Skip to main content

ORIGINAL RESEARCH article

Front. Energy Res., 09 May 2023
Sec. Wind Energy
This article is part of the Research Topic Online Monitoring of Wind Power Plants using Digital Twin Models View all 10 articles

An MPC based active and reactive power coordinated control strategy of PMSG wind turbines to enhance the support capability

Xiyuan MaXiyuan Ma1Jingyi YuJingyi Yu1Ping Yang
Ping Yang2*Pengyu WangPengyu Wang1Peng ZhangPeng Zhang2
  • 1Digital Grid Research Institute of China Southern Power Grid, Guangzhou, China
  • 2Guangdong Key Laboratory of Green Energy Technology, South China University of Technology, Guangzhou, China

As wind turbines are constantly replacing traditional units, it is becoming a consensus that wind turbines should participate in the grid support that was only responsible by traditional units in the past. In order to enhance the grid support capabilities (including active power support and reactive power support) of permanent magnet synchronous generator (PMSG) based wind turbines, this paper constructs an active and reactive power coordinated control strategy. Compared with the current active and reactive power coordinated control strategy of PMSG wind turbines, the method of the proposed one innovatively considers the climbing coordinated restriction between active and reactive power, flexible prioritization arrangement between active and reactive power, the accurate amplitude and climbing constraints of grid-side converters’ output voltage, and the model predictive control (MPC) technique. The simulation results verify that the proposed power control strategy can make PMSG wind turbines achieve excellent power output performance and thus better meet the requirements of power grid support.

1 Introduction

Traditionally, the frequency and voltage of power systems are mainly controlled by thermal units and hydropower units. Wind and photovoltaic units account for a small generating capacity, and their power decouples with the grid frequency and voltage, standing at maximum power points and fixed power factors (Gaied et al., 2022; Zeng et al., 2022). However, with the implementation of the “double carbon” strategy in recent years, the installed capacity of wind and photovoltaic energy in China is increasing significantly, which reached approximate 706 GW by the end of September 2022 (National Energy Administration, 2023). The traditional units responsible for frequency and voltage control are gradually being replaced by the wind and photovoltaic units, which is gradually weakening the frequency and voltage control capability of power systems. Hence, it is a growing consensus that wind and photovoltaic units should provide frequency and voltage support services to power systems (i.e., grid support), so as to maintain the security operation of power systems (Hansen et al., 2006; Feltes et al., 2009).

Permanent magnet synchronous generator (PMSG) wind turbine, one of the mainstream wind turbines, is receiving more and more popularity nowadays (Guo et al., 2021). The strengths of a PMSG wind turbine include high energy efficiency and low maintenance costs (Li et al., 2012; Musarrat et al., 2019). In addition, a PMSG wind turbine contains a back-to-back full-scale converter for connecting to power systems so that power system faults and abnormal conditions will not directly affect the power output of the generator. This means that it holds inherent advantages in fault ride through and grid support (Tan et al., 2017; Sheng et al., 2021).

To provide grid support services, it is necessary for a PMSG wind turbine to adjust its active and reactive power to respond to the changes of grid frequency and voltage. Topics about power control strategies of a PMSG wind turbine/wind farm to provide grid support could be found in a great deal of literature (Wu et al., 2017; Peng et al., 2021; Zhong et al., 2021; Li et al., 2022; Okedu, 2022). For instance, a control strategy is proposed in literature (Wu et al., 2017) for a PMSG wind turbine coordinating with a battery system to provide frequency support, which is realized by instantly raising its active power to a predefined level once grid frequency disturbance occurs. In (Peng et al., 2021), the authors design a reactive voltage support method for a wind farm with static synchronous compensators considering remaining capacities and voltage unbalanced factors for different PMSG wind turbines. Yet, the power control strategies in literature (Wu et al., 2017; Peng et al., 2021; Zhong et al., 2021; Li et al., 2022; Okedu, 2022) do not fall under the category of coordinated control between active and reactive power.

Unlike loose regulatory codes for daily power generation, in the periods of providing grid support, the active and reactive power of a PMSG wind turbine is required to meet exact amplitude and response rate requirements, which are calculated based on the deviation or slope of frequency and voltage (Mohseni and Islam, 2012; Liu et al., 2015; You et al., 2015). In this context, active and reactive power coordinated control which involves active and reactive power coordinated restriction and priority decisions becomes an unavoidable and meaningful problem. On the one hand, active and reactive power coordinated restriction can improve the power control performance of a PMSG wind turbine in order to better provide grid support. On the other hand, when the apparent power of a PMSG wind turbine is greater than its rated apparent power, the priority of active and reactive power must be judged and then reduce the party with lower priority in order to ensure that the party with higher priority meets the power grid support requirements.

As shown in Figure 1, the shaded part represents the amplitude range of active and reactive power that PMSG wind turbines can output, which picture forms a semicircle or rectangle when active and reactive power is restricted coordinately or separately. To obey the given apparent power amplitude constraint, the semicircle’s radius is equal to maximum apparent power S, and the rectangle is contained in a semicircle with a radius of maximum apparent power S. Obviously, under the given apparent power amplitude constraint, active and reactive power amplitude coordinated restriction enables PMSG wind turbines to output a larger range of active and reactive power amplitude. By the same token, under the given apparent power climbing constraint, active and reactive power climbing coordinated restriction allows PMSG wind turbines to perform a larger range of active and reactive power climbing. Therefore, active and reactive power coordinated restriction is contributing to improving the PMSG wind turbines’ power control performance.

FIGURE 1
www.frontiersin.org

FIGURE 1. Amplitude range of active and reactive power that PMSG wind turbines can output. (A) coordinated restriction. (B) separated restriction.

For this reason, some literature pays attention to designing the coordinated control strategies of active and reactive power for PMSG wind turbines providing grid support (Nguyen et al., 2013; Moghadasi and Sarwat, 2015; Yan et al., 2016; Zhang et al., 2016; Tripathi et al., 2019). Ref (Dong et al., 2012). presents a coordinated control strategy to enhance the low voltage ride through and grid support capability of PMSG wind turbines. In (Khazaei et al., 2020), a consensus-based control strategy is proposed to regulate the output of PMSG wind turbines and distributed batteries in a wind farm to deliver active and reactive power to the load. These strategies only focus on amplitude coordinated restriction of active and reactive power, which will become more perfect if the climbing coordinated restriction of active and reactive power can be taken into account at the same time.

In summary, most previous power control strategies for PMSG wind turbines providing grid support either do not explore the coordinated control between active and reactive power, or only focus on amplitude coordinated restriction and ignore the climbing coordinated restriction between active and reactive power. In addition, the priority decisions of active and reactive power in previous power coordinated control strategies are not flexible enough to apply to multiple grid support scenarios. Model predictive control (MPC) (Rodriguez et al., 2009; Mayne, 2014), which can handle complex constraints and achieve multiple optimization objectives, is suitable to structure flexible power coordinated control strategies. MPC is numerous applicated in industrial process control (Qin and Badgwell, 2003; Venkat et al., 2008; Vazquez et al., 2014) and power control of PMSG wind turbines (Maaoui-Ben Hassine et al., 2016; Shehata, 2017; Mishra and Saha, 2020), while has not been found to be applicated in PMSG wind turbines’ active and reactive power coordinated control. Finally, the current MPC models on the PMSG wind turbines lack the accurate amplitude and climbing constraints of grid-side converters’ output voltage.

