Skip to main content

ORIGINAL RESEARCH article

Front. Energy Res., 13 January 2022
Sec. Smart Grids

A Control Parameters Design Method With Multi-Constrains for an LCL-Filtered Grid-Connected Inverter in a Weak Grid

Fuyun WuFuyun Wu1Zhuang SunZhuang Sun2Weiji XuWeiji Xu2Zhizhou LiZhizhou Li2Jianguo Lyu
Jianguo Lyu2*
  • 1College of Mechanical and Electrical Engineering, Sanjiang University, Nanjing, China
  • 2School of Automation, Nanjing University of Science and Technology, Nanjing, China

Under weak grid conditions, the variation of the grid impedance will affect the steady-state and dynamic performance of the LCL-filtered grid-connected inverter and even make the inverter unstable. To ensure the system stability and further improve the dynamic performance in a weak grid, a control parameter design method with multi-constrains considering the system bandwidth for the current controller and active damping is proposed in this paper. First, based on the current controller and active damping with only grid current feedback, the effects of control parameters and grid impedance on the LCL resonant suppression and the performance of the inverter are analyzed. Moreover, the parameter constraints of the controllers are derived considering the grid impedance, including stability, resonance suppression, and margin constraints. Furthermore, as the system bandwidth affects the dynamic performance of the inverter, combined with the obtained multi-constraints, the optimal control parameters are determined by achieving the maximum bandwidth of the system against the impedance variation. Compared with other two methods, when the proposed method is applied, the system can operate with a better dynamic and steady-state performance. Finally, experiments are performed on a 2 kW three-phase grid-connected inverter in the weak grid, which verify the effectiveness of the parameter design method proposed in this paper.

1 Introduction

Currently, distributed power generation systems based on renewable energy have been widely used in power grids (Zhang et al., 2021; Li et al., 2021), and the three-phase grid-connected inverter with an LCL or L filter, as an important interface between the distributed generation system and the grid, plays an important role in it (Busada et al., 2005; Wu and Lehn, 2006; Malinowski and Bernet, 2008; Xin et al., 2017; Xing et al., 2018).

Although the LCL filter has better performance and switching harmonic attenuation ability than the L filter (Lindgren and Svensson, 1998; Hava et al., 1995), the inherent resonance problem of the LCL filter is harmful to the quality of grid current and even affects the stability of the system (Parker and McGrath, 2012). Compared with passive damping solutions proposed in Liserre et al. (2005), Dannehl et al. (2011) that cause non-negligible power loss, the active damping (AD) method is more flexible and efficient. In the literature (Jiao and Lee, 2015), an RLC damping circuit for the LCL filter is investigated to solve the resonant frequency peak of an LCL grid-connected inverter, which is equivalent to an AD control method essentially. The literature (Pena-Alzola et al., 2014) proposes an AD method by adding a notch filter to the forward channel for canceling the LCL filter resonant peak, but its robustness should be improved, and the parameter adjustment is relatively complex. The literature (Dannehl et al., 2010; Chenlei Bao et al., 2014; Wang et al., 2015) proposes AD algorithms with three different kinds of feedback signals, which are the filter capacitor current, the filter capacitor voltage, and the grid-side current. In order to decrease power losses caused by multiple sensors and reduce the system cost, the grid-current-feedback AD method is adopted in Xu et al. (2013a), Zhou et al. (2018). Meanwhile, a proportional resonant (PR) controller is preferred to provide suitable power quality to the grid for the inverter, which can significantly increase the gain at the intended frequency, track of the sinusoidal waveform with zero steady-state error, and have better disturbance rejection capability (Holmes et al., 2017; Zmood and Holmes, 2003). According to the method in Liu et al. (2020), a parameter range can be obtained for the PR controller and AD loop, which could ensure the grid current quality and system stability under ideal grid conditions.

However, due to the direct interconnection with power grids, system control performance and stability may be affected by weak grid conditions, for example, gird impedance variation (Sun, 2011). It is known that grid impedance can lead to sustained harmonic resonance or other instability problems, which destabilizes the grid-connected inverter (Liserre et al., 2006). Furthermore, the wide-range variation of the grid impedance may affect the resonant suppression for the LCL filter in a weak grid (Liu et al., 2020; Xu et al., 2013b). Therefore, it is necessary to design the control parameters reasonably considering grid impedance in the weak grid.

The existing approaches have been proposed to maintain the grid-connected inverter work normally and stably under weak grid conditions. The literature (Sun, 2011) proposed a method to determine inverter-grid system stability using the inverter output impedance and the grid impedance. It is shown that a grid-connected inverter system will remain stable if the ratio between the grid impedance and the inverter output impedance satisfies the Nyquist stability criterion. Then, based on the impedance-based stability criterion for grid-connected inverters, the literature (Cespedes and Sun, 2014a; Yang et al., 2014; Xu et al., 2018; Zhu et al., 2020) proposed different methods to ensure the stable operation of the grid-connected inverter system in the weak grid. However, this analysis method based on the impedance-based stability criterion needs to design the parameters in advance for the stable operation of the grid-connected inverter system, without considering the grid impedance. Moreover, this method is normally used to analyze the stability of the grid-connected inverter in the weak grid, in which the analysis of the dynamic performance is not considered. In addition, other scholars proposed a control strategy by the grid impedance detection technique to eliminate the impact of the grid impedance on the grid-connected inverter system (Liserre et al., 2007; Cespedes and Sun, 2014b). Although the automatic adaptive control technology based on the grid impedance online measurement can improve the adaptability of the grid-connected inverter system to the weak grid effectively, and the harmonics injected during impedance detection will deteriorate the quality of grid currents. Besides, the control performance of the inverter system depends on the rapidity and accuracy of the grid impedance online measurement, and the dynamic performance of system is still not well addressed.

