ORIGINAL RESEARCH article

Front. Built Environ., 27 June 2023
Sec. Earthquake Engineering
This article is part of the Research Topic Energy-Based Seismic Engineering View all 8 articles

Energy-based response prediction of reinforced concrete buildings with steel damper columns under pulse-like ground motions

  • Department of Architecture, Faculty of Creative Engineering, Chiba Institute of Technology, Chiba, Japan

The response of structures under pulse-like ground motions is characterized by the large amount of energy input in a few cycles. Consequently, structures with insufficient strength may suffer severe damage owing to excessive deformation. In a previous paper, the energy-based prediction procedure for the peak and cumulative response of a reinforced concrete (RC) frame building with steel damper columns was proposed (Fujii and Shioda, Buildings, 2023, 13, 401). Although this procedure was verified by comparison to the nonlinear time-history analysis (NTHA) results, the performance of the proposed procedure with pulse-like ground motion records has not been verified yet. In this study, the accuracy of the energy-based prediction procedure for an RC frame building with steel damper columns was investigated by considering pulse-like ground motions. The numerical analysis results reveal that the accuracy of the predicted peak response is satisfactory, which agrees with the results of the author’s previous study. However, the accuracy of the predicted total input energy to the building model depends on the ratio of the pulse period of the ground motion to the effective fundamental period of the building model. The reasons for this underestimation of the total input energy are discussed in this paper.

1 Introduction

1.1 Background and motivation

Pulse-like ground motions have been observed in past earthquakes (1994 Northridge Earthquake, 1995 Kobe Earthquake, 1999 Kocaeli Earthquake, 1999 Chi-Chi Earthquake). The response of structures under such ground motions is characterized by a large amount of energy input in a few cycles. Consequently, structures with insufficient strength may suffer severe damage owing to excessive deformation. Therefore, the evaluation of the peak deformation of structures is essential in the case of pulse-like ground motions.

In a previous paper, the energy-based prediction procedure for the peak and cumulative response of a reinforced concrete (RC) frame building with steel damper columns (SDCs) was proposed (Fujii and Shioda, 2023). In this procedure, two energy-related seismic intensity parameters are considered, namely, the maximum momentary input energy (Hori and Inoue, 2002) and the total input energy (Akiyama, 1985). The peak displacement is predicted by considering the energy balance during a half cycle of the structural response, using the maximum momentary input energy. Then, the energy dissipation demand of the dampers is predicted by considering the energy balance during an entire response cycle using the total input energy. Although this procedure has been verified by comparing the nonlinear time-history analysis (NTHA) results, the performance of this procedure in the case of pulse-like ground motion records has not been verified yet. Therefore, this study investigated the accuracy of the proposed procedure for buildings subjected to pulse-like ground motions.

1.2 Brief review of related studies

1.2.1 Studies on characteristics of near-fault ground motions

The characteristics of near-fault ground motions have been widely investigated (Somerville et al., 1997; Alavi and Krawinkler, 2000; Mavroeidis and Papageorgiou, 2003; Bray and Rodriguez-Marek, 2004; Baker, 2007; He and Agrawal, 2008; Ghahari et al., 2010; Shahi and Baker, 2014; Yang and Zhou, 2015; Quaranta and Mollaioli, 2019; Feng et al., 2021; Sugino et al., 2021; Ghanbari and Fathi, 2022). Somerville et al. (1997) pointed out that large velocity pulses can be observed in the normal-fault direction in near-fault records owing to the forward directivity effect. Many studies have modeled the velocity pulses (Alavi and Krawinkler, 2000; Mavroeidis and Papageorgiou, 2003; He and Agrawal, 2008). Alavi and Krawinkler (2000) modeled the velocity pulses using simple rectangular waves for structural analysis. Mavroeidis and Papageorgiou (2003) proposed a mathematical model for representing the velocity pulses as the product of two sine functions. He and Agrawal (2008) proposed a mathematical model based on the Belarge wavelet. Yang and Zhou (2015) and Sugino et al. (2021) modeled velocity pulses using the Gabor wavelet. The decomposition of the near-fault ground motion records into pulse components and (other) residual components has also been attempted by several studies. Ghahari et al. (2010) proposed a procedure for decomposing the near-fault ground motions into long-period pulses and relatively high-frequency background records using a moving average filtering technique; Quaranta and Mollaioli (2019); Feng et al. (2021) proposed a procedure for decomposing near-fault ground motions using the Variational Mode Decomposition (VMD) technique. Ghanbari and Fathi (2022) proposed a procedure for decomposing near-fault ground motions using empirical Fourier decomposition.

The pulse period (or pulse duration) is a key parameter for appropriately modeling velocity pulses. Several studies (Alavi and Krawinkler, 2000; Mavroeidis and Papageorgiou, 2003; Bray and Rodriguez-Marek, 2004; Baker, 2007; Shahi et al., 2014; Quaranta and Mollaioli, 2019) have pointed out that, although the definition of the pulse period may differ among researchers, the pulse period becomes longer when the moment magnitude (MW) of earthquakes becomes larger.