Based on the mentioned issues, this paper proposes an MPC based active and reactive power coordinated control strategy of PMSG wind turbines to enhance the grid support capability. The contributions of this article are as follows.

(1) Take the lead in adopting MPC to build an active and reactive power coordinated control strategy of PMSG wind turbines that can be flexibly applicated in different grid support scenarios due to the MPC can flexibly set the priority of active and reactive power.

(2) Not only the existing amplitude coordinated restriction between active and reactive power but also the innovative climbing coordinated restriction between active and reactive power is considered in the proposed control strategy, which enables PMSG wind turbines to perform a wider range of active and reactive power amplitude and climbing. So it enhances the power control performance and the grid support capability of PMSG wind turbines.

(3) The amplitude and climbing constraint model of grid-side converter voltage is structured in the proposed MPC based control strategy in order to protect the grid-side converters and dignify the output voltage waveform.

The rest of this paper is organized as follows. Section 2 describes the overview of PMSG wind turbines. Section 3 displays the mathematical model of PMSG wind turbines. The MPC based active and reactive power coordinated control strategy is introduced in Section 4 and simulated in Section 5. Finally, Section 6 summarizes this paper.

2 The system description

The composition of the PMSG wind turbine studied is shown in Figure 2, which mainly consists of a wind turbine, a PMSG, a back-to-back converter, and multiple controllers. In this paper, the generator-side converter is employed to maintain capacitor voltage and the grid-side converter controls active power to realize maximum power point tracking and provide grid frequency support. Meanwhile, the grid-side converter is also used to control the reactive power exchange to the power grid, so as to provide grid voltage support. Therefore, the key to providing frequency and voltage support for the power grid is to control the active and reactive power of the grid-side converter.

FIGURE 2
www.frontiersin.org

FIGURE 2. The composition of the PMSG wind turbine studied.

In order to obtain the wider range of active and reactive power amplitude and climbing under the given apparent power amplitude and climbing constraints, in this paper, both the amplitude coordinated restriction and climbing coordinated restriction of the grid-side converter’s active and reactive power are considered. In view of the obvious advantages of MPC in dealing with multi-input and multi-output control problems with complex constraints and specific objectives, this paper applies MPC to struct the active and reactive power coordinated control strategy of the grid-side converter.

The MPC based active and reactive power coordinated control system of the grid-side converter is presented in Figure 2. The MPC controller uses the predictive model of the controlled system to predict the behavior of the controlled system under different control actions and selects the optimal control action which minimizes the objective function. According to the situations of the power grid and the PMSG wind turbine, the objective function is automatically adjusted so that the proposed control strategy can adapt to different grid support scenarios.

Firstly, the mathematical model of the grid-side converter is established. Secondly, an inverse system is designed in order to change the grid-side converter into a pseudolinear composite system. Thirdly, the prediction model and constraint conditions of the MPC controller are built according to the state space equation and operation boundary of the pseudolinear composite system, and the objective function of the MPC controller is built according to the reference value and priority of active and reactive power. Finally, the optimal control action is obtained by solving the optimization problem.

3 The system model

3.1 Mathematical model of grid side converter

By analyzing the three-phase circuit between the grid-side converter and the power system as shown in Figure 2, the three-phase mathematical model of the grid-side converter system can be written as follows:

UabcEabc=IabcR+LdIabcdt(1)

where Uabc and Eabc represent the three-phase voltage of the grid-side converter and the power system respectively. R and L are the resistor and inductor of the filter. Iabc represents the three-phase grid current flowing into the power grid from the grid-side converter.

The three-phase mathematical model (1) of the grid-side converter can be transformed to a mathematical model in dq synchronously rotating reference frame, which can be expressed as follows.

Ldiddt=Rid+ωLiq+udedLdiqdt=RiqωLid+uqeq(2)
ed=eeq=0(3)

where id and iq, ud and uq, ed and eq are the grid current, converter voltage, grid voltage in dq-axis. e and ω are the amplitude and angular frequency of the grid voltage, which are uncertain and varying parameters. The active and reactive power flowing into the power grid can be given by

P=32eidQ=32eiq(4)

3.2 Grid Side Converter Model Linearization

It can be seen that the nonlinearities exist in the grid-side converter’s mathematical model (2) since it contains the nonlinear terms e and ω. In this paper, an inverse system is designed and connected in series to the control loop to cope with the nonlinearity existing in the grid-side converter’s mathematical model. The inverse system uses real time state feedback to compensate the control variables vd and vq, which the compensation law can be expressed as follows.

It is worth mentioning that, due to the need to solve the optimization model, the sampling interval of an MPC controller cannot be set as a small value, while the sampling interval of an inverse system can be set to very small, so the inverse system can sample the state variables (id and iq), amplitude e and angular frequency ω in real time to compensate the control variables vd and vq. The real time system states (id and iq) can be obtained by measuring the real time three-phase current and making a Park’s Transformation.

ud=Lvd+RidωLiq+euq=Lvq+Riq+ωLid(5)

As shown in Figure 2, vd and vq are the inputs of the inverse system. ud and uq are the outputs of the inverse system and as converter control voltages to input in the grid-side converter system. The mathematical model of the composite system composed of the inverse system and the grid-side converter system can be obtained by substituting (5) into (2)–(4).

diddt=vddiqdt=vq(6)
P=32eidQ=32eiq(7)

Therefore, a grid-side converter composite system is structed which inputs are vd and vq, and outputs are the active power P and reactive power Q.

The state variables and output variables of the composite system are the same as those of the grid-side converter system. Therefore, to control the composite system is essential to control the converter system grid-side converter system.

The state representation Eq. 2 of the grid-side converter system contains the nonlinear terms e and ω. If the amplitude e and angular frequency ω of the grid voltage change, the MPC controller may not achieve the expected effect of predicting and controlling the state variables. In contrast, the state representation Eq. 6 of the composite system is linear and definite, so that the state variables can be accurately predicted and controlled by the MPC controller whether the amplitude and angular frequency of the grid voltage change or not. Therefore, compared with the direct control of the grid-side converter system, the control of the composite system can obtain a more reliable control effect.

The grid-side converter composite system model (6)–(7) can be written as a normal linear state space model.

x=Ax+Bvy=Cxx=[id,iq]T,y=P,QTA=0,00,0,B=1,00,1,C=1.5*e,00,1.5*e(8)

If the amplitude of the grid voltage is stable, the system model can accurately describe the output characteristic of the system. So that the MPC controller can accurately predict and control the outputs of the system. The system outputs will gradually reach the reference values under the control of the MPC controller.

In contrast, if the amplitude of the grid voltage changes after being measured, this means that the output characteristic of the system has changed and does not match the currently established system model during this sampling interval. The MPC controller may not achieve the expected effect of predicting and controlling the system outputs during this sampling interval. However, the system model will be corrected because the MPC controller will re-measure the grid voltage amplitude at the beginning of the next sampling interval. Based on the correct system model, the system outputs will gradually reach the reference values under the control of the MPC controller. Therefore, the change of the grid voltage amplitude will not cause the system to lose stability, but make the outputs of the system fail to reach the expected value within the current sampling interval.