Above all, under the weak grid, the multi-constrains including stability constraints, resonance suppression constraints, and margin constraints have not been considered to design the current controller and active damping loop comprehensively in these solutions, which determine stability, grid-current quality, and dynamic and steady-state performance of the inverter. Furthermore, considering the variation of grid impedance, the impact of grid impedance on the bandwidth of the inverter system should also be concerned, which also affects the dynamic performance of the system.

In this paper, aiming at improving the dynamic and stability performance of the three-phase LCL-filtered grid-connected inverter with a good quality of the grid current in the weak grid, a parameter design method for the current controller and active damping with grid-side current feedback is proposed in this paper. In Section 2, the mathematical model of the three-phase LCL-filtered grid-connected inverter in the weak grid is established. The influence of the PR controller and the active damping circuit on the resonance peak suppression of the LCL filter and the stability of the inverter under weak grid conditions are analyzed. In Section 3, the parameter constraints of the current controller and active damping loop are analyzed in the weak grid, including stability, resonance suppression, and margin constraints. In Section 4, based on the derived multi-constraints, a parameter design method for the active damping and current controller is proposed, which can achieve the maximum bandwidth of the inverter considering the impedance variation so that the system can operate with a good dynamic and steady-state performance. The experimental results in Section 5 verify the effectiveness of the parameter design method proposed in this paper.

2 Modeling and Control of the LCL-Filtered Grid-Connected Inverter in the Weak Grid

Figure 1 shows the main circuit of the three-phase LCL-filtered grid-connected inverter under the weak grid. L1x (x = a,b,c) are LCL filter inverter-side three-phase inductors, whose value is L1. Cx (x = a,b,c) are LCL filter three-phase capacitors, whose value is C1. L2x (x = a,b,c) are LCL filter grid-side three-phase inductors, whose value is L2. The weak grid consists of ideal voltage sources ex (x = a,b,c) and inductive grid impedances Lgx (x = a,b,c), and the value of grid impedance is Lg. uix (x = a,b,c) are inverter three-phase output voltages, i1x (x = a,b,c) are three-phase inverter-side currents of the LCL filter, and i2x (x = a,b,c) are three-phase grid-side currents of the filter. Vdc is the dc-bus voltage.

FIGURE 1
www.frontiersin.org

FIGURE 1. Main circuit diagram of the three-phase LCL-filtered grid-connected inverter.

In the two-phase static coordinate system (αβ), the closed-loop control block diagram of the three-phase LCL-filtered grid-connected inverter is shown in Figure 2, where Kpwm = Vdc/2 is the gain of the PWM inverter. Gc(s) is the proportional resonance controller expressed as

Gc(s)=Kp+Kr2ωiss2+2ωis+ωo2(1)

where Kp and Kr are the proportional gain and the resonant gain of the PR controller, ωi is the cut-off angular frequency of the PR controller, and ωo is the grid fundamental angular frequency (Chenlei Bao et al., 2014).

FIGURE 2
www.frontiersin.org

FIGURE 2. Closed loop control block diagram of the grid-connected inverter in the αβ coordinate system.

Gad(s) is the transfer function of the AD loop. Considering the complexity of the AD loop which affects the characteristic of three-phase LCL-filtered grid-connected inverter in the low-frequency range, Gad(s) is implemented by a second-order differential term in the s-domain (Liu et al., 2020). Gad(s) can be expressed as

Gad(s)=kads2(2)

where kad is the AD coefficient.

GD(s) is the transfer function of the total delay due to digital control, consisting of the computation delay, the zero-order holder, and the sampling switch. Considering that the computation delay may reduce the control loop bandwidth and make the system unstable, a previously reported time-delay compensator (Lu et al., 2018), as a first-order digital filter with a phase-lead characteristic, is directly adopted to mitigate time delay here. GD(s) is expressed as

GD(s)=1Ts1esTss11+0.5sTs(3)

where Ts is the sampling period.

The transfer function from ui(s) to i2(s) for the LCL filter can be derived as

G1(s)=i2(s)ui(s)=1C1L1(L2+Lg)s(s2+ωres2)(4)
ωres=L1+L2+LgC1L1(L2+Lg)(5)

where ωres is defined the resonant frequency when grid impedance Lg is considered.

Generally, the resonant gain Kr of the PR controller can be neglected at the cutoff frequency ωc and the frequencies higher than ωc (Chenlei Bao et al., 2014; Geng et al., 2018). Hence, in the process of analyzing system stability, the current controller Gc(s) can be approximated as Kp. From (14), the open-loop transfer function of the system can be derived as

Gop(s)=Gc(s)G1(s)KPWM1+0.5sTs+G1(s)KPWMkads2(6)

In order to analyze the influence of the PR controller and the active damping loop on the resonance peak suppression of the LCL filter and the stability of the inverter under weak grid conditions, Figure 3 shows the Bode diagram of the open-loop transfer function of the system. LCL filter parameters are shown in Table 1, where fs is the sampling frequency.

FIGURE 3
www.frontiersin.org

FIGURE 3. Bode diagram of the system open-loop transfer function. (A)Kp = 0.025, kad = 2 × 10–9. (B) Kp = 0.04, kad = 2 × 10–9. (C) Kp = 0.025, kad = 1 × 10–9.

TABLE 1
www.frontiersin.org

TABLE 1. Parameters of the LCL filter.

From Figure 3A, it can be seen that when Kp = 0.025 and kad = 2 × 10–9, the system can maintain stable under different Lg conditions. Supposing that Kp is modified to 0.04, as shown in Figure 3B, when Lg increases, the gain margin (GM) of the system changes from positive to negative, and the grid-connected inverter becomes unstable. Otherwise, supposing that kad is modified to 1 × 10–9, as shown in Figure 3C, when Lg increases, the GM of the system also changes from positive to negative, which means that the grid-connected inverter becomes unstable. Besides, when Lg varies, the resonant frequency of the system will shift, which affects the ability of the LCL resonant suppression. Another problem worthy of attention is that the bandwidth of the open-loop transfer function decreases with the increase of Lg. Taking Lg = 3 mH as an example, the bandwidth of the system is close to fundamental frequency, which may not maintain the inverter a good dynamic performance (Dorf and Bishop, 2011).