1.2.2 Studies on response of buildings subjected to near-fault ground motions

The responses of structures under pulse-like ground motions were widely investigated after the 1994 Northridge and 1995 Kobe earthquakes (Hall et al., 1995; Alavi and Krawinkler, 2000; Huang, 2003; Alavi and Krawinkler, 2004; Mavroeidis et al., 2004; Akkar et al., 2005; Kalkan and Kunnath, 2006; Xu et al., 2007; Kojima and Takewaki, 2015a; Alonso-Rodríguez and Miranda, 2015; Kojima and Takewaki, 2015b; Alhan and Öncü-Davas, 2016; Güneş and Ulucan, 2019; Al Shawa et al., 2020; Yalcin and Dicleli, 2020; Mota-Páez et al., 2021). Hall et al. (1995) investigated the response of 20-story steel moment-resisting frame (MRF) building models and a three-story RC base-isolated building model using artificially generated pulse-like ground motions. They found that long-period pulse-like ground motions are critical to such flexible building structures. Alavi and Krawinkler (2000; 2004) investigated the response of generalized steel MRF models using a rectangular pulse wave model. They demonstrated that the response of MRF models strongly depends on the ratio of the pulse period (Tp) to the fundamental period (T) of the MRF model: if the Tp/T ratio is larger than unity, the response of the MRF model is governed by the fundamental mode, while the contribution of the higher modal response to the entire response is obvious when Tp/T is smaller than unity. Huang (2003) investigated the response of an elastic continuous shear-beam model, and reported that the influence of a higher modal response to the entire response is obvious when T is larger than 3Tp; Mavroeidis et al. (2004) investigated the response of elastic and inelastic single-degree-of-freedom (SDOF) systems subjected to near-fault ground motions using the velocity pulse model proposed in their previous study (Mavroeidis and Papageorgiou, 2003). They pointed out that the pulse period (Tp) and amplitude (A) can be used to “effectively normalize the elastic and inelastic response spectra of SDOF systems subjected to actual near-fault records”. Akkar et al. (2005) investigated the applicability of a simplified procedure for estimating the local displacement demands in regular MRF responding in the elastic range. In their procedure, the local displacement demands are estimated based on the response of the fundamental mode. Their study demonstrated that this simplified procedure is sufficiently accurate when the T/Tp ratio is less than 1.5; Kalkan and Kunnath (2006) investigated 4-, 7-, and 13-story steel MRF building models subjected to near-fault and far-fault ground motion records. They demonstrated that low-cycle fatigue is critical in the case of far-fault ground motion records, owing to the gradual increase of cumulative energy with longer duration, while excessive larger deformation is critical in the case of near-fault ground motion records, owing to the high-amplitude velocity pulses; Xu et al. (2007) considered the response of a SDOF model with dampers subjected to the velocity pulse model proposed in their study (He and Agrawal, 2008), and investigated the relationship between the energy response of the model and the T/Tp ratio. Alonso-Rodríguez and Miranda (2015) investigated the elastic response of a continuous model formed by a flexural beam laterally coupled to a shear beam subjected to the velocity-pulse model proposed by Mavroeidis and Papageorgiou (2003). They reported that the pulse duration is the most critical parameter affecting both the acceleration and drift response. Kojima and Takewaki (2015a, 2015b) formulated the critical response of an undamped elasto-plastic SDOF model subjected to pulse-like ground motions. In their studies, the fling-step input and forward-directivity input were modeled as double- and triple-impulses, respectively. They demonstrated that the timing of critical pulses depends on the ductility of the elasto-plastic SDOF model. Alhan and Öncü-Davas (2016) investigated the response of a base-isolated building model subjected to the velocity-pulse model proposed by He and Agrawal (2008). In their study, the superstructure model was assumed to behave elastically, while the isolation layer model was assumed to have smoothed bilinear behavior. They demonstrated that “the ratio of the isolation period to the pulse period significantly affects the peak base displacement demands and peak floor acceleration demands”. Güneş and Ulucan (2019) investigated the nonlinear response of a 40-story RC building model subjected to near-fault and far-fault ground motion records. In their study, the ground motion records were divided into four groups: the near-fault ground motions were divided into three groups depending on the pulse duration (Tp) defined by Shahi and Baker (2014), while the far-fault ground motions formed a single group. They demonstrated that the response of a tall reinforced concrete (RC) building depends on the ratio of Tp to the first mode period (T1); the responses of the upper stories become obvious when the Tp/T1 ratio is less than unity, while the responses of the lower stories becomes obvious when the Tp/T1 ratio is larger than unity. Al Shawa et al. (2020) investigated the nonlinear response of SDOF models with different hysteresis models subjected to pulse-like ground motions in terms of energy responses. They demonstrated that the cumulative input energy to the long-period structures becomes larger as the moment magnitude (MW) of the earthquake increases, which is consistent with the pulse duration phenomenon of the pulse-like ground motions becoming longer as MW increases. Yalcin and Dicleli (2020) compared the nonlinear response spectrum of the long-period pulses obtained using the moving average filtering technique to that of the original records. They reported that, in the case of flexible structures subjected to ground motions with larger Tp, the influence of relatively high-frequency background records may be negligible. Mota-Páez et al. (2021) investigated the applicability of the energy-based response prediction procedure to an RC building with hysteresis dampers installed in the soft-story under near-fault ground motions. Their procedure is based on the simplified procedure proposed by Akiyama (1985). They demonstrated that, to better predict the peak response, the equivalent number of cycles should be smaller than the non-pulse-like ground motions.

To the author’s understanding, the ratio of the pulse period Tp to the fundamental period of structures (T or T1) is a key parameter for investigating the response of a building subject to pulse-like ground motions. Because the pulse period (Tp) depends on the moment magnitude (MW), as discussed above, the Tp/T1 ratio is essential for investigating the accuracy of the procedure proposed by the authors (Fujii and Shioda, 2023) for buildings subjected to pulse-like ground motions.

1.3 Objectives

With the background outlined above, this study addressed the following questions.

(i) How accurate is the proposed procedure for RC MRFs with SDCs subjected to pulse-like ground motions?

(ii) Does the accuracy of the procedure depend on the ratio of the pulse period of ground motions to the effective fundamental period of the building model?

In this study, the accuracy of the energy-based prediction procedure for an RC building with SDCs was investigated by considering pulse-like ground motions. To answer the questions stated above, 8- and 16-story RC MRFs with SDCs were considered. Additionally, 30 pulse-like ground motion records were used. The pulse-like ground motions were divided into two groups in accordance with the pulse period defined in the NGA-West2 ground motion database (Shahi et al., 2014).

The rest of this paper is organized as follows. Section 2 outlines the procedure proposed by the authors (Fujii and Shioda, 2023). Section 3 presents two RC MRFs with SDCs, and introduces the ground acceleration data used in the NTHA. The 30 ground motions are grouped into two groups and scaled such that the predicted peak equivalent displacement of the first modal response reaches the predetermined value. Section 4 describes the validation of the seismic demand predictions. Section 5 discusses the accuracy of the predicted peak equivalent displacement of the first modal response, and the contribution of the first modal response to the cumulative energy input. Then, the accuracy of the cumulative input of the first modal response is investigated. The conclusions drawn from this study and the directions of future research are discussed in Section 6.