The MPC algorithm is not executed continuously in the controller, but at regular interval, which is called sampling interval or control period and is denoted by T. Discretization (8) can result in

xk+1=Adxk+Bdvkyk=Cdxkxk=[idk,iqk]T,vk=vdk,vqkTyk=Pk,QkTAd=eAT,Bd=0TeAtdtB,Cd=C(9)

where xk, vk, yk are the states, inputs and outputs of the grid-side converter composite system in discrete time. Next, the MPC controller is designed to control the grid-side converter composite system, based on the discrete state-space model (9).

4 The MPC based control strategy

The prediction horizon refers to the time range from the current time point to a certain time point in the future. The MPC algorithm needs to predict the state variables of the composite system in this time range. The time length of the prediction horizon is an integral multiple of the MPC sampling interval/control interval, so it can be expressed as NP*T. Similarly, The control horizon refers to the time range from the current time point to a certain time point in the future. The MPC algorithm needs to compute the optimal control variables of the composite system in this time range. The time length of the control horizon is an integral multiple of the MPC sampling interval/control interval, so it can be expressed as NC*T.

In this paper, NP = 3 and NC = 2 when we introduce the formulas of the optimization problem. This means that the MPC algorithm needs to predict the state variables of the system from the time t = (k+1)*T to the time t = (k+ 3)*T, meanwhile, the MPC algorithm needs to compute the optimal control variables of the system in the period from the time t = kT to the future time t = (k+2)*T. In fact, they can take other values. With the increase in the NP and NC, the computing time and controller performance of the MPC algorithm will increase. When setting the values of NP and NC, it is necessary to ensure that the computing time of the MPC algorithm cannot exceed the MPC sampling interval.

In each sampling interval, the MPC controller solves the optimization problem (823) and obtains the optimal control variables vt=vdt,vqt,t=kT,k+1T,...k+NCT of future NC sampling interval, and then only the first set of optimal control variable vdkT,vqkT will be provided for the composite system.

4.1 Constraint conditions of power amplitude

Generalized power amplitude constraint conditions include the power amplitude constraints and current amplitude constraints. Based on the discrete state-space model (9), the grid current amplitudes in the future triple control periods can be predicted as follows.

xk+1=Adxk+Bdvkxk+2=Adxk+1+Bdvk+1=Ad2xk+AdBdvk+Bdvk+1xk+3=Adxk+2+Bdvk+2=Ad3xk+Ad2Bdvk+AdBdvk+1+Bdvk+2(10)

The prediction model (10) of grid current amplitudes can be rewritten in matrix form.

X=ADxk+BDVX=xk+1;xk+2;xk+3V=vk;vk+1;vk+2AD=Ad;Ad2;Ad3BD=Bd,02×2,02×2AdBd,Bd,02×2Ad2Bd,AdBd,Bd(11)

The future grid current amplitudes should not be greater than of the rated current amplitude of the grid-side converter. Then, we have.

xj2=idj2+iqj2iN2,j=k+1,...,k+3(12)

Compared to separately restricting each active current idj and reactive current iqj amplitude such as idminidjidmax,iqminiqjiqmax, coordinately restricting active current id and reactive current iqj amplitudes as (12) makes the amplitude range of active current and reactive current larger.

Similarly, based on discrete state-space model (9), the power amplitudes in the future triple control periods can be predicted.

yk+1=CdAdxk+CdBdvkyk+2=CdAdxk+1+CdBdvk+1=CdAd2xk+CdAdBdvk+CdBdvk+1yk+3=CdAdxk+2+CdBdvk+2=CdAd3xk+CdAd2Bdvk+CdAdBdvk+1+CdBdvk+2(13)

The prediction model (12) of the power amplitudes can be rewritten in matrix form.

Y=CDxk+DDVY=yk+1;yk+2;yk+3V=vk;vk+1;vk+2CD=CdAd;CdAd2;CdAd3DD=CdBd,02×2,02×2CdAdBd,CdBd,02×2CdAd2Bd,CdAdBd,CdBd(14)

The future apparent power amplitudes of the grid-side converter should not be greater than its rated apparent power amplitude. Then, we have.

yj2=Pj2+Qj2SN2,j=k+1,...,k+3(15)

Compared to separately restricting each active power Pj and reactive power Qj amplitude such as PminPjPmax,QminQjQmax, coordinately restricting active power Pj and reactive power Qj amplitudes as (15) makes the amplitude range of active power and reactive power larger.

4.2 Constraint conditions of power climbing and voltage

Based on the state space model (6)–(9), we can see that the climbing of active power and reactive power depends on the control variables vd and vq. To restrict the maximum climbing of apparent power, the coordinately restricting climbing of active and reactive power can be set as

vdj2+vqj2vmax2,j=k,...,k+2(16)

Compared to separately restricting each control input such as vdminvdjvdmax,vqminvqjvqmax, coordinately restricting vd and vq as (16) makes the climbing range of active and reactive power larger.

In order to protect the grid-side converter and dignify the output voltage waveform, the amplitude coordinated restriction and climbing coordinated restriction between grid-side converter voltages ud and uq are structed in this sub-section. The variation characteristic of the converter voltage ud and uq can be analyzed as follow and is shown as Figure 3.

(1) The variation characteristic of the control variables vd and vq

FIGURE 3
www.frontiersin.org

FIGURE 3. The variation characteristic of the control variables, current and converter voltage.

As mentioned above, The MPC algorithm is not executed continuously, but at regular control period T. At the starting point of each control period T, the MPC controller solves the MPC algorithm and outputs a new round of control variables vd and vq. Then, the outputs of the MPC controller will remain unchanged until the next control period.

Therefore, during a control period T, the control variables vd and vq remain unchanged. At the moments of two control period junctures, the MPC controller will give a new round of control variables vd and vq, so that the control variables vd and vq will suddenly change at these moments. The variation characteristic of the control variables vd and vq can be seen in Figure 3.

(2) The variation characteristic of the current id and iq

According to mathematical model (6), it can be seen that the change rates of the current id and iq are the control variables vd and vq, respectively. During a control period T, the control variables vd and vq remain unchanged. Therefore, the current id and iq will monotonically increase or decrease. The variation characteristic of the current id and iq can be seen in Figure 3. The variation characteristics of the power P and Q are consistent with those of the current id and iq.

(3) The variation characteristic of the converter voltage ud and uq.

Based on inverse system model (5), the derivative of the converter voltage ud and uq can be calculated as dud/dt=RvdωLvq and duq/dt=Rvq+ωLvd. It can be seen that the derivatives of the converter voltage ud and uq are constant, so they vary monotonically during a control period T.

At the moments of two control period junctures (such as t = kT…t=(k+3)T), the MPC controller will give a new round of control variables vd; vq. According to mathematical model (5), the converter voltage ud and uq will suddenly change at these moments due to the sudden change of the control variables vd and vq. The variation characteristic of the converter voltage ud and uq can be seen in Figure 3.

Based on the inverse system model (5), the future converter voltage uj+,j=k...k+2 in Figure 3 can be calculated as

uk+=Lvk+Rjxk+ejuk+1+==Lvk+1+Rjxk+1+ejuk+2+=Lvk+2+Rjxk+2+ejuk+=udk+uqk+,Rj=R,Lω0Lω0,R,ej=e0(17)

The prediction model (17) of converter voltage can be rewritten in matrix form.