Above all, both the control parameters and Lg affect the ability of the LCL resonant suppression and the performance of the LCL grid-connected inverter. Therefore, in order to ensure the stable operation of the system and improve the dynamic performance under the weak grid, a multi-constrain parameter design method for the active damping loop and current controller considering system bandwidth is proposed in Sections 3, 4.

3 Constraints of Active Damping and the Current Controller for the LCL-Filtered Grid-Connected Inverter

3.1 Stability, Resonance Suppression, and Gain Margin Constraints with the Variation of Grid Impedance

In order to ensure the effective operation of the LCL grid-connected inverter and make it have better stability and dynamic response performance, the parameters of the current controller and active damping loop for the grid-connected inverter need to meet certain constraints.

Based on (6), by the Routh-Hurwitz criterion, the constrain to ensure the system stability is

0<Kp<Kp1(kad,Lg)(7)

where

Kp1(kad,Lg)=kad(L1+L2+Lg)C1L1(L2+Lg)(8)

Due to the existence of the delay GD(s), the resonant frequency ωres of the LCL filter will shift after adding the active damping control loop, note that as ωres'. Figure 4 can be obtained by equivalent transformation of Figure 2. With this representation, it immediately informs that a virtual impedance Zeq in parallel with filter capacitor C1 is introduced by the AD control loop. Zeq can be expressed as

Zeq(s)=L1(L2+Lg)(1+0.5sTs)KPWMkad(9)

FIGURE 4
www.frontiersin.org

FIGURE 4. Equivalent closed loop control block diagram of the grid-connected inverter in the αβ coordinate system.

Figure 5 shows the equivalent physical circuit of the LCL filter, where Zeq = Req//Xeq. Substitute s = into (9), the expressions of Req and Xeq are given in (10)

Req=L1(L2+Lg)(1+0.25ω2Ts2)KPWMkadXeq=L1(L2+Lg)(1+0.25ω2Ts2)0.5ωTsKPWMkad(10)

FIGURE 5
www.frontiersin.org

FIGURE 5. Equivalent virtual impedance of active damping.

From Figure 5, the expression of ωres of the system after adding active damping is

ωres=2kadKPWMTs4C1L1(L2+Lg)+(L1+L2+Lg)Ts2+A2Ts2C1L1(L2+Lg)(11)

where

A=16C1L1(L2+Lg)(L1+L2+Lg)Ts2      +(4C1L1(L2+Lg)2kadKPWMTs(L1+L2+Lg)Ts2)2(12)

Generally, the gain of Gop (s = ) should be less than 0dB at ωres, which maintains the suppression ability for the resonant peak. Through making 20lg|Gop (s = res)|≤0, Kp can be derived as

Kp<Kp2(kad,Lg)(13)

where

Kp2(kad,Lg)=x2+y2KPWMx=0.5C1L1(L2+Lg)Tsωres4(0.5(L1+L2+Lg)Ts+kadKPWM)ωres2y=(L1+L2+Lg)ωresC1L1(L2+Lg)ωres3(14)

Considering the phase of Gop (s = ) is −180° at crossing frequency ωh, Gop (s = ) is absolutely real at ωh. Making Im (Gop (s = )) = 0, the expression of ωh can be obtained as

ωh=L1+L2+LgC1L1(L2+Lg)(15)

The grid-connected inverter system needs to have a certain gain margin (GM) to ensure sufficient stability. We assume that the ideal gain margin is GM0 at ωh, which is generally 3dB (Guan et al., 2019). In order to ensure GM ≥ GM0, the gain margin constraint of Kp is

KpKp3(kad,Lg)(16)

where

Kp3(kad,Lg)=kad(L1+L2+Lg)C1L1(L2+Lg)10GM020(17)

In Etxegarai et al. (2012), the maximum value of the grid impedance Lg is expressed as

Lg_max=UsωoINSCR(18)

where Us is the root mean square of grid-connected voltage and IN is the root mean square of grid-connected current.

When the grid inductance Lg is in the range [0, Lg_max], in order to ensure that Kp simultaneously satisfies the three constraints in (7, 13, 16), Kp needs to be less than or equal to the minimum among them as

Kpmin{Kp1(kad,Lg),Kp2(kad,Lg),Kp3(kad,Lg)|0LgLg_max}(19)

which is

KpKp3(kad,Lg_max)(20)

3.2 Phase Margin Constraint With the Variation of Grid Impedance

In addition, the system also needs to meet the phase margin (PM) requirement for good stability and dynamic performance, and the expression of PM is

PM=180°+Gop(s=jωc)       =180°+arctanωc2ωres20.5Tsωc30.5Tsωcωres2kadKPWMωcC1L1(L2+Lg)(21)

Then, the AD coefficient kad can be expressed as

kad=0.5C1L1(L2+Lg)Tsωc20.5(L1+L2+Lg)TsKPWM+ωres2ωc2KPWMωctan(PM)(22)

Furthermore, the partial differential of kad with respect to PM is

kadPM=ωres2ωc2KPWMωc(1sin2PM)(23)

In order to make the system parameter design reasonable, the cut-off frequency ωc should be smaller than ωres. From (23), the active damping parameter kad and the phase margin PM are in a monotonically decreasing relationship.