2 Outline of prediction procedure

Figure 1 outlines the prediction procedure proposed in previous work by the author (Fujii and Shioda, 2023). As can be seen, this procedure consists of three stages, as summarized below.

FIGURE 1
www.frontiersin.org

FIGURE 1. Outline of prediction procedure (Fujii and Shioda, 2023).

In Stage 1, the pushover analysis of the building model is carried out to obtain the restoring force–displacement relationship. From this result, the equivalent displacement (D1*n) and equivalent acceleration of the RC MRF and SDCs (A1f*n and A1d*n, respectively) are calculated for each loading step. For simplicity, the A1f*nD1*n and A1d*nD1*n relationships are idealized as bilinear curves. Then, the equivalent velocity of the maximum momentary input energy corresponding to D1*n (VΔE1*n) is calculated. In this procedure, the VΔE1*nD1*n relationship is referred to as the capacity curve. The effective period corresponding to D1*n is calculated as follows:

T1effn=2π4+7πβ6D1*nVΔE1*n,(1)

where β is the complex damping ratio of the equivalent linear system considered in the calculation of the maximum momentary input energy spectrum (VΔE spectrum) and total input energy spectrum (VI spectrum). In this study, β was set to 0.10 based on the results obtained in previous work by the author (Fujii and Shioda, 2023).

In Stage 2, the VΔE and VI spectra are calculated from the time-varying function (TVF) proposed in a previous study by the author (Fujii et al., 2019). First, the maximum momentary input energy per unit mass (ΔEmax/m) and the total input energy per unit mass (EI/m) of the equivalent linear system (natural period T, complex damping ratio β) are calculated using the TVF. The equivalent velocities of the maximum momentary input energy (VΔE) and total input energy (VI) are calculated as follows:

VΔE=2ΔEmaxm,VI=2EIm.(2)

The equivalent displacement of the equivalent linear system (DT) is calculated as follows:

DT=64+7πβT2πVΔET.(3)

In this procedure, the VΔETDT relationship is referred to as the demand curve. The peak response point of the equivalent SDOF model (D1max*; VΔE1*) is located at the intersection point of the capacity and demand curves. Then, the equivalent velocity of the cumulative input energy of the first modal response (VI1*) is obtained from the VI spectrum, as follows:

VI1*=VIT1eff,(4)

where T1eff is the effective period corresponding to the peak response point, and is calculated as follows:

T1eff=2π4+7πβ6D1max*VΔE1*.(5)

The total input energy of the entire building model is evaluated as follows:

EIMM1*EI1*=12MVI1*2,(6)

where M1* is the effective first modal mass corresponding to the peak response point, and M1 is the total mass. The cumulative strain energy of the RC MRF and SDCs, and cumulative damping dissipated energy are calculated such that the total cumulative energy is equal to EI.

In Stage 3, the local seismic demand of the building model is predicted using the peak and cumulative response of the equivalent SDOF model and the pushover analysis results.

More details on the procedure can be found in a previous paper by the author (Fujii and Shioda, 2023).

3 Building and ground motion data

3.1 Building data

The two planar building models analyzed in this study are 8- and 16-story RC MRFs with SDCs, which are the same as those used in the author’s previous study (Fujii and Shioda, 2023). Figure 2 shows the simplified structural plan and elevation of the RC MRF building models with SDCs. Details on the two structural models can be found in the author’s previous study (Fujii and Shioda, 2023). In this study, the viscous damping ratio of the first modal response of the RC MRFs in the elastic range (h1f) was set to 0.03.

FIGURE 2
www.frontiersin.org

FIGURE 2. Simplified structural plan and elevations of analysis models (Fujii and Shioda, 2023).

Figure 3 shows the capacity curve of the two models calculated based on the pushover analysis results. In this study, the input ground motions were scaled such that the predicted D1max* reaches the predetermined value: the target D1max* was set to 0.252 m for the 8-story model and 0.479 m for the 16-story model. The VΔE1* and T1eff corresponding to target D1max* are 1.220 m/s and 1.318 s, respectively, for the 8-story model, and 1.187 m/s and 2.576 s, respectively, for the 16-story model.

FIGURE 3
www.frontiersin.org

FIGURE 3. Capacity curve of analysis models calculated based on pushover analysis results.

3.2 Ground motion data

As has been shown by the previous studies discussed in Section 1.2, the response of a building structure subjected to pulse-like ground motions is obviously affected by the ratio of the pulse period of the ground motion (Tp) to the fundamental period of the structure (T1). Therefore, two ground motion groups are considered in this study: in group 1, the pulse period (Tp) ranges between 1.0 s and 2.0 s; in group 2, Tp ranges between 2.0 s and 4.0 s. A total of 30 horizontal ground motion sets (15 horizontal ground motion sets in each group) from the NGA-West2 ground motion database of the Pacific Earthquake Engineering Research Center were used. The ground motion sets were selected based on the following criteria: (i) the moment magnitude (MW) is larger than 6.0; (ii) the closest distance from the rupture plane (Rrup) is smaller than 20 km. These values were obtained from the NGA-West2 ground motion database. Table 1 presents the ground motion records. In group 1, MW ranges from 6.0 to 7.1, Rrup ranges from 0.3 km to 10.2 km, Tp ranges from 1.02 s to 1.81 s, and VS30 (the time-averaged shear-wave velocity in the top 30 m at the recording sites) ranges from 139 m/s to 2016 m/s. In group 2, MW ranges from 6.2 to 7.9, Rrup ranges from 1.0 km to 12.8 km, Tp ranges from 2.02 s to 3.77 s, and VS30 ranges from 198 m/s to 553 m/s.

TABLE 1
www.frontiersin.org

TABLE 1. List of ground motion sets investigated in this study.

It is important to show the range of the ratio Tp/T1eff of each ground motion group for both models. The range of the Tp/T1eff ratio for group 1 is 0.775–1.370 for the 8-story model, and 0.397–0.701 for the 16-story model. The range of the Tp/T1eff ratio for group 2 is 1.535–2.863 for the 8-story model, and 0.785–1.465 for the 16-story model.