U+=LV+RJW+eJU+=uk+;uk+1+;uk+2+W=xk;xk+1;xk+2V=vk;vk+1;vk+2eJ=ej;ej;ejRJ=diagRj,Rj,Rj(18)

Based on the inverse system model (5), the future converter voltage uj,j=k+1...k+3 in Figure 3 can be calculated as

uk+1==Lvk+Rjxk+1+ejuk+2=Lvk+1+Rjxk+2+ejuk+3=Lvk+2+Rjxk+3+ejuk=udkuqk,Rj=R,Lω0Lω0,R,ej=e0(19)

The prediction model (19) of converter voltage can be rewritten in matrix form.

U=LV+RJX+eJU=uk+1;uk+2;uk+3X=xk+1;xk+2;xk+3V=vk;vk+1;vk+2eJ=ej;ej;ejRJ=diagRj,Rj,Rj(20)

The future voltage amplitudes of the grid-side converter should not be greater than its rated voltage amplitude. Then, we have.

uj+2=udj+2+uqj+2uN2,j=k,...,k+2uj2=udj2+uqj2uN2,j=k+1,...,k+3(21)

As shown in Figure 3, at the moments of two control period T junctures (such as t = kTt=(k+3)T), the output converter voltage u=ud,uqT will suddenly change due to the suddenly change of control input v=vd,vqT. The climbing of the converter voltage depends on the change of the control input which is denoted by Δv=Δvd,ΔvqT. Δvd and Δvd are coordinated restricted in order to avoid excessive transient climbing of converter voltage.

Δvj2=Δvdj2+Δvqj2Δvmax2,j=k,...,k+2Δvk=vkvk1Δvk+1=vk+1vkΔvk+2=vk+2vk+1(22)

The square of the current amplitude is i2=id2+iq2 and the square of the converter voltage amplitude is u2=ud2+uq2. Based on did/dt=vd and diq/dt=vq, the second derivative of i2 can be calculated as d2i2/dt2=idvd+2iqvq. Similarly, based on dud/dt=RvdωLvq and duq/dt=Rvq+ωLvd, the second derivative of u2 can be calculated as d2u2/dt2=2RvdωLvq2+2Rvq+ωLvd2.

It can be seen that the second derivatives of both i2 and u2 are greater than or equal to 0. This means that during a control period T, the curves of both i2 and u2 are concave downward. The maximum values of i2 and u2 during a control period T will appear at the beginning and end instants of the control period. The square of the apparent power amplitude S2 and the square of the current amplitude i2 have the same characteristics. Therefore, it is only necessary to restrict the amplitude square of converter voltage, current and power at the beginning and end instants of each control period T such as constraint conditions (12), (15), (21). Even without the above reasons, since the MPC controller is discrete, it can only carry out discrete constraints on voltage, current and power.

4.3 Objective function

The optimization objective is to minimize the deviations between the output values and reference values of the grid-side converter composite system’s active and reactive power.

minJ=ΔYTRΔYΔY=YrefYY=yk+1;yk+2;yk+3Yref=yk+1ref;yk+2ref;yk+3refykref=Pkref,QkrefT,yk=Pk,QkTr=rP,00,rQ,R=diagr,r,r(23)

When the apparent power reference of the grid-side converter composite system lesser than its rated apparent power, the output values of active and reactive power can reach their reference values. If the apparent power reference is greater than rated apparent power, the priority of active and reactive power must be set and the party with lower priority cannot reach its reference.

This paper sets the priority of active and reactive power by setting the deviation coefficients rP and rQ. When rP is greater than rQ, it means that the active priority is higher. On the contrary, when rP is less than rQ, reactive power priority is higher. The party with higher priority can achieve greater amplitude and climbing.

According to the National standard of China “Technical Regulations for Wind Farm Access to Electric Power System, GB/T 19963.1-2021”, when the grid voltage change is in the domain of e<0.9eN or e>1.1eN, the wind farm should provide reactive power support for the grid voltage recovery, and when the grid voltage change is in the domain of 0.9eN<e<1.1eN, the wind farm should withdraw reactive power support.

Therefore, in the proposed control strategy, according to the situation of the power grid and the PMSG wind turbine, the deviation coefficients rP and rQ. are automatically adjusted so that the proposed control strategy can adapt to different grid support scenarios. For example, when the grid voltage change is in the domain of 0.9eN<e<1.1eN, the active power priority is set higher ( rP > rQ ), so that the PMSG wind turbine can carry out maximum wind energy capture and frequency support. When the grid voltage change is in the domain of e<0.9eN or e>1.1eN, the priority task of the PMSG wind turbine is to provide reactive power support for the grid voltage recovery, and of cause the reactive power priority is set higher ( rP < rQ ). The priority of active and reactive power can also be set according to other conditions, such as grid frequency or rotor speeds of the PMSG wind turbine.

4.4 Stability analysis

The optimization problem of the MPC controller can be sort out as follows

minJV=ΔYTRΔYs.t.823ciV0,i=1,,mhjV=0,j=1,,n(24)

where ciV and hjV represent the inequality constraints and equality constraints in (823). The optimization variables V of the optimization problem (24) are V=vk;;vk+NC.

4.4.1 The feasibility of the optimization process

To avoid the feasible set determined by the constraints becoming empty, the optimization problem (24) can be modified as follows.

minJV,ε=ΔYTRΔY+i=1mρiεi2s.t.ciV,εεi,i=1,,mεi0,i=1,,mhjV=0,j=1,,n(25)

The optimization variables V,ε of the optimization problem (25) include original optimization variables V=vk;;vk+NC and slack optimization variables ε=ε1;;εm. The values of the slack optimization variables ε=ε1;;εm are flexible, thus any values of the original optimization variables V=vk;;vk+NC can satisfy the constraints. In other word, the feasible set determined by the constraints is always non-empty so that the optimization problems (25) always exists the optimal solution during the optimization process.

The slack optimization variables ε=ε1;;εm are contained in the objective function, so that all the slack optimization variables ε=ε1;;εm will eventually approach 0 during the optimization process. In the end, the optimization problem (25) is the same as the optimization problem (24).

4.4.2 The stability analysis of the control system.

The control system including the MPC controller and the grid-side converter composite system. Stability analysis is to construct an energy function for the control system and determine whether the energy function meets the stability conditions. The energy function chosen here is EFxk=ykTryk, where yk=Cdxk. Next, we will prove that it satisfies the stability conditions.

1) EFxk is a positive definite function.

If xk0, we have yk=Cdxk0, then EFxk=ykTryk>0.

If xk=0, we have yk=Cdxk=0, then EFxk=ykTryk=0.

Therefore, EFxk is a positive definite function.

2) when xk, the EFxk.

Firstly, EF=ykTryk=αyk2, α is a constant.

If xk, we have yk=Cdxk, then EFxk.

3) If xk0, EFxk is going to go down over time.

