIR-II fluorescence imaging of skin avulsion and necrosis. Trans. China Electrotech. Soc. 36 (S2), 696–722. doi:10.3389/fchem.2019.00696

PubMed Abstract | CrossRef Full Text | Google Scholar

Li, D., Wu, Z., Wang, C., Tang, L., and Liang, D. (2021). Research on topology of a three-level power electronic hybrid transformer. Transformers 58 (10), 41–47. doi:10.19487/j.cnki.1001-8425.2021.10.007

CrossRef Full Text | Google Scholar

Li, H., Yin, Q., Wang, Q., Luo, H., and Hou, Y. (2022b). A novel DC-link voltage feedback active damping control method for IPMSM drives with small DC-link capacitors. IEEE Trans. Industrial Electron. 69 (3), 2426–2436. doi:10.1109/TIE.2021.3066942

CrossRef Full Text | Google Scholar

Li, M., Yu, P., Hu, W., Wang, Y., Shu, S., Zhang, Z., et al. (2022a). Phase feedforward damping control method for virtual synchronous generators. IEEE Trans. Power Electron. 37 (8), 9790–9806. doi:10.1109/TPEL.2022.3150950

CrossRef Full Text | Google Scholar

Liang, D., Liu, Y., Kou, P., Cai, S., Zhou, K., and Zhang, M. (2019). Analysis of development trend of intelligent distribution transformer. Automation Electr. Power Syst. 44 (7), 1–14. doi:10.7500/AEPS20190507007

CrossRef Full Text | Google Scholar

Perez, M. A., Ceballos, S., Konstantinou, G., Pou, J., and Aguilera, R. P. (2021). Modular multilevel converters: recent achievements and challenges. IEEE Open J. Industrial Electron. Soc. 2, 224–239. doi:10.1109/OJIES.2021.3060791

CrossRef Full Text | Google Scholar

Tang, A., Ma, L., Qiu, P., Song, J., Chen, Q., Guan, M., et al. (2022a). Research on the harmonic currents rates for the exchanged energy of unified distributed power flow controller. IET Generation, Transm. Distribution 17 (3), 530–538. doi:10.1049/gtd2.12741

CrossRef Full Text | Google Scholar

Tang, A., Song, X., Shang, Y., Guo, G., Yu, M., and Zhan, X. (2024). Harmonic mitigation method and control strategy of offshore wind power system based on distributed power flow controller. Automation Electr. Power Syst. 48 (2), 20–28. doi:10.7500/AEPS20230113008

CrossRef Full Text | Google Scholar

Tang, A., Zhai, X., Lu, Z., Zheng, X., and Xu, Q. (2021). A novel topology of distributed power flow controller for distribution network. Trans. China Electrotech. Soc. 36 (16), 3400–3409. doi:10.19595/j.cnki.1000-6753.tces.200744

CrossRef Full Text | Google Scholar

Tang, A., Zhou, W., Song, J., Qiu, P., Chen, Q., Zhai, X., et al. (2022b). Optimal output power coordinated control strategy of distributed power flow controller. Int. J. Electr. Power and Energy Syst. 140, 108075. doi:10.1016/j.ijepes.2022.108075

CrossRef Full Text | Google Scholar

Wang, G., Fu, L., Hu, Q., Liu, C., and Ma, Y. (2022). Analysis and control of low frequency oscillation damping of virtual synchronous generator with voltage loop effect. Automation Electr. Power Syst. 46 (14), 177–184. doi:10.7500/AEPS20211112003

CrossRef Full Text | Google Scholar

Wang, H., Liu, M., Dong, H., Lu, S., Yang, Z., Cheng, S., et al. (2023a). Analysis and suppression of Low Frequency Oscillation in power systems with high proportion of new energy. Electr. Power Autom. Equip. 43 (9), 152–163. doi:10.16081/j.epae.202307020

CrossRef Full Text | Google Scholar

Wang, J., Tang, A., Guo, G., Lu, Z., Yang, Y., and Zhou, W. (2023b). Research on damping control of distributed power flow controller. Power Syst. Prot. Control 51 (10), 163–171. doi:10.19783/j.cnki.pspc.221383