3.3 Analysis method

For the NTHA of building structures subjected to near-fault ground motions, the selection of the axis of the horizontal component is important. According to research on near-fault ground motions, the horizontal component of the fault normal/fault-parallel (FN/FP) directions is critical to structures (Somerville et al., 1997). However, Kalkan and Kwong demonstrated that rotating the ground motions to the FN/FP directions does not always provide the maximum responses at all angles (Kalkan and Kwong, 2013). Güneş and Ulucan (2019) analyzed a 40-story reinforced concrete building model subjected to near-fault pulse-like ground motions. In their study, the direction of the maximum pseudo-velocity spectrum was used instead of the FN direction, because large velocity pulses were observed in the FP direction in the Yarimca records of the 1999 Kocaeli earthquake. Therefore, it is likely that the FN/FP directions cannot be used as the critical axis of the horizontal ground motion.

In this study, the horizontal component axis was calculated based on the author’s previous study (Fujii, 2022). The procedure is described below.

Step 1. Calculate the complex Fourier coefficients of the ground motion components (c1,n and c2,n, respectively).

c1,n=1td0tdag1texpiωntdtc2,n=1td0tdag2texpiωntdt,(7)
ωn=nΔω=n2π/td,(8)

where ag1t and ag2t are the major and minor components of the horizontal ground motion defined by Arias (1970), td is the length of the ground motion records, and i is the imaginary unit. The range of the number n is taken from NG to NG.

Step 2. Calculate the following matrix E12 for the given equivalent linear system (mass m, natural period T, complex damping ratio β).

E12=EI11EI12EI12EI22,(9)
EI11m=2tdn=1NGReHCViωnc1,n2EI12m=2tdn=1NGReHCViωnRec1,nc2,nEI22m=2tdn=1NGReHCViωnc2,n2,(10)
HCViωn=iωnω02ωn2+2βω02sgnωni,(11)

where HCViωn is the velocity transfer function of the equivalent linear system, and ω0=2π/T is the natural circular frequency of the equivalent linear system.

Step 3. Carry out eigenvalue analysis for matrix E12, and find the angle of the horizontal major direction based on the cumulative energy input (ψE).

Step 4. Calculate the horizontal major component based on the cumulative energy input, as follows:

agξt=ag1tcosψEag2tsinψE.(12)

In the calculation of agξt, the properties of the equivalent linear system are set as T=T1eff and β = 0.10. Therefore, the direction of agξt for the 8-story model may be different to that of the 16-story model.

Next, the scaling factor (λ) is calculated as follows:

λ=VΔE1*/VΔEOT1eff,β(13)

where VΔEOT1eff,β is the equivalent velocity of the maximum momentary input energy of the equivalent linear system for the ground motion component agξt.

In this study, the horizontal major component agξt was scaled by factoring λ, and then used as the input ground motion for NTHA. Table 2 shows the angle of the horizontal major direction based on the cumulative energy input and scale factor of the ground motion sets investigated in this study. Figure 4 shows the maximum momentary input energy spectra (VΔE spectra) and the total input energy spectra (VI spectra) of the scaled ground motions for each model.

In the NTHA of this study, a computer program developed by the authors in the previous study (Fujii and Miyagawa, 2018) was used.

TABLE 2
www.frontiersin.org

TABLE 2. Angle of horizontal major direction based on cumulative energy input and scale factor of ground motion sets investigated in this study.

FIGURE 4
www.frontiersin.org

FIGURE 4. Maximum momentary input energy spectra and total input energy spectra of scaled ground motion sets.

4 Analysis results

4.1 Peak response

In the following discussion, the peak response obtained from the pushover analysis results corresponding to the target D1max* is referred to as “the predicted peak response”.

Figure 5 compares the predicted peak responses of the 8-story model and the NTHA results; the following local response quantities are compared: (i) the peak relative displacement, (ii) the peak story drift, (iii) the peak plastic rotation at the beam end at the right of column X2 (θpmax), and (iv) the peak shear strain of the damper panel (γDmax). In addition to the NTHA results for each ground motion, the mean, maximum, and minimum value of the NTHA results for the 15 ground motions are compared with the predicted results.

FIGURE 5
www.frontiersin.org

FIGURE 5. Comparisons of peak response of 8-story model.

The following conclusions can be drawn from Figure 5.

The predicted peak relative displacement is between the mean and maximum of the NTHA results at all floors.

The predicted peak story is close to the mean of the NTHA results. Around the second to fourth stories, the predicted peak story drift is larger than the mean of the NTHA results.

The predicted θpmax is between the mean and maximum of the NTHA results below the fourth floor level. Beam yielding does not occur at the sixth to eighth floor levels (θpmax = 0).

The precicted γDmax is larger than the mean of the NTHA results. Below the forth story level, the predicted γDmax is close to the maximum of the NTHA results.

The trends in group 1 for all local response quantities shown in Figure 5 are similar to those in group 2. Therefore, the influence of the pulse period of the ground motion to the peak response of 8-story model is limited.

Figure 6 compares the predicted peak responses of the 16-story model to the NTHA results. The following conclusions can be drawn from Figure 6.

The predicted peak relative displacement is between the mean and maximum of the NTHA results at all floors.

The predicted peak story is larger than the mean of the NTHA results below the mid-story level (7th or 8th story). However, the predicted peak story drift above this level is smaller than that of the mean of the NTHA results.

The predicted θpmax is larger than the mean of the NTHA results below the mid-story level (7th or 8th story). However, the predicted θpmax above this level is smaller than that of the mean of the NTHA results.

The precicted γDmax is larger than the mean of the NTHA results below the mid-story level (7th or 8th story). Below the sixth story level, the predicted γDmax is close to the maximum of the NTHA results. However, the predicted γDmax above the mid-story level is smaller than the mean of the NTHA results.

The trends in group 1 in the peak story drift, θpmax, and γDmax are significantly different to those in group 2. In group 1, the difference between the predicted peak response and the mean of the NTHA is significant. Therefore, the influence of the pulse period of the ground motion to the peak response of 16-story model is also significant.

FIGURE 6
www.frontiersin.org

FIGURE 6. Comparisons of peak response of 16-story model.