We assuming that the ideal phase margin is PM0, which is generally 45°. In order to ensure PM ≥ PM0, combining (22) with (23), kad needs to meet

kadkad(Lg,ωc)(24)

where

kad(Lg,ωc)=0.5C1L1(L2+Lg)Tsωc20.5(L1+L2+Lg)TsKPWM                        +ωrec2ωc2KPWMωctan(PM0)(25)

The partial derivative of kad (Lg, ωc) with respect to Lg in (25) can be obtained

{kad(Lg,ωc)Lg0,ωo<ωc1C1L1kad(Lg,ωc)Lg<0,1C1L1<ωc<ωres(26)

According to (26), when 1/C1L1 <ωc<ωres, kad (Lg, ωc) decreases monotonously with respect to Lg; when ωo<ωc1/C1L1, kad (Lg, ωc) increases monotonously with respect to Lg. To make the phase margin of the system meet the requirements when Lg is in the range [0, Lg_max], kad needs to meet the following requirements:

{kadkad(0,ωc),ωo<ωc1C1L1kadkad(Lg_max,ωc),1C1L1<ωc<ωres(27)

Above all, the stability, resonance suppression, gain margin, and phase margin constraints with the variation of grid impedance are derived, ensuring that the system has a good performance while suppressing LCL resonance. Besides, under the weak grid, according to 7, 13, 16, and 25, the range of Kp is affected by kad and Lg, and the range of kad is affected by ωc and Lg. Considering the grid impedance Lg, the control parameters Kp and kad can be determined according to the requirements of the system for ωc which determines the bandwidth of the system.

4 Parameter Design for Active Damping and the Current Controller of the LCL-Filtered Grid-Connected Inverter

In order to maintain the grid-connected inverter, a good dynamic performance with the stability, resonance suppression, and gain margin and phase margin constraints in the weak grid, the bandwidth (ωc) of the system should be set to the maximal value considering the variation of the grid impedance.

According to the two cases in (27), Kp of the current controller and kad of the active damping loop are analyzed and solved at different ωc ranges.

4.1 Case I: 1/C1L1 <ωc<ωres

From (27), in this case, if the phase margin of the system meets the requirements when Lg is in the range [0, Lg_max], kad needs to meet

kadkad11(ωc)(28)

where

kad11(ωc)=kad(Lg_max,ωc)(29)

At ωc, the gain of the system open-loop transfer function equals to 1. By making |Gop (s = jωc)| = 1, Kp can be expressed as

Kp(kad,Lg,ωc)=m2+n2KPWM(30)

where

m=0.5C1L1(L2+Lg)Tsωc4(0.5(L1+L2+Lg)Ts+kadKPWM)ωc2n=(L1+L2+Lg)ωcC1L1(L2+Lg)ωc3(31)

and then when Lg = Lg_max, Kp = Kp(kad, Lg_max, ωc), Kp should also meet the constraint in (20) as

{Kp=Kp(kad,Lg_max,ωc)KpKp3(kad,Lg_max)(32)

By solving (32), kad also needs to meet

kadkad12(ωc)ωc<100.1GM4ωres(33)

where

kad12(ωc)=0.5C1L1(L2+Lg_max)2(C1L1L2ωc2L1L2Lg_max)                 ·(C1L1(L2+Lg_max)ωc3+B)ωc(C12L12(L2+Lg_max)2ωc4100.1GM(L1+L2+Lg_max)2)KPWMB=4C12L12(L2+Lg_max)2ωc4+100.1GM(L1+L2+Lg_max)2Ts2ωc2       +4100.1GM(L1+L2+Lg_max)2(34)

Substituting system parameters into (28, 33), when 1/C1L1 <ωc<ωres, we get

kad12(ωc)>kad11(ωc)(35)

Therefore, in this case, the active damping parameter kad that satisfies all constraints cannot be obtained.

4.2 Case II: ωo<ωc< 1/C1L1

Similar to the analysis in case I, if the phase margin of the system meets the requirements when Lg is in the range [0, Lg_max], kad needs to meet

kadkad21(ωc)(36)

where

kad21(ωc)=kad(0,ωc)(37)

and then when Lg = 0, Kp = Kp(kad, 0, ωc), Kp should also meet the constraint in (20) as

{Kp=Kp(kad,0,ωc)KpKp3(kad,Lg_max)(38)

By solving (38), kad also needs to meet

kadkad22(ωc)(39)

where

kad22(ωc)=0.5C1L1(L2+Lg_max)2(C1L1L2ωc2L1L2)·(C1L1(L2+Lg_max)ωc3+B)ωc(C12L12(L2+Lg_max)2ωc4100.1GM(L1+L2+Lg_max)2)KPWM(40)

Combining (37) with (40), the partial derivative of kad21 (ωc) and kad22 (ωc) with respect to Lg in (25) can be obtained

{kad21(ωc)ωc<0kad22(ωc)ωc>0(41)

It can be seen from (41) that kad21 (ωc) decreases monotonously with respect to ωc, and kad22 (ωc) increases monotonously with respect to ωc. By solving kad21 (ωc) = kad22 (ωc), the expressions of optimal active damping parameter kad_opt and optimal proportional gain Kp_opt can be derived as

{kad_opt=0.5C1L1L2Tsωc_max20.5(L1+L2)TsKPWM             +L1+L2C1L1L2ωc_max2KPWMωc_maxtan(PM)Kp_opt =kad_opt(L1+L2+Lg_max)C1L1(L2+Lg_max)10GM20(42)

According to (18, 42) and system parameters in Table 2, the values of kad_opt and Kp_opt are respectively

{kad_opt=5×10-9Kp_opt =0.05(43)

TABLE 2
www.frontiersin.org

TABLE 2. Parameters of the LCL grid-connected inverter.

Therefore, to maintain the system a good dynamic performance in the weak grid, considering the maximal bandwidth of the system in the weak grid, the optimal Kp and kad are derived from the stability, resonance suppression, and gain margin and phase margin constraints.