When judging the change trend of the energy function EFxk, the system input vector is 0 vector (Yref=0) but the initial system state vector is not 0 vector (xk=[idk,iqk]T0). Given that ΔY=YrefY and Yref=0, the optimization problem (25) can be rewritten as:

minJV,ε=YTRY+i=1mρiεi2=l=k+1k+NPylTryl+i=1mρiεi2s.t.ciV,εεi,i=1,,mεi0,i=1,,mhjV=0,j=1,,n(26)

When initial state variables are xk=[idk,iqk]T0, the energy function is EFxk=ykTryk. Solving the optimization problem (26), the optimal variables obtained are denoted by Vk=vk;;vk+NC, εk=ε1k;;εmk, and the optimal state sequence is denoted by Xk=xk+1;;xk+NP, and the optimal output sequence is denoted by Yk=yk+1;;yk+NP. Then, the objective function is JV,εk=l=k+1k+NPylTryl+i=1mρiεik2. By analyzing the optimization problem (26), the optimization results have the following two hypothesis.

If the value taking of the original optimization variables Vk=vk;;vk+NC makes the state variables and outputs constantly approach 0 (that is xk>xk+1xk+NP0 and yk>yk+1yk+NP0), the value taking of the slack optimization variables εk=ε1k;;εmk can be smaller or remain 0. so that the result of the objective function JV,εk=l=k+1k+NPylTryl+i=1mρiεik2 will be smaller.

On the contrary, if the value taking of the original optimization variables Vk=vk;;vk+NC make the state variables and outputs constantly away from 0 (that is xk<xk+1<<xk+NP and yk<yk+1<<yk+NP), the slack optimization variables εk=ε1k;;εmk will be forced to take larger values to ensure that the inequality constraint can be satisfied. In this way, the result of the objective function JV,εk=l=k+1k+NPylTryl+i=1mρiεik2 will be larger.

Given that the optimal variables obtained Vk=vk;;vk+NC, εk=ε1k;;εmk always minimize the objective function JV,ε=l=k+1k+NPylTryl+i=1mρiεik2. Therefore, the optimization result will satisfy the first hypothesis. That is to say, the optimal state variables and optimal outputs obtained from solving the optimization problem (26) will constantly approach 0 (xk>xk+1xk+NP0 and yk>yk+1yk+NP0).

Under the control of the MPC controller, in the next sampling interval, the system state variables changes to xk+1=[idk+1,iqk+1]T, the energy function is EFxk+1=yk+1Tryk+1. Given that yk>yk+1, we have EFxk>EFxk+1. The energy function EFxk declines over time.

If xk+10, solving the optimization problem (26), the optimal variables obtained are denoted by Vk+1=vk+1;;vk+1+NC, εk+1=ε1k+1;;εmk+1, and the optimal state sequence is denoted by Xk+1=xk+2;;xk+1+NP, and the optimal output sequence is denoted by Yk+1=yk+2;;yk+1+NP. Similarly, the optimization result will satisfy that xk+1>xk+2xk+1+NP0 and yk+1>yk+2yk+1+NP0). Under the control of the MPC controller, the system state variables will changes to xk+2 in the next sampling interval, and we have EFxk+1>EFxk+2.

By analogy, if the state vector is not 0 vector, the energy function EFxk is going to go down over time under the control of the MPC controller.

4.5 Optimization solving program

The optimization problem (25) is a convex optimization problem with a convex quadratic objective function and multiple convex quadratic constraints which can be solved in many ways. Specifically, a convex optimization problem can be sort out as the following general form.

minfxks.t.gixk0,i=1,,mhjxk=0,j=1,,n(27)

where xk is the set of optimization variables, and fxk is the objective function of the convex optimization problem. gixk and hjxk represent inequality constraints and equality constraints of the convex optimization problem, respectively. The Lagrange function is defined as:

Lxk,λi,μj=fxk+i=1mλigixk+j=1nμjhjxk(28)

where λi and μj are called Lagrange multipliers. The optimal solution of convex optimization problem (27) can be obtained by solving the KKT conditions (Xu et al., 2001). as follows.

Lxk=0,k=1,,KLμj=0,j=1,,Jλigixk=0,i=1,,mλi0,i=1,,mgixk0,i=1,,m(29)

In (29), equality constraints are used to solve the optimal solution, and inequality constraints are used to verify the optimal solution. It is worth mentioning that in addition to the above method, there are many solving methods (An, 2000) and mature commercial solvers for convex optimization problems. The commercial solvers (Gurobi optimization, 2023; IBM CPLEX Optimizer, 2023) can be used to solve convex optimization problems conveniently and quickly, without the need for users to write optimization programs.

In each sampling interval T, the actions of the MPC controller include measuring the system states, constructing and solving the optimization problem (823), and providing the optimal control variables (Vd and Vq) to the system. The flow of the MPC algorithm is shown in Figure 4.

FIGURE 4
www.frontiersin.org

FIGURE 4. The flow of the MPC algorithm.

5 Case study

5.1 Simulation description

The performance of the proposed active and reactive power coordinated control strategy is evaluated in this section by testing the tracking performance of the PMSG wind turbine to the active and reactive power step references. The references of active and reactive power are shown in Figure 5. In order to capture maximum wind energy, the active power reference remains at 2.5 MW unchanged. The grid voltage stays in the rated value at 0–0.2s and the reactive power reference is set as 0.1 MW at 0–0.2 s. While the grid voltage drops down to 50% of the rated value at 0.2 s and the duration is 0.6 s. According to the reactive current support requirements in grid codes [21], the reactive power reference is stepped from 0.1 MW to 1.35 MW at 0.2 s.

FIGURE 5
www.frontiersin.org

FIGURE 5. The active and reactive power step references of the PMSG wind turbine.

Three different scenarios are simulated in this section using MATLAB/Simulink.

S1: Active and reactive power are controlled using the MPC controller without coordinated restrictions and priority arrangement

S2: Active and reactive power are coordinately controlled using the MPC controller, which considers amplitude coordinated restrictions and priority arrangement of active and reactive power.

S3: Active and reactive power are coordinately controlled using the MPC controller, which considers amplitude coordinated restrictions and priority arrangement of active and reactive power. Meanwhile, the climbing coordinated restrictions of active and reactive power is considered.

S4: Active and reactive power are coordinately controlled using the PI controller, which considers amplitude coordinated restrictions and priority arrangement of active and reactive power.

The other conditions and parameters in the three simulated scenarios are the same. The parameters of the grid-side converter system are indicated in Table 1 (Yaramasu and Wu, 2014). The prediction horizon is set as five times control period T and the control horizon is set as four times control period T when simulating.

TABLE 1
www.frontiersin.org

TABLE 1. Parameters of the grid-side converter system.

5.2 Results and analysis

Figures 68 depict the power reference tracking results of the PMSG wind turbine in the three different scenarios. Due to the grid voltage droping down to 50% of the rated value at 0.2 s, the maximum apparent power of the PMSG wind turbine change from 3MW to 1.5 MW at 0.2 s. In Scenario S1, the active and reactive power coordinated restrictions and priority decisions are not considered. Regardless of the power grid status, the amplitude range and climbing range of active and reactive power are fixed and do not interfere with each other. Therefore, the PMSG wind turbine cannot guarantee reactive power output by reducing the active power output. Therefore, when the grid voltage drop, the reactive power of the PMSG wind turbine cannot meet the 1.35 MW reference which is the reactive power support requirement.

FIGURE 6
www.frontiersin.org

FIGURE 6. The power references tracking results of the PMSG wind turbine in the S1 scenario.

FIGURE 7
www.frontiersin.org

FIGURE 7. The power references tracking results of the PMSG wind turbine in the S2 scenario.

FIGURE 8
www.frontiersin.org

FIGURE 8. The power references tracking results of the PMSG wind turbine in the S3 scenario.