4.2 Cumulative response

Figure 7 shows comparisons of the predicted total input energy per unit mass obtained from the NTHA results. All response quantities have been normalized by the total mass M. The following conclusions can be drawn from Figure 7.

For the 8-story model, the predicted total input energy is conservative compared with the NTHA results. The mean of the predicted/NTHA ratio is 1.366 for group 1, and 1.469 for group 2.

For the 16-story model, the predicted total input energy is significantly unconservative compared with the NTHA results for group 1: the mean of the predicted/NTHA ratio is 0.661. However, for group 2, the predicted total input energy is conservative compared with the NTHA results: the mean of the predicted/NTHA ratio is 1.523.

FIGURE 7
www.frontiersin.org

FIGURE 7. Relationships between predicted total input energy per unit mass and that obtained from NTHA.

The reasons for having unconservative predicted total input energy for the 16-story model in group 1 would be (i) the contribution of a higher modal response is large, and (ii) the cumulative energy input of the first modal response at the end of the seismic event cannot satisfactorily predicted using the equivalent linear system. These reasons will be discussed below.

4.3 Summary of analysis results

This section demonstrates the accuracy of the prediction procedure proposed in a previous study (Fujii and Shioda, 2023) for the two pulse-like ground motion groups. The analysis results can be summarized as follows.

For the 8-story model, the accuracy of the predicted peak response is acceptable both in group 1 and group 2. The predicted total input energy is conservative compared with the NTHA results.

For the 16-story model, the accuracy of the predicted peak relative displacement is acceptable. However, the other local response quantities (peak story drift, peak plastic rotation at the beam end, peak shear strain of damper panel) are unconservative in the upper stories, while those in the lower stories are conservative. The accuracy of the total input energy depends on the ground motion group.

Importantly, differences in the accuracy of each analysis case may occur owing to the pulse period of the ground motions. As noted in Section 3.2, the Tp/T1eff ratio of the ground motion sets in group 1 for the 16-story model, which is the most inaccurate estimation of the total input energy, is less than unity. The difference in the energy response of the first modal response of each case is discussed below.

5 Discussion

This section focuses on (i) the accuracy of the predicted peak equivalent displacement of the first modal response, (ii) the contribution of the first modal response to the cumulative energy input, and (iii) the accuracy of the predicted cumulative input energy of the first modal response. The equivalent velocities of the maximum momentary input energy and cumulative energy (VΔE1* and VI1*) and the peak equivalent displacement D1max* are calculated from the NTHA results according to the procedure described in a previous paper by the author (Fujii, 2022).

5.1 Accuracy of predicted peak equivalent displacement of first modal response

Figure 8 shows the comparisons between the capacity curve and the VΔE1*D1max* relationship obtained from the NTHA results. In addition, the Tp/T1eff ratio and the ratio of the predicted D1max* and that of the NTHA for all analysis cases are shown in Table 3. The following conclusions can be drawn from Figure 8; Table 3.

Most NTHA results are slightly above and very close to the capacity curve.

The predicted peak response point gives a conservative D1max* value. The ratio of the predicted D1max* and that of the mean of the NTHA is 1.221 and 1.189 for groups 1 and 2 of the 8-story model, respectively, and 1.145 and 1.273 for groups 1 and 2 of the 16-story model, respectively.

FIGURE 8
www.frontiersin.org

FIGURE 8. Comparisons between capacity curve and VΔE1*D1*max relationship obtained from NTHA results.

TABLE 3
www.frontiersin.org

TABLE 3. The Tp/T1eff ratio and the ratio of the predicted peak equivalent displacement to that obtained from NTHA for all analysis cases.

Therefore, as far as D1max* is concerned, the prediction accuracy is satisfactory for both the 8- and 16-story models: the influence of the Tp/T1eff ratio on the accuracy of the predicted D1max* is limited.

5.2 Contribution of first modal response to cumulative energy input

In the prediction procedure, the contribution of the higher modal response to the total input energy is approximated by assuming the following relationship.

EI1*/EIM1*/M.(14)

Eq. 14 suggests that the total input energy EI can be evaluated from the equivalent velocity of the cumulative input energy of the first modal response (VI1*) and total mass (M). Therefore, the accuracy of the predicted EI depends on (i) the validity of the assumed relationship (Eq. 14), and (ii) the accuracy of the predicted VI1* from the VI spectrum. Therefore, (i) the validity of Eq. 14 is evaluated first.

Figure 9 shows the relationship between the cumulative input energy of the first modal response (EI1*) and total input energy (EI) obtained from the NTHA results. In this figure, the two dotted lines indicate the relationship EI1*/EI=1 and EI1*/EI=M1*/M: M1*/M=0.845 for the 8-story model, and M1*/M=0.802 for the 16-story model. Notably, M1* is the effective first modal mass corresponding to the target D1max*. The following conclusions can be drawn from Figure 9.

For the 8-story model, most plots are distributed between EI1*/EI=0.845 and EI1*/EI=1. The difference between the results for groups 1 and 2 is negligible.

For the 16-story model, the difference between the results for groups 1 and 2 is obvious. For group 1, most plots are distributed below the dotted line EI1*/EI=0.802. In contrast, for group 2, most plots are distributed between EI1*/EI=0.802 and EI1*/EI=1.

FIGURE 9
www.frontiersin.org

FIGURE 9. Relationships between cumulative input energy of first modal response (EI1*) and total input energy (EI).

The trends shown in Figure 9 are consistent with the results shown in Figure 7. Thus, one of the reasons for the predicted EI being less accurate in the case of the 16-story model subjected to the ground motion group 1 is that, in this case, the contribution of a higher modal response to the total input energy is large. This observation is consistent with the conclusions drawn by previous studies (Huang, 2003; Alonso-Rodríguez and Miranda, 2015).

5.3 Accuracy of predicted cumulative input energy of first modal response

Next, the accuracy of the predicted VI1* from the VI spectrum is evaluated. Figure 10 shows the relationship between the predicted VI1* and that obtained from the NTHA. The following conclusions can be drawn from Figure 10.