In order to realize digital control, it is necessary to discretize each part of the grid-connected inverter control system. Applying the ZOH z-transformation, the transfer function of the LCL filter in (4) can be given by

G1(z)=ωresTs(z22zcosωresTs+1)(z1)2sinωresTsωres(L1+L2+Lg)(z1)(z22zcosωresTs+1)(44)

By the Tustin method with pre-warping, the transfer function of the PR controller in (1) can be transformed to Gc(z), which can be derived as

Gc(z)=Kp+Krωisin(ωoTs)(z21)ωo(z22zcosωoTs+1)+ωisin(ωoTs)(z21)(45)

Gad(z) is the transfer function of the AD loop in the z-domain, by applying the backward-difference transformation to (2), Gad(z) can be described as

Gad(z)=kad(z1)2Ts2z2(46)

The expression of the open-loop transfer function of the LCL grid-connected inverter after discretization is

Gop(z)=Gc(z)KpwmG1(z)1+KpwmG1(z)Gad(z)(47)

Based on (43) and system parameters in Table 2, Figure 6 shows the Bode plot for Gop(z) with Lg variation. It can be seen that the system can remain stable and have a sufficient margin and the bandwidth of the system is relatively large. When Lg = 0 mH, Lg = 1.5 mH, and Lg = 3 mH, the bandwidths of the system are 320, 250, and 205 Hz, respectively.

FIGURE 6
www.frontiersin.org

FIGURE 6. Bode plot for Gop(z).

Compared with Figure 3, when the optimal parameters Kp and kad in (43) are applied considering the variation of Lg, not only can the constraint conditions in Section 3 be met to ensure the stable operation of the inverter but also a large bandwidth can be obtained to improve the dynamic performance.

5 Experimental Results

To verify the effectiveness of the parameter design method proposed in this paper under the weak grid, an experimental prototype of the three-phase LCL-filtered grid-connected inverter is built. The parameters of the experimental prototype are listed in Table 2. In the experimental platform, as shown in Figure 7A, a digital control system consists of a TMS320F28335 DSP and a EPM1270T CPLD. The DSP is applied for the implementation of the control algorithm mainly, which also completes the sampling of grid phase voltages and grid phase currents. Besides, the CPLD is used to arrange digital signals and realize protections for power switches. The photograph of the experimental platform is shown in Figure 7B, where the oscilloscope and power analyzer are Tektronix MDO3000 and HIOKI PW6001, respectively. By applying the proposed method and the methods in Jiao and Lee (2015) and Liu et al. (2020), comparisons of the experimental results are shown in Figures 813.

FIGURE 7
www.frontiersin.org

FIGURE 7. Schematic diagram and experimental photograph of the system. (A) Schematic diagram of the system. (B) Experimental photograph of the system.

FIGURE 8
www.frontiersin.org

FIGURE 8. Steady-state experimental waveforms of the inverter at Lg = 0 mH: (A) with the proposed method in this paper, (B) with the method in Liu et al. (2020), and (C) with the method in Jiao and Lee (2015).

FIGURE 9
www.frontiersin.org

FIGURE 9. Steady-state experimental waveforms of the inverter at Lg = 1.5 mH: (A) with the proposed method in this paper, (B) with the method in Liu et al. (2020), and (C) with the method in Jiao and Lee (2015).

FIGURE 10
www.frontiersin.org

FIGURE 10. Steady-state experimental waveforms of the inverter at Lg = 3 mH: (A) with the proposed method in this paper, (B) with the method in Liu et al. (2020), and (C) with the method in Jiao and Lee (2015).

FIGURE 11
www.frontiersin.org

FIGURE 11. Dynamic experimental results of the inverter at Lg = 0 mH: (A)) with the proposed method in this paper, (B) with the method in Liu et al. (2020), and (C) with the method in Jiao and Lee (2015).

FIGURE 12
www.frontiersin.org

FIGURE 12. Dynamic experimental results of the inverter at Lg = 1.5 mH: (A) with the proposed method in this paper, (B) with the method in Liu et al. (2020), and (C) with the method in Jiao and Lee (2015).

FIGURE 13
www.frontiersin.org

FIGURE 13. Dynamic experimental results of the inverter at Lg = 3 mH: (A) with the proposed method in this paper, (B) with the method in Ref. Liu et al. (2020), and (C) with the method in Jiao and Lee (2015).

Figures 810 (Lg = 0 mH, Lg = 1.5 mH, and Lg = 3 mH, respectively) show the steady-state experimental waveforms of the inverter against different grid impedances with the three methods, in which ia, ib, and ic are the three-phase grid currents and vpcca is the PCC voltage of phase A. It can be seen that when the grid impedance varies, the proposed method can achieve a better quality of grid currents for the inverter, and the THD of grid currents are 1.41, 1.66, and 1.63%, respectively, which satisfy the harmonic distortion standard (IEEE Recommended Practice and Requirements for Harmonic Control in Electric Power Systems, 2014) (IEEE Std. 519-2014) for the grid currents of the inverter. In addition, the THD result with the proposed method is lower than that with other two methods in Jiao and Lee (2015) and Liu et al. (2020) obviously.

Moreover, according to the THD results of the grid current, compared with other two methods in Ref Jiao and Lee (2015) and Liu et al. (2020), when the proposed method is applied, the resonance peak (at 850 Hz in Figure 8, 750 Hz in Figure 9, and 650 Hz in Figure 10) around the LCL resonant frequency is suppressed more effectively under different grid impedance conditions, especially when Lg is 3 mH in Figure 10.

