AUTHOR=Jiang Di TITLE=Effects and optimization of airflow on the thermal environment in a data center JOURNAL=Frontiers in Built Environment VOLUME=10 YEAR=2024 URL=https://www.frontiersin.org/journals/built-environment/articles/10.3389/fbuil.2024.1362861 DOI=10.3389/fbuil.2024.1362861 ISSN=2297-3362 ABSTRACT=
In this research, the escalating energy consumption challenges in data centers are addressed by optimizing airflow organization designs. Through the use of computational fluid dynamics (CFD) simulations, three different airflow strategies were evaluated and improved: underfloor precision air conditioning, inter-column air conditioning, and backplane air conditioning. These cooling systems, which are usually considered in isolation, were compared in a comprehensive manner to get a full picture of their efficiency and effectiveness. The findings reveal that the implementation of cold aisle containment (CAC) or hot aisle containment (HAC) significantly improves air supply efficiency (ASE) and reduces the supply heat index (SHI), leading to a more uniform temperature distribution and enhanced cooling performance. Specifically, the ASE increased from 65.69% to 85.57% and 90.25% for underfloor precision air conditioning and from 71.29% to 92.16% and 92.17% for inter-column air conditioning, with corresponding reductions in SHI. The backplane cooling system offered consistent ambient temperatures throughout the room, eliminating thermal hotspots without the need for aisle containment. This study offers a comparative analysis of different airflow organization schemes, highlighting the benefits of aisle containment in precision and inter-column air conditioning and the suitability of backplane air conditioning for high-density cooling without the need for traditional aisle separation. The results are crucial for informing energy-efficient cooling strategies in data center design and operation.