For the 8-story model, the predicted VI1* is in good agreement with that obtained from the NTHA. The mean of the Predicted/NTHA ratio is 1.079 and 1.108 for groups 1 and 2, respectively. The difference in the accuracy of the predicted VI1* between groups 1 and 2 is negligible.

For the 16-story model, the difference in the accuracy of the predicted VI1* between the results for groups 1 and 2 is obvious. For group 1, the predicted VI1* underestimates the NTHA results: the mean of the Predicted/NTHA ratio is 0.833. In contrast, the predicted VI1* is in good agreement with that obtained from the NTHA for group 2: the mean of the Predicted/NTHA ratio is 1.137.

FIGURE 10
www.frontiersin.org

FIGURE 10. Relationships between predicted VI1* and that obtained from NTHA.

Therefore, another reason for the predicted EI being less accurate in the case of the 16-story model subjected to ground motion group 1 is that, in this case, the VI1* predicted from the VI spectrum underestimates the NTHA results. Because the predicted VI1* is calculated from the TVF for the equivalent linear system (effective period T1eff, complex damping β = 0.10), the time-history of the energy input of the first modal response is considered next. Figures 11, 12 compare the time-history of the momentary input energy (ΔE1*/Δt/M1*) and the cumulative input energy (EI1*/M1*) calculated from the TVF and NTHA. Figure 11 shows the results for the 8-story model (group 1: 1995TAZ (Tp/T1eff = 1.370), group 2: 1979ELCA06 (Tp/T1eff = 2.863)), while Figure 11 shows the results for the 16-story model (group 1: 1984CYC (Tp/T1eff = 0.416), group 2: 1994SYL (Tp/T1eff = 0.946)). The following conclusions can be drawn from these figures.

For the 8-story model, the time-history of ΔE1*/Δt/M1* calculated from the TVF is similar to that obtained from the NTHA results for both 1995TAZ and 1979ELCA06. The ΔE1max*/M1* values calculated from the TVF and NTHA are close. Additionally, the time-history of the EI1*/M1* calculated from the TVF is close to that obtained from the NTHA until the end.

For the 16-story model, however, the time-history of ΔE1*/Δt/M1* calculated from the TVF is significantly different to the NTHA results for 1984CYC, although the ΔE1max*/M1* values calculated from the TVF and NTHA are close: in the time-history of the TVF, a significant negative value is observed after ΔE1max*/M1* occurs (approximately 4–5 s), but is not observed in the time history of the NTHA. Additionally, the time-history of EI1*/M1* calculated based on the TVF is significantly different to that calculated based on the NTHA after 4 s: a large drop of EI1*/M1* can be observed at approximately 4–5 s in the time-history of the cumulative input energy obtained from the TVF. The EI1*/M1* at the end calculated from the TVF is significantly smaller compared with that of NTHA: the EI1*/M1* at the end calculated from the NTHA is close to the maximum EI1*/M1* (around 4 s) calculated from the TVF.

In contrast, the time-history of ΔE1*/Δt/M1* calculated from the TVF is similar to that in the NTHA results for 1994SYL of the 16-story model. The ΔE1max*/M1* values calculated based on the TVF and NTHA are close, although the timing of ΔE1max*/M1* is slightly different. Additionally, the time-history of EI1*/M1* calculated from the TVF is close to that obtained from the NTHA until the end.

FIGURE 11
www.frontiersin.org

FIGURE 11. Comparisons between time-history of momentary input energy and cumulative input energy (8-story model).

FIGURE 12
www.frontiersin.org

FIGURE 12. Comparisons between time-history of momentary input energy and cumulative input energy (16-story model).

Therefore, the reason for the VI1* predicted from the VI spectrum underestimating the NTHA results for the 16-story model subjected to ground motion group 1 is the difference of the time-history of the TVF and NTHA. In this case, the cumulative input energy of the first modal response at the end of the seismic event cannot be satisfactorily predicted using the equivalent linear system (effective period T1eff, complex damping β = 0.10). To better predict VI1*, the maximum value of EI1*/M1* over the course of a seismic event calculated from the TVF should be used instead of the EI1*/M1* value at the end.

5.4 Summary of discussion

The above discussion can be summarized as follows.

As far as D1max* is concerned, the prediction accuracy is satisfactory for both the 8- and 16-story model: the influence of the Tp/T1eff ratio on the accuracy of the predicted D1max* is limited.

The underestimation of EI may occur when Tp/T1eff is smaller. For the analysis results obtained in this study, this is the case when Tp/T1eff is in the range of 0.397–0.701. The underestimation of EI may occur for the following reasons: (i) the contribution of the higher modal response to the cumulative energy input is significant; (ii) the cumulative input energy of the first modal response at the end of the seismic event cannot be satisfactorily predicted using the equivalent linear system.

6 Conclusion

In this study, the accuracy of the energy-based prediction procedure for an RC building with SDCs, which has been proposed in a previous paper by the author (Fujii and Shioda, 2023), was investigated with consideration to pulse-like ground motions. The nonlinear response of 8- and 16-story RC MRFs with SDCs was analyzed using 30 pulse-like ground motion records. The main results and conclusions can be summarized as follows.

The accuracy of the predicted peak response is acceptable for the pulse-like ground motion records of the 8-story model investigated in this study, which agrees with the results of a previous study by the author. The predicted peak local responses (relative displacement, peak story drift, peak plastic rotation at the beam end, peak shear strain of damper panel) are in good agreement with those obtained from the NTHA results.

The predicted peak relative displacement of the 16-story model is also in good agreement with that obtained from the NTHA results. However, for the 16-story model, the other local response quantities (peak story drift, peak plastic rotation at the beam end, peak shear strain of damper panel) are unconservative in the upper stories and conservative in the lower stories. This tendency is significant when the ratio of the pulse period (Tp) to the effective period (T1eff) of the building model is small.

The accuracy of the predicted total input energy (EI) depends on the Tp/T1eff ratio. Based on the results obtained by this study, the predicted EI tends to be conservative in the case of the 8-story model (the Tp/T1eff ratio is larger than 0.775). However, for the 16-story model, the predicted EI tends to be unconservative when the range of Tp/T1eff is 0.397–0.701.