Amplitude coordinated restrictions and priority decisions of active and reactive power are considered in Scenario S2. When the grid voltage drops down to 50% of the rated value at 0.2s, the priority task of the PMSG wind turbine is to provide reactive power support for the grid voltage recovery, and of cause the reactive power priority is set higher. As shown in Figure 6, by reducing the amplitude of active power, the PMSG wind turbine can output 1.35 MW reactive power to meet the reactive power support requirements of the grid. That is why we say it is very necessary and meaningful to coordinately control the active and reactive power amplitude of the wind turbine under the background of grid support.

The proposed control strategy in this paper is simulated in Scenario 3 which considers amplitude and climbing coordinated restrictions and priority decisions between active and reactive power. Similarly to Scenario 2, the PMSG wind turbine can meet the reactive power support requirements of the grid when the grid voltage drops. The difference between Scenario 2 and Scenario 3 is that, the PMSG wind turbine shows a faster response speed in Scenario 3, which the dynamic time in Scenario 3 is 20 ms and it is 40 ms in Scenario 2. This demonstrates the superiority of the control strategy proposed in this paper.

Figures 9, 10 show the current climbing of the PMSG wind turbine in Scenario 2 and Scenario 3. It can be found that the active and reactive current climbing limit value of the PMSG wind turbine in Scenario 3 is larger than that in Scenario 2. The greater ability to climb allows the PMSG wind turbine to show faster response speed in response to a step change in the power reference value. The results explain why the PMSG wind turbine shows a faster response speed in Scenario 3. The simulation results verify that under the given apparent power/current climbing constraint, active and reactive power/current climbing coordinated restrictions allow PMSG wind turbines to perform a larger range of active and reactive power/current climbing.

FIGURE 9
www.frontiersin.org

FIGURE 9. The power climbing of the PMSG wind turbine in Scenario 2.

FIGURE 10
www.frontiersin.org

FIGURE 10. The power climbing of the PMSG wind turbine in Scenario 3.

The voltage of the grid-side converter is shown in Figure 11 when the PMSG wind turbine executes the proposed control strategy in Scenario 3. It is easy to see that the voltage amplitude does not exceed its maximum allowed value in the whole process. In addition, there are no sharp climb and spike in the voltage waveform, which can protect the grid-side converters and improve the electricity quality of the PMSG wind turbine. Hence, The voltage amplitude and climbing constraint model proposed in this paper is effective.

FIGURE 11
www.frontiersin.org

FIGURE 11. The voltage of the grid-side converter in Scenario 3.

The three-phase current of the grid-side converter is shown in Figure 12 when the PMSG wind turbine executes the proposed control strategy in Scenario 3. The rated peak value of single-phase current is 0.816 kA. It is easy to see that the amplitudes of the three-phase current do not exceed the rated peak value 0.816 kA in the whole process. In addition, there are no sharp climb and spike in the three-phase current waveforms, which can protect the grid-side converters and improve the electricity quality of the PMSG wind turbine. Hence, The current amplitude and climbing constraint model proposed in this paper is effective.

FIGURE 12
www.frontiersin.org

FIGURE 12. The three-phase current of the grid-side converter in Scenario 3.

Figure 13 shows the result of the PMSG wind turbine tracking a 3 MW step active power reference, which is simulated with different prediction horizons. As can be seen from Figure 13, when the prediction horizon is short (Np = 1), the output of the PMSG wind turbine exists the overshoot. This is because the MPC model in this paper contains constraints on the power climbing change. The active power output of the PMSG wind turbine has a large climbing in the early stage, and the climbing cannot be changed quickly after approaching the active power reference value, so overdrive occurs. When the prediction horizon is long, the MPC controller can predict the corresponding future multi-step power output under different control variables, and select the optimal control variable to avoid overshoot. It is worth mentioning that the longer the prediction horizon, the better the control effect. In the scenario, the control effect is exactly the same when Np = 5 as when Np = 9. It is worth mentioning that as the prediction horizon increases, the control effect will not get better. In the current scenario, the control effect is exactly the same when Np = 5 and Np = 9.

FIGURE 13
www.frontiersin.org

FIGURE 13. The active power references tracking results of the PMSG wind turbine under different prediction horizon.

In the proposed MPC based control strategy, the priority of active and reactive power can be flexibly arranged by setting the deviation coefficients rP and rQ in the objective function. The steady-state amplitude of active and reactive power at 0.2–0.4s in Scenario 3 are displayed in Table 2, which is simulated with different deviation coefficients rP and rQ. Due to the grid voltage drops of 50% at 0.2 s, the maximum apparent power of the PMSG wind turbine changes from 3MW to 1.5 MW. Under the given 1.5 MW apparent power constraint, different priority settings will result in different active and reactive power outputs. So that the PMSG wind turbine can operate in different modes such as giving priority to the active power support/output, giving priority to the reactive power support/output, and giving the same/close priority to the active power support and the reactive power support. The MPC controller can flexibly set the priority of active and reactive power, so that the proposed control strategy can be flexibly applicated in different grid support scenarios.

TABLE 2
www.frontiersin.org

TABLE 2. The steady-state amplitude of active and reactive power with different deviation coefficients.

Figures 14, 15 depict the power reference tracking results and the grid-side converter voltage of the PMSG wind turbine when the PMSG wind turbine is controlled by a PI controller in Scenario 4. It can be seen in Figure 14 that there are overshoots and steady-state errors existing when the PMSG wind turbine tracks the active power references. It is worth mentioning that increasing the integral parameter in the PI controller can eliminate steady-state errors, but can lead to larger overshoots. As can be seen in Figure 15, the grid-side converter voltage may exceed its rated value during the dynamic process, which may cause damage to the grid-side converter and degrade the power quality. In addition, the amplitudes of output power and the grid-side converter voltage continue to fluctuate during the steady state period. This means that the power quality of the PMSG wind turbine output is lower.

FIGURE 14
www.frontiersin.org

FIGURE 14. The power references tracking results of the PMSG wind turbine in the S4 scenario.

FIGURE 15
www.frontiersin.org

FIGURE 15. The voltage of the grid-side converter in Scenario 4.

As shown in Figures 813, the MPC based active and reactive power coordinated control strategy proposed in this paper can enable one of active power and reactive power (the one with higher priority) to track its references perfectly with zero steady-state error, zero overshoot and transient dynamic process. The steady-state power curve and the steady-state voltage curve are smooth straight lines. The power amplitude constraint, power climbing constraint, power priority arrangement, voltage amplitude constraint and voltage ramp constraint set in the proposed control strategy have achieved the expected results. That is because the MPC controller is good at dealing with multi-input and multi-output control problems with complex constraints and specific objectives. The above complex constraints and specific objectives are difficult to implement by PI controllers.

6 Conclusion

In this paper, an MPC based active and reactive power coordinated control strategy is proposed to enhance the power control performance and grid support capability of PMSG wind turbines. Firstly, the constraint conditions in the MPC controller are constructed which include amplitude and climbing coordinated restrictions between active and reactive power, voltage amplitude and climbing constraints of grid-side converters. These constraint conditions enable PMSG wind turbines to perform a wider range of active and reactive power amplitude and climbing, and a smoother output voltage waveform. Then, an objective function is constructed to minimize the deviation of active and reactive power from their reference values. By setting the deviation coefficients in the objective function, the priority of active power output and reactive power output can be flexibly arranged. So that PMSG wind turbines can meet the power output requirements in different grid support scenarios. In the end, the simulation results show that the proposed control strategy can make PMSG wind turbines achieve excellent power control performance and thus better meet the requirements of power grid support. In the future, the influences of sampling delay and MPC calculation delay on the proposed control strategy will be analyzed and the proposed control strategy will be improved by using delay compensation technology.