Furthermore, to demonstrate the advantage of the proposed method against different grid impedances, Figures 1113 show the dynamic experimental waveforms of the inverter with the three methods when the current reference steps from half to full loads. In Figures 11A, 12A, 13A, supposing that Lg varies from 0 to 3 mH (0, 1.5, and 3 mH), the adjustment time Δt is 20, 23, and 31 ms, respectively, with the proposed method in this paper. The adjustment time with the other two methods in Jiao and Lee (2015) and Liu et al. (2020) is listed in Table 3, which shows the comparisons of the dynamic adjustment time with the three methods above. It can be seen that although the grid-connected inverter system can operate stably with the above three methods, the proposed method in this paper has a shorter adjustment time that is less than a fundamental frequency period against different grid impedances among the three methods.

TABLE 3
www.frontiersin.org

TABLE 3. Comparison of dynamic performances with the three methods.

Above all, according to comparisons of experimental results with the three methods against different grid impedances, the proposed method can obtain the optimal proportional gain Kp of the PR controller and the AD coefficient kad of the AD loop for the LCL-filtered grid-connected inverter system, which maintains that the inverter system achieves better grid current quality, and the resonance peak of the LCL filter is suppressed more effectively under weak grid conditions. Besides, the experimental results show that the dynamic adjustment time of the proposed method is shortened obviously, which illustrates a better dynamic performance of the grid-connected inverter system.

6 Conclusion

In order to improve the stability and dynamic performance of the three-phase LCL-filtered grid-connected inverter under the weak grid, based on the PR controller and active damping with only grid current feedback, a control parameter design method with multi-constrains considering system bandwidth for the inverter is proposed in this paper. According to the stability constraint, resonance suppression constraint, and margin constraint, the maximal bandwidth of the system with variation of Lg is considered, which can ensure a better dynamic performance of the grid-connected inverter under the weak grid. Besides, the proposed method realizes resonance suppression more effectively and maintains a better performance for the inverter, compared with other two methods. With the parameters obtained from the proposed method, the experimental results show the better dynamic performance of the LCL filter in the weak grid with different grid impedances as well as the better steady-state performance and more effective resonance suppression.

Data Availability Statement

The original contributions presented in the study are included in the article/Supplementary Material, further inquiries can be directed to the corresponding author.

Author Contributions

Theoretical promotion and manuscript edition, FW and JL; theoretical analysis and experiment, ZS and WX; simulation and analysis, ZL. All authors contributed to manuscript revision, read, and approved the submitted version.

Funding

This study was supported by the Natural Science Foundation of the Jiangsu Higher Education Institutions of China (Grant: 20KJB470029).

Conflict of Interest

The authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest.

Publisher’s Note

All claims expressed in this article are solely those of the authors and do not necessarily represent those of their affiliated organizations or those of the publisher, the editors, and the reviewers. Any product that may be evaluated in this article or claim that may be made by its manufacturer is not guaranteed or endorsed by the publisher.

References

Busada, C. A., Jorge, S. G., and Solsona, J. A. (2005). Resonant Current Controller with Enhanced Transient Response for Grid-Tied Inverters. IEEE Trans. Ind. Appl. 65 (4), 1281–1291.

Google Scholar

Cespedes, M., and Sun, J. (2014). Adaptive Control of Grid-Connected Inverters Based on Online Grid Impedance Measurements. IEEE Trans. Sustain. Energ. 5 (2), 516–523. doi:10.1109/tste.2013.2295201

CrossRef Full Text | Google Scholar

Cespedes, M., and Sun, J. (2014). Impedance Modeling and Analysis of Grid-Connected Voltage-Source Converters. IEEE Trans. Power Electron. 29 (3), 1254–1261.

CrossRef Full Text | Google Scholar

Chenlei Bao, C., Xuehua Wang, X., Donghua Pan, X., and Kailei, W. (2014). Step-by-Step Controller Design for LCL-type Grid-Connected Inverter with Capacitor-Current-Feedback Active-Damping. IEEE Trans. Power Electron. 29 (3), 1239–1253. doi:10.1109/tpel.2013.2262378

CrossRef Full Text | Google Scholar

Dannehl, J., Fuchs, F. W., Hansen, S., and Thøgersen, P. B. (2010). Investigation of Active Damping Approaches for PI-Based Current Control of Grid-Connected Pulse Width Modulation Converters with LCL Filters. IEEE Trans. Ind. Applicat. 46 (4), 1509–1517. doi:10.1109/tia.2010.2049974

CrossRef Full Text | Google Scholar

Dannehl, J., Liserre, M., and Fuchs, F. W. (2011). Filter-Based Active Damping of Voltage Source Converters with $LCL$ Filter. IEEE Trans. Ind. Electron. 58 (8), 3623–3633. doi:10.1109/tie.2010.2081952

CrossRef Full Text | Google Scholar

Dorf, R. C., and Bishop, R. H. (2011). Modern Control Systems. 12th ed. Upper Saddle River, NJ: Prentice-Hall.

Google Scholar

Etxegarai, A., Eguia, P., Torres, E., and Fernandez, E. (2012). Impact of Wind Power in Isolated Power Systems. In 2012 16th IEEE Mediterranean Electrotechnical Conference. Tunisia: Yasmine Hammamet, 63–66.

CrossRef Full Text | Google Scholar

Geng, Y., Yun, Y., Chen, R., Wang, K., Bai, H., and Wu, X. (2018). Parameters Design and Optimization for LC-type Off-Grid Inverters with Inductor-Current Feedback Active Damping. IEEE Trans. Power Electron. 33 (1), 703–715. doi:10.1109/tpel.2017.2664812

CrossRef Full Text | Google Scholar

Guan, Y., Wang, Y., Xie, Y., Liang, Y., Lin, A., and Wang, X. (2019). The Dual-Current Control Strategy of Grid-Connected Inverter with LCL Filter. IEEE Trans. Power Electron. 34 (6), 5940–5952. doi:10.1109/tpel.2018.2869625

CrossRef Full Text | Google Scholar

Hava, A. M., Lipo, T. A., and Erdman, W. L. (1995). Utility Interface Issues for Line Connected PWM Voltage Source Converters: a Comparative Study. In Proc.10th IEEE Appl. Power Electron. Conf. Expo. USA: TX, 125–132.