The underestimation of EI may occur for the following reasons: (i) the contribution of a higher modal response to the cumulative energy input is significant; (ii) the cumulative input energy of the first modal response at the end of the seismic event cannot be satisfactorily predicted using the equivalent linear system.

Notably, the current version of this procedure is reliable when considering low-rise to mid-rise regular buildings. For the 8-story building model considered in this study, this procedure may be reliable in the case of pulse-like ground motions and non-pulse-like ground motions, as shown in a previous study by the author (Fujii and Shioda, 2023). However, for high-rise buildings, such as the16-story building considered in this study, the predicted local responses should be carefully assessed for the following reasons: (i) owing to the influence of higher modal responses, the distribution of local responses may be significantly different compared with that of the predicted responses; (ii) in the case of pulse-like ground motions with a short pulse period, the total input energy may be underestimated. Therefore, the following questions remain unanswered, although the list below is not comprehensive.

What is the criterion of applicability for the current procedure in the case of pulse-like ground motions? Based on the results obtained by this study, the Tp/T1eff ratio is a key parameter for investigating the applicability. Can this criterion be expressed quantatively? To this end, mathematical models of pulse-like ground motion (Mavroeidis and Papageorgiou, 2003) would be useful.

How can we improve the accuracy of predicting EI? Based on the results obtained by this study, this can be done by (i) using the maximum value of the cumulative input energy over the course of a seismic event, which is calculated from the TVF instead of the value of the cumulative input energy at the end, and (ii) considering the contribution of the higher modal response to the cumulative energy input.

Data availability statement

The raw data supporting the conclusion of this article will be made available by the authors, without undue reservation.

Author contributions

The author confirms being the sole contributor of this work and has approved it for publication.

Funding

This study received financial support from JFE Civil Engineering and Construction Corp.

Acknowledgments

The original frame model data used in this study were provided by Momoka Shioda, who is a former graduate student of Chiba Institute of Technology. The ground motions used in this study were obtained from the website of the Pacific Earthquake Engineering Research Center (https://ngawest2.berkeley.edu/, accessed on 24 February 2023). We thank Edanz (https://jp.edanz.com/ac) for editing a draft of this manuscript.

Conflict of interest

The author declares that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest.

Publisher’s note

All claims expressed in this article are solely those of the authors and do not necessarily represent those of their affiliated organizations, or those of the publisher, the editors and the reviewers. Any product that may be evaluated in this article, or claim that may be made by its manufacturer, is not guaranteed or endorsed by the publisher.

Abbreviations

COV, covariance; MRF, moment-resisting frame; NTHA, nonlinear time-history analysis; RC, reinforced concrete; SDC, steel damper column; TVF, time-varying function; VMD, variational modal decomposition.

References

Akiyama, H. (1985). Earthquake resistant limit-state design for buildings. Tokyo, Japan: University of Tokyo Press.

Google Scholar

Akkar, S., Yazgan, U., and Gülkan, P. (2005). Drift estimates in frame buildings subjected to near-fault ground motions. J. Struct. Eng. ASCE 131, 1014–1024. doi:10.1061/(asce)0733-9445(2005)131:7(1014)

CrossRef Full Text | Google Scholar

Al Shawa, O., Angelucci, G., Mollaioli, F., and Quaranta, G. (2020). Quantification of energy-related parameters for near-fault pulse-like seismic ground motions. Appl. Sci. 10, 7578. doi:10.3390/app10217578

CrossRef Full Text | Google Scholar

Alavi, B., and Krawinkler, H. (2004). Behavior of moment-resisting frame structures subjected to near-fault ground motions. Earthq. Eng. Struct. Dyn. 33, 687–706. doi:10.1002/eqe.369

CrossRef Full Text | Google Scholar

Alavi, B., and Krawinkler, H. (January 2000). “Consideration of near-fault ground motion effects is seismic design,” in Proceedings of the 13th world conference on earthquake engineering Auckland, New Zealand

Google Scholar

Alhan, C., and Öncü-Davas, S. (2016). Performance limits of seismically isolated buildings under near-field earthquakes. Eng. Struct. 116, 83–94. doi:10.1016/j.engstruct.2016.02.043

CrossRef Full Text | Google Scholar

Alonso-Rodríguez, A., and Miranda, E. (2015). Assessment of building behavior under near-fault pulse-like ground motions through simplified models. Soil Dyn. Earthq. Eng. 79A, 47–58. doi:10.1016/j.soildyn.2015.08.009

CrossRef Full Text | Google Scholar

Arias, A. (1970). “A measure of earthquake intensity,” in Seismic design for nuclear power plants. Editors R. J. Hansen, and Massachusetts, USA: The MIT Press, 438–483.

Google Scholar

Baker, J. W. (2007). Quantitative classification of near-fault ground motions using wavelet analysis. Bull. Seismol. Soc. Am. 97 (5), 1486–1501. doi:10.1785/0120060255

CrossRef Full Text | Google Scholar

Bray, J. D., and Rodriguez-Marek, A. (2004). Characterization of forward-directivity ground motions in the near-fault region. Soil Dyn. Earthq. Eng. 24, 815–828. doi:10.1016/j.soildyn.2004.05.001

CrossRef Full Text | Google Scholar

Feng, J., Zhao, B., and Zhao, T. (2021). Quantitative identification of near-fault pulse-like ground motions based on variational mode decomposition technique. Soil Dyn. Earthq. Eng. 151, 107009. doi:10.1016/j.soildyn.2021.107009

CrossRef Full Text | Google Scholar

Fujii, K. (2022). Influence of the angle of seismic incidence of long-period pulse-like ground motion on an irregular base-isolated building. Front. Built Environ. 8, 1034166. doi:10.3389/fbuil.2022.1034166

CrossRef Full Text | Google Scholar

Fujii, K., Kanno, H., and Nishida, T. (2019). Formulation of the time-varying function of momentary energy input to a SDOF system by Fourier series. J. Jpn. Assoc. Earthq. Eng. 19, 247–255. doi:10.5610/jaee.19.5_247