Data availability statement

The original contributions presented in the study are included in the article/Supplementary Material, further inquiries can be directed to the corresponding author.

Author contributions

XM proposed the idea and carried out the model establishment, simulation experiment, result analysis, meanwhile he wrote the first draft. JY assisted in establishment of model and improvement of the idea. PY was in charge of knowledge coaching and error correction. PW is responsible for data collection, analysis, and processing and assisted in result analysis. PZ helped the revision of the manuscript and typeset the manuscript.

Funding

This work was supported by Key-Area Research and Development Program of Guangdong Province (2021B0101230003), and The Research Project of Digital Grid Research Institute, China Southern Power Grid (670000KK52220011).

Conflict of interest

The authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest.

Publisher’s note

All claims expressed in this article are solely those of the authors and do not necessarily represent those of their affiliated organizations, or those of the publisher, the editors and the reviewers. Any product that may be evaluated in this article, or claim that may be made by its manufacturer, is not guaranteed or endorsed by the publisher.

References

An, L. T. H. (2000). An efficient algorithm for globally minimizing a quadratic function under convex quadratic constraints. Math. Program. Ser. B 87, 401–426. doi:10.1007/s101070050003

CrossRef Full Text | Google Scholar

Dong, S., Wang, Y., and Li, H. (2012). Coordinated control for active and reactive power of PMSG-based wind turbine to enhance the LVRT capability. 2012 15th int. Conf. Electr. Mach. Syst., (ICEMS), 33–36.

Google Scholar

Feltes, C., Engelhardt, S., Kretschmann, J., Fortmann, J., Koch, F., and Erlich, I. (2009). Comparison of the grid support capability of DFIG-based wind farms and conventional power plants with synchronous generators. 2009 IEEE power energy soc. Gen. Meet., 1–7. doi:10.1109/PES.2009.5275441

CrossRef Full Text | Google Scholar

Gaied, H., Naoui, M., Kraiem, H., Goud, B. S., Flah, A., Alghaythi, M. L., et al. (2022). Comparative analysis of MPPT techniques for enhancing a wind energy conversion system. Front. Energy Res. 10, 1–15. doi:10.3389/fenrg.2022.975134

CrossRef Full Text | Google Scholar

Guo, L., Ren, Y., Wang, Z., Zhu, X., Wang, X., Li, X., et al. (2021). Double-layer feedback control method for synchronized frequency regulation of PMSG-based wind farm. IEEE Trans. Sustain. Energy 12, 2423–2435. doi:10.1109/TSTE.2021.3096724

CrossRef Full Text | Google Scholar

Gurobi optimization (2023). Gurobi. Available at: http://www.gurobi.com (Accessed Feb, 2023).

Google Scholar

Hansen, A. D., Sørensen, P., Iov, F., and Blaabjerg, F. (2006). Grid support of a wind farm with active stall wind turbines and AC grid connection. Wind Energy 9, 341–359. doi:10.1002/we.176

CrossRef Full Text | Google Scholar

IBM CPLEX Optimizer (2023). High-performance mathematical programming solver for linear programming, mixed integer programming, and quadratic programming. Available at: https://www.ibm.com/cn-zh/analytics/cplex-optimizer (Accessed Feb, 2023).

Google Scholar

Khazaei, J., Nguyen, D. H., and Asrari, A. (2020). Consensus-based demand response of PMSG wind turbines with distributed energy storage considering capability curves. IEEE Trans. Sustain. Energy 11, 2315–2325. doi:10.1109/TSTE.2019.2954796

CrossRef Full Text | Google Scholar

Li, Q., Ren, B., Li, Q., Wang, D., Tang, W., Meng, J., et al. (2022). Virtual inertial control strategy based on fuzzy logic algorithm for PMSG wind turbines to enhance frequency stability. Front. energy Res. 10, 1–9. doi:10.3389/fenrg.2022.907770

CrossRef Full Text | Google Scholar

Li, S., Haskew, T. A., Swatloski, R. P., and Gathings, W. (2012). Optimal and direct-current vector control of direct-driven PMSG wind turbines. IEEE Trans. Power Electron. 27, 2325–2337. doi:10.1109/TPEL.2011.2174254

CrossRef Full Text | Google Scholar

Liu, Y., Gracia, J. R., King, T. J., and Liu, Y. (2015). Frequency regulation and oscillation damping contributions of variable-speed wind generators in the U.S. Eastern interconnection (EI). IEEE Trans. Sustain. Energy 6, 951–958. doi:10.1109/TSTE.2014.2318591

CrossRef Full Text | Google Scholar

Maaoui-Ben Hassine, I., Naouar, M. W., and Mrabet-Bellaaj, N. (2016). Predictive control strategies for wind turbine system based on permanent magnet synchronous generator. ISA Trans. 62, 73–80. doi:10.1016/j.isatra.2015.12.002

PubMed Abstract | CrossRef Full Text | Google Scholar

Mayne, D. Q. (2014). Model predictive control: Recent developments and future promise. Automatica 50, 2967–2986. doi:10.1016/j.automatica.2014.10.128

CrossRef Full Text | Google Scholar

Mishra, R., and Saha, T. K. (2020). Performance analysis of model predictive technique based combined control for PMSG-Based distributed generation unit. IEEE Trans. Ind. Electron. 67, 8991–9000. doi:10.1109/TIE.2020.2992970

CrossRef Full Text | Google Scholar

Moghadasi, A., and Sarwat, A. I. (2015). Optimal analysis of resistive superconducting fault current limiters applied to a variable speed wind turbine system. Conf. Proc. - IEEE S., 1–7. doi:10.1109/SECON.2015.7132944

CrossRef Full Text | Google Scholar

Mohseni, M., and Islam, S. M. (2012). Review of international grid codes for wind power integration: Diversity, technology and a case for global standard. Renew. Sustain. Energy Rev. 16, 3876–3890. doi:10.1016/j.rser.2012.03.039

CrossRef Full Text | Google Scholar

Musarrat, N., Islam, R., Member, S., Muttaqi, K. M., and Member, S. (2019). Enhanced frequency support from a PMSG-based wind energy conversion system integrated with a high temperature SMES in standalone power supply systems. IEEE Trans. Appl. Supercond. 29, 1–6. doi:10.1109/tasc.2018.2882429

CrossRef Full Text | Google Scholar

National Energy Administration (2023). Transcript of the online press conference of the National Energy Administration in the fourth quarter of 2022. Available at: http://www.nea.gov.cn/2022-11/14/c_1310676392.htm (Accessed Feb, 2023).