Google Scholar

Holmes, D. G., Lipo, T. A., McGrath, B., and Kong, W. Y. (2017). Optimized Design of Stationary Frame Three Phase Ac Current Regulator. IEEE Trans. Power Electron. 24 (11), 3216–3228.

Google Scholar

Ieee Recommended Practice and Requirements for Harmonic Control in Electric Power Systems (2014). IEEE Std 519-2014. (Revision of IEEE Std 519-1992), 3 Park Avenue. New York, USA.

Google Scholar

Jiao, Y., and Lee, F. C. (2015). LCL Filter Design and Inductor Current Ripple Analysis for a Three-Level NPC Grid Interface Converter. IEEE Trans. Power Electron. 30 (9), 4659–4668. doi:10.1109/tpel.2014.2361907

CrossRef Full Text | Google Scholar

Li, Y., Gao, W., Yan, W., Huang, S., Wang, R., Gevorgian, V., et al. (2021). Data-driven Optimal Control Strategy for Virtual Synchronous Generator via Deep Reinforcement Learning Approach. J. Mod. Power Syst. Clean. Energ. 9 (4), 919–929. doi:10.35833/mpce.2020.000267

CrossRef Full Text | Google Scholar

Lindgren, M., and Svensson, J. (1998). Control of a Voltage-Source Converter Connected to the Grid through an LCL-Filter-Application to Active Filtering. in Proc. PESC. Fukuoka, Japan, 229–235.

Google Scholar

Liserre, M., Blaabjerg, F., and Hansen, S. (2005). Design and Control of an LCL-Filter-Based Three-phase Active Rectifier. IEEE Trans. Ind. Applicat. 41 (5), 1281–1291. doi:10.1109/tia.2005.853373

CrossRef Full Text | Google Scholar

Liserre, M., Blaabjerg, F., and Teodorescu, R. (2007). Grid Impedance Estimation via Excitation of $LCL$-Filter Resonance. IEEE Trans. Ind. Applicat. 43 (5), 1401–1407. doi:10.1109/tia.2007.904439

CrossRef Full Text | Google Scholar

Liserre, M., Teodorescu, R., and Blaabjerg, F. (2006). Stability of Photovoltaic and Wind Turbine Grid-Connected Inverters for a Large Set of Grid Impedance Values. IEEE Trans. Power Electron. 21 (1), 263–272. doi:10.1109/tpel.2005.861185

CrossRef Full Text | Google Scholar

Liu, T., Liu, J., Liu, Z., and Liu, Z. (2020). A Study of Virtual Resistor-Based Active Damping Alternatives for LCL Resonance in Grid-Connected Voltage Source Inverters. IEEE Trans. Power Electron. 35 (1), 247–262. doi:10.1109/tpel.2019.2911163

CrossRef Full Text | Google Scholar

Lu, M., Wang, X., Loh, P. C., Blaabjerg, F., and Dragicevic, T. (2018). Graphical Evaluation of Time-Delay Compensation Techniques for Digitally Controlled Converters. IEEE Trans. Power Electron. 33 (3), 2601–2614. doi:10.1109/tpel.2017.2691062

CrossRef Full Text | Google Scholar

Malinowski, M., and Bernet, S. (2008). A Simple Voltage Sensorless Active Damping Scheme for Three-phase PWM Converters with an $LCL$ Filter. IEEE Trans. Ind. Electron. 55 (4), 1876–1880. doi:10.1109/tie.2008.917066

CrossRef Full Text | Google Scholar

Parker, S. G., and McGrath, B. P. (2012). Regions of Active Damping Control for LCL Filters. In Proc. IEEE Energy Convers. Congr. Expo. Raleigh, USA, 53–60. doi:10.1109/ecce.2012.6342412

CrossRef Full Text | Google Scholar

Pena-Alzola, R., Liserre, M., Blaabjerg, F., Ordonez, M., and Kerekes, T. (2014). A Self-Commissioning Notch Filter for Active Damping in a Three-phase LCL -Filter-Based Grid-Tie Converter. IEEE Trans. Power Electron. 29 (12), 6754–6761. doi:10.1109/tpel.2014.2304468

CrossRef Full Text | Google Scholar

Sun, J. (2011). Impedance-Based Stability Criterion for Grid-Connected Inverters. IEEE Trans. Power Electron. 26 (11), 3075–3078. doi:10.1109/tpel.2011.2136439

CrossRef Full Text | Google Scholar

Wang, X., Blaabjerg, F., and Loh, P. C. (2015). Grid-current-feedback Active Damping for LCL Resonance in Grid-Connected Voltage Source Converters. IEEE Trans. Power Electron. 31 (1), 213–223.

Google Scholar

Wu, E., and Lehn, P. W. (2006). Digital Current Control of a Voltage Source Converter with Active Damping of LCL Resonance. IEEE Trans. Power Electron. 21 (5), 1364–1373. doi:10.1109/tpel.2006.880271

CrossRef Full Text | Google Scholar

Xin, Z., Wang, X., Loh, P. C., and Blaabjerg, F. (2017). Grid-Current-Feedback Control for LCL-Filtered Grid Converters with Enhanced Stability. IEEE Trans. Power Electron. 32 (4), 3216–3228. doi:10.1109/tpel.2016.2580543

CrossRef Full Text | Google Scholar

Xing, X., Zhang, C., Chen, A., Geng, H., and Qin, C. (2018). Deadbeat Control Strategy for Circulating Current Suppression in Multiparalleled Three-Level Inverters. IEEE Trans. Ind. Electron. 65 (8), 6239–6249. doi:10.1109/tie.2017.2786234

CrossRef Full Text | Google Scholar

Xu, J., Xie, S., and Tang, T. (2013). Active Damping-Based Control for Grid-Connected LCL -filtered Inverter with Injected Grid Current Feedback Only. IEEE Trans. Ind. Electron. 61 (9), 4746–4758.