CrossRef Full Text | Google Scholar

Xiao, H., Gan, H., Yang, P., Li, L., Li, D., Hao, Q., et al. (2023). Robust submodule fault management in modular multilevel converters with nearest level modulation for uninterrupted power transmission. IEEE Trans. Power Del, 1–16. doi:10.1109/TPWRD.2023.3343693

CrossRef Full Text | Google Scholar

Xiao, H., He, H., Zhang, L., and Liu, T. (2024). Adaptive grid-synchronization based grid-forming control for voltage source converters. IEEE Trans. Power Syst. 39 (2), 4763–4766. doi:10.1109/TPWRS.2023.3338967

CrossRef Full Text | Google Scholar

Yang, B., Zhao, J., Ji, Z., Wang, J., and Zhou, K. (2022). Research review of hybrid transformer technology. Electr. Power Autom. Equip. 40 (2), 205–213. doi:10.16081/j.epae.202001034

CrossRef Full Text | Google Scholar

Zhang, L., Harnefors, L., and Nee, H.-P. (2010). Power-synchronization control of grid-connected voltage-source converters. IEEE Trans. Power Syst. 25 (2), 809–820. doi:10.1109/tpwrs.2009.2032231

CrossRef Full Text | Google Scholar

Zhang, L., Liu, Y., Liang, D., Kou, P., Wang, Y., Cao, Y., et al. (2022). Local and remote cooperative control of hybrid distribution transformers integrating photovoltaics in active distribution networks. IEEE Trans. Sustain. Energy 13 (4), 2012–2026. doi:10.1109/TSTE.2022.3179120

CrossRef Full Text | Google Scholar

Zhang, N., Liu, J., Chen, J., Yao, Y., Bao, Y., Chen, P., et al. (2019). Low Frequency Oscillation suppression strategy based on Flexible load and UPFC. Power Syst. Prot. Control 47 (10), 82–87. doi:10.19783/j.cnki.pspc.180748

CrossRef Full Text | Google Scholar

Zheng, L., Aniruddh, M., Vikram, C., Nishant, B., Rajendra, K., Maryam, S., et al. (2022). Solid-state transformer and hybrid transformer with integrated energy storage in active distribution grids: technical and economic comparison, dispatch, and control. IEEE J. Emerg. Sel. Top. Power Electron. 10 (4), 3771–3787. doi:10.1109/JESTPE.2022.3144361

CrossRef Full Text | Google Scholar

Keywords: flexible distribution transformer, additional damping control strategy, lowfrequency oscillation, small-signal modeling, voltage source converter

Citation: Guo G, Wang J, Zhan X, Liu Z, Gong D, Tang A, Shang Y and Wang Z (2024) Research on additional damping control strategy of flexible distribution transformer. Front. Energy Res. 12:1337649. doi: 10.3389/fenrg.2024.1337649

Received: 13 November 2023; Accepted: 14 March 2024;
Published: 03 April 2024.

Edited by:

Shuqing Zhang, Tsinghua University, China

Reviewed by:

Mehdi Firouzi, Islamic Azad University, Abhar, Iran
Huangqing Xiao, South China University of Technology, China

Copyright © 2024 Guo, Wang, Zhan, Liu, Gong, Tang, Shang and Wang. This is an open-access article distributed under the terms of the Creative Commons Attribution License (CC BY). The use, distribution or reproduction in other forums is permitted, provided the original author(s) and the copyright owner(s) are credited and that the original publication in this journal is cited, in accordance with accepted academic practice. No use, distribution or reproduction is permitted which does not comply with these terms.

*Correspondence: Aihong Tang, dGFoQHdodXQuZWR1LmNu

Disclaimer: All claims expressed in this article are solely those of the authors and do not necessarily represent those of their affiliated organizations, or those of the publisher, the editors and the reviewers. Any product that may be evaluated in this article or claim that may be made by its manufacturer is not guaranteed or endorsed by the publisher.