Google Scholar

Nguyen, T. H., Lee, D. C., Van, T. L., and Kang, J. H. (2013). Coordinated control of reactive power between STATCOMs and wind farms for PCC voltage regulation. J. Power Electron. 13, 909–918. doi:10.6113/JPE.2013.13.5.909

CrossRef Full Text | Google Scholar

Okedu, K. E. (2022). Improving the performance of PMSG wind turbines during grid fault considering different strategies of fault current limiters. Front. Energy Res. 10, 1–12. doi:10.3389/fenrg.2022.909044

CrossRef Full Text | Google Scholar

Peng, Y., Li, Y., Lee, K. Y., Tan, Y., Cao, Y., Wen, M., et al. (2021). Coordinated control strategy of pmsg and cascaded H-bridge STATCOM in dispersed wind farm for suppressing unbalanced grid voltage. IEEE Trans. Sustain. Energy 12, 349–359. doi:10.1109/TSTE.2020.2995457

CrossRef Full Text | Google Scholar

Qin, S. J., and Badgwell, T. A. (2003). A survey of industrial model predictive control technology. Control Eng. Pract. 11, 733–764. doi:10.1016/S0967-0661(02)00186-7

CrossRef Full Text | Google Scholar

Rodriguez, J., Cortes, P., Kennel, R., and Kazmierkowski, M. P. (2009). Model predictive control - a simple and powerful method to control power converters. IEEE Trans. Ind. Electron. 56, 41–49. doi:10.1109/IPEMC.2009.5289335

CrossRef Full Text | Google Scholar

Shehata, E. G. (2017). A comparative study of current control schemes for a direct-driven PMSG wind energy generation system. Electr. Power Syst. Res. 143, 197–205. doi:10.1016/j.epsr.2016.10.039

CrossRef Full Text | Google Scholar

Sheng, Y., Li, C., Jia, H., Liu, B., Li, B., and Coombs, T. A. (2021). Investigation on FRT capability of PMSG-based offshore wind farm using the SFCL. IEEE Trans. Appl. Supercond. 31, 2021–2024. doi:10.1109/TASC.2021.3091054

CrossRef Full Text | Google Scholar

Tan, Y., Member, S., Muttaqi, K. M., Member, S., Ciufo, P., Member, S., et al. (2017). Enhanced frequency response strategy for a PMSG-based wind energy conversion system using ultracapacitor in remote area power supply systems. IEEE Trans. Ind. Appl. 53, 549–558. doi:10.1109/tia.2016.2613074

CrossRef Full Text | Google Scholar

Tripathi, S. M., Tiwari, A. N., and Singh, D. (2019). Low-voltage ride-through enhancement with the ω and T controls of PMSG in a grid-integrated wind generation system. IET Gener. Transm. Distrib. 13, 1979–1988. doi:10.1049/iet-gtd.2018.6275

CrossRef Full Text | Google Scholar

Vazquez, S., Leon, J., Franquelo, L., Rodriguez, J., Young, H., Marquez, A., et al. (2014). Model predictive control. IEEE Ind. Electron. Mag. 8, 91–94. doi:10.1007/978-3-319-91707-8_12

CrossRef Full Text | Google Scholar

Venkat, A. N., Hiskens, I. A., Rawlings, J. B., and Wright, S. J. (2008). Distributed MPC strategies with application to power system automatic generation control. IEEE Trans. Control Syst. Technol. 16, 1192–1206. doi:10.1109/TCST.2008.919414

CrossRef Full Text | Google Scholar

Wu, Z., Gao, D. W., Member, S., Zhang, H., Yan, S., and Wang, X. (2017). Coordinated control strategy of battery energy storage system and PMSG-WTG to enhance system frequency regulation capability. IEEE Trans. Sustain. Energy 8, 1330–1343. doi:10.1109/tste.2017.2679716

CrossRef Full Text | Google Scholar

Xu, Y., Wang, W., and Gao, Z. (2001). The algorithm of sequential KKT equations by nonmonotone search for arbitrary initial point. Comput. Optim. Appl. 18, 221–232. doi:10.1023/A:1011281102385

CrossRef Full Text | Google Scholar

Yan, Z., Chen, M., Zhen, X., Li, X., and Wubin, W. (2016). An experimental system for LVRT of direct-drive PMSG wind generation system. 2016 IEEE 8th int. Power electron. Motion control conf. Hefei: IPEMC-ECCE Asia 2016, 1452–1456. doi:10.1109/IPEMC.2016.7512505

CrossRef Full Text | Google Scholar

Yaramasu, V., and Wu, B. (2014). Predictive control of a three-level boost converter and an NPC inverter for high-power PMSG-based medium voltage wind energy conversion systems. IEEE Trans. Power Electron. 29, 5308–5322. doi:10.1109/TPEL.2013.2292068

CrossRef Full Text | Google Scholar

You, R., Barahona, B., Chai, J., and Cutululis, N. A. (2015). Frequency support capability of variable speed wind turbine based on electromagnetic coupler. Renew. Energy 74, 681–688. doi:10.1016/j.renene.2014.08.072

CrossRef Full Text | Google Scholar

Zeng, C., Yang, B., Cao, P., Li, Q., Deng, J., and Tian, S. (2022). Current status, challenges, and trends of maximum power point tracking for PV systems. Front. Energy Res. 10, 1–5. doi:10.3389/fenrg.2022.901035

CrossRef Full Text | Google Scholar

Zhang, B., Hu, W., Hou, P., Soltani, M., and Chen, Z. (2016). “Coordinated power dispatch of a PMSG based wind farm for output power maximizing considering the wake effect and losses,” in 2016 IEEE power energy soc. Gen. Meet. (PESGM), 1–5. doi:10.1109/PESGM.2016.7741738

CrossRef Full Text | Google Scholar

Zhong, C., Lv, Y., Zhou, Y., and Li, H. (2021). An equivalent rotor speed compensation control of PMSG-based wind turbines for frequency support in islanded microgrids. Front. energy Res. 9, 1–13. doi:10.3389/fenrg.2021.717327

CrossRef Full Text | Google Scholar

Keywords: grid support, permanent magnet synchronous generator (PMSG) wind turbine, active and reactive power coordinated control strategy, model predictive control (MPC), amplitude and climbing

Citation: Ma X, Yu J, Yang P, Wang P and Zhang P (2023) An MPC based active and reactive power coordinated control strategy of PMSG wind turbines to enhance the support capability. Front. Energy Res. 11:1159946. doi: 10.3389/fenrg.2023.1159946

Received: 06 February 2023; Accepted: 17 April 2023;
Published: 09 May 2023.

Edited by:

Taeseong Kim, Technical University of Denmark, Denmark

Reviewed by:

Alan Wai Hou Lio, Technical University of Denmark, Denmark
Liansheng Huang, Chinese Academy of Sciences (CAS), China

Copyright © 2023 Ma, Yu, Yang, Wang and Zhang. This is an open-access article distributed under the terms of the Creative Commons Attribution License (CC BY). The use, distribution or reproduction in other forums is permitted, provided the original author(s) and the copyright owner(s) are credited and that the original publication in this journal is cited, in accordance with accepted academic practice. No use, distribution or reproduction is permitted which does not comply with these terms.

*Correspondence: Ping Yang, ZXBweWFuZ0BzY3V0LmVkdS5jbg==

Disclaimer: All claims expressed in this article are solely those of the authors and do not necessarily represent those of their affiliated organizations, or those of the publisher, the editors and the reviewers. Any product that may be evaluated in this article or claim that may be made by its manufacturer is not guaranteed or endorsed by the publisher.