Google Scholar

Xu, J., Xie, S., and Tang, T. (2013). Evaluations of Current Control in Weak Grid Case for Grid‐connected LCL‐filtered Inverter. IET Power Elect. 6 (2), 227–234. doi:10.1049/iet-pel.2012.0192

CrossRef Full Text | Google Scholar

Xu, J., Xie, S., Zhang, B., and Qian, Q. (2018). Robust Grid Current Control with Impedance-phase Shaping for LCL-Filtered Inverters in Weak and Distorted Grid. IEEE Trans. Power Electron. 33 (12), 10240–10250. doi:10.1109/tpel.2018.2808604

CrossRef Full Text | Google Scholar

Yang, D., Ruan, X., and Wu, H. (2014). Impedance Shaping of the Grid-Connected Inverter with LCL Filter to Improve its Adaptability to the Weak Grid Condition. IEEE Trans. Power Electron. 29 (11), 5795–5805. doi:10.1109/tpel.2014.2300235

CrossRef Full Text | Google Scholar

Zhang, N., Sun, Q., Wang, J., and Yang, L. (2021). Distributed Adaptive Dual Control via Consensus Algorithm in the Energy Internet. IEEE Trans. Ind. Inf. 17 (7), 4848–4860. doi:10.1109/tii.2020.3031437

CrossRef Full Text | Google Scholar

Zhou, L., Zhou, J. M. X., Lv, Y. Z., He, Z., Wu, W., Yang, L., et al. (2018). Inverter-Current-Feedback Resonance-Suppression Method for LCL-type DG System to Reduce Resonance-Frequency Offset and Grid-Inductance Effect. IEEE Trans. Ind. Electron. 65 (9), 7036–7048. doi:10.1109/tie.2018.2795556

CrossRef Full Text | Google Scholar

Zhu, K., Sun, P., Zhou, L., Du, X., and Luo, Q. (2020). Frequency-Division Virtual Impedance Shaping Control Method for Grid-Connected Inverters in a Weak and Distorted Grid. IEEE Trans. Power Electron. 35 (8), 8116–8129. doi:10.1109/tpel.2019.2963345

CrossRef Full Text | Google Scholar

Zmood, D., and Holmes, D. (2003). Stationary Frame Current Regulation of PWM Inverters with Zero Steady-State Error. IEEE Trans. Power Electron. 18 (3), 3216–3228. doi:10.1109/tpel.2003.810852

CrossRef Full Text | Google Scholar

Nomenclature

AD active damping

C1 capacitor in the LCL filter

fs sampling frequency

G1 transfer function from ui(s) to i2(s) for the LCL filter

Gad transfer function of the AD loop

Gc proportional resonance controller

Gcl closed-loop transfer function of the system

GD total time delay model

GM gain margin

GM0 ideal gain margin

Gop open-loop transfer function of the system

i1 Inverter-side currents in the LCL filter

i2 grid-side currents in the LCL filter

ia, ib, ic three-phase grid currents

IN root mean square of grid current

kad aD coefficient

kad_opt optimal AD parameter

Kpwm gain of the PWM inverter

Kp proportional gain of the PR controller

Kp_opt optimal proportional gain of the PR controller

Kr resonant gain of the PR controller

L1 inverter-side inductor in the LCL filter

L2 grid-side inductor in the LCL filter

Lg grid impedance

Lg_max maximum grid impedance

PCC point of common coupling

PM phase margin

PM0 ideal phase margin

Req virtual resistance in parallel with filter capacitor C1

SCR short-circuit ratio

Ts sampling period

ui inverter output voltage

Us root mean square of grid voltage

Vdc DC-bus voltage

vpcca PCC voltage of phase A

Xeq virtual reactance in parallel with filter capacitor C1

Zeq virtual impedance in parallel with filter capacitor C1

Δt adjustment time

ωc cutoff angular frequency of the system

ωc_max maximum cutoff frequency of system

ωh crossing frequency

ωi cutoff angular frequency of the PR controller

ωo grid fundamental angular frequency

ωres resonant frequency of the LCL filter

ωres actual resonant frequency considering the AD loop

Keywords: weak grid, dynamic performance, LCL filter, active damping, grid current control

Citation: Wu F, Sun Z, Xu W, Li Z and Lyu J (2022) A Control Parameters Design Method With Multi-Constrains for an LCL-Filtered Grid-Connected Inverter in a Weak Grid. Front. Energy Res. 9:798793. doi: 10.3389/fenrg.2021.798793

Received: 20 October 2021; Accepted: 16 December 2021;
Published: 13 January 2022.

Edited by:

Ningyi Dai, University of Macau, China

Reviewed by:

Yushuai Li, University of Oslo, Norway
Xi Lu, Southeast University, China

Copyright © 2022 Wu, Sun, Xu, Li and Lyu. This is an open-access article distributed under the terms of the Creative Commons Attribution License (CC BY). The use, distribution or reproduction in other forums is permitted, provided the original author(s) and the copyright owner(s) are credited and that the original publication in this journal is cited, in accordance with accepted academic practice. No use, distribution or reproduction is permitted which does not comply with these terms.

*Correspondence: Jianguo Lyu, amlhbmd1b2x5dUBuanVzdC5lZHUuY24=

Disclaimer: All claims expressed in this article are solely those of the authors and do not necessarily represent those of their affiliated organizations, or those of the publisher, the editors and the reviewers. Any product that may be evaluated in this article or claim that may be made by its manufacturer is not guaranteed or endorsed by the publisher.