CrossRef Full Text | Google Scholar

Fujii, K., and Miyagawa, K. (June 2018). Nonlinear seismic response of a seven-story steel reinforced concrete condominium retrofitted with low-yield-strength-steel damper columns. Proceeding of the. 16th Eur. Conf. Earthq. Eng. Thessalon. Thessaloniki, Greece

Google Scholar

Fujii, K. (2022). Peak and cumulative response of reinforced concrete frames with steel damper columns under seismic sequences. Buildings 12, 275. doi:10.3390/buildings12030275

CrossRef Full Text | Google Scholar

Fujii, K., and Shioda, M. (2023). Energy-based prediction of the peak and cumulative response of a reinforced concrete building with steel damper columns. Buildings 13, 401. doi:10.3390/buildings13020401

CrossRef Full Text | Google Scholar

Ghahari, S. F., Jahankhah, H., and Ghannad, M. A. (2010). Study on elastic response of structures to near-fault ground motions through record decomposition. Soil Dyn. Earthq. Eng. 30, 536–546. doi:10.1016/j.soildyn.2010.01.009

CrossRef Full Text | Google Scholar

Ghanbari, B., and Fathi, M. (2022). Extraction of velocity pulses of pulse-like ground motions using empirical Fourier decomposition. J. Seismol. 26, 967–986. doi:10.1007/s10950-022-10106-8

CrossRef Full Text | Google Scholar

Güneş, N., and Ulucan, Z. Ç. (2019). Nonlinear dynamic response of a tall building to near-fault pulse-like ground motions. Bull. Earthq. Eng. 17, 2989–3013. doi:10.1007/s10518-019-00570-y

CrossRef Full Text | Google Scholar

Hall, J. F., Heaton, T. H., Halling, M. W., and Wald, D. J. (1995). Near-source ground motion and its effects on flexible buildings. Earthq. Spectra 11 (4), 569–605. doi:10.1193/1.1585828

CrossRef Full Text | Google Scholar

He, W. L., and Agrawal, A. K. (2008). Analytical model of ground motion pulses for the design and assessment of seismic protective systems. J. Struct. Eng. ASCE 134 (7), 1177–1188. doi:10.1061/(asce)0733-9445(2008)134:7(1177)

CrossRef Full Text | Google Scholar

Hori, N., and Inoue, N. (2002). Damaging properties of ground motions and prediction of maximum response of structures based on momentary energy response. Earthq. Eng. Struct. Dyn. 31, 1657–1679. doi:10.1002/eqe.183

CrossRef Full Text | Google Scholar

Huang, C. T. (2003). Considerations of multimode structural response for near-field earthquakes. J. Eng. Mech. ASCE 129 (4), 458–467. doi:10.1061/(asce)0733-9399(2003)129:4(458)

CrossRef Full Text | Google Scholar

Kalkan, E., and Kunnath, S. K. (2006). Effects of fling step and forward directivity on seismic response of buildings. Earthq. Spectra 22 (2), 367–390. doi:10.1193/1.2192560

CrossRef Full Text | Google Scholar

Kalkan, E., and Kwong, N. S. (2013). Pros and cons of rotating ground motion records to fault-normal/parallel directions for response history analysis of buildings. J. Struct. Eng. (N. Y. N. Y). 140 (3), 1–14. doi:10.1061/(asce)st.1943-541x.0000845

CrossRef Full Text | Google Scholar

Kojima, K., and Takewaki, I. (2015a). Critical earthquake response of elastic–plastic structures under near-fault ground motions (Part 1: Fling-step input). Front. Built Environ. 1, 12. doi:10.3389/fbuil.2015.00012

CrossRef Full Text | Google Scholar

Kojima, K., and Takewaki, I. (2015b). Critical earthquake response of elastic–plastic structures under near-fault ground motions (Part 2: Forward-directivity input). Front. Built Environ. 1, 13. doi:10.3389/fbuil.2015.00013

CrossRef Full Text | Google Scholar

Mavroeidis, G. P., Dong, G., and Papageorgiou, A. S. (2004). Near-fault ground motions, and the response of elastic and inelastic single-degree-of-freedom (SDOF) systems. Earthq. Eng. Struct. Dyn. 33, 1023–1049. doi:10.1002/eqe.391

CrossRef Full Text | Google Scholar

Mavroeidis, G. P., and Papageorgiou, A. S. (2003). A mathematical representation of near-fault ground motions. Bull. Seismol. Soc. Am. 93 (3), 1099–1131. doi:10.1785/0120020100

CrossRef Full Text | Google Scholar

Mota-Páez, S., Escolano-Margarit, D., and Benavent-Climent, A. (2021). Seismic response of RC frames with a soft first story retrofitted with hysteretic dampers under near-fault earthquakes. Appl. Sci. 11, 1290. doi:10.3390/app11031290

CrossRef Full Text | Google Scholar

Quaranta, G., and Mollaioli, F. (2019). Analysis of near-fault pulse-like seismic signals through Variational Mode Decomposition technique. Eng. Struct. 193, 121–135. doi:10.1016/j.engstruct.2019.05.003

CrossRef Full Text | Google Scholar

Shahi, S. K., Jack, W., and Baker, J. W. (2014). An efficient algorithm to identify strong-velocity pulses in multicomponent ground motions. Bull. Seismol. Soc. Am. 104 (5), 2456–2466. doi:10.1785/0120130191

CrossRef Full Text | Google Scholar

Somerville, P. G., Smith, M. F., Graves, R. W., and Abrahamson, N. A. (1997). Modification of empirical strong ground motion attenuation relations to include the amplitude and duration effects of rupture directivity. Seismol. Res. Lett. 68 (1), 199–222. doi:10.1785/gssrl.68.1.199

CrossRef Full Text | Google Scholar

Sugino, M., Tanaka, K., and Hayashi, Y. (September 2021). “Proposal of simplified characterization method of pulse-like ground motions,” in Proceedings of the 17th world conference on earthquake engineering (sendai). Sendai, Japan

Google Scholar

Xu, Z., Agrawal, A. K., He, W. L., and Tan, P. (2007). Performance of passive energy dissipation systems during near-field ground motion type pulses. Eng. Struct. 29, 224–236. doi:10.1016/j.engstruct.2006.04.020

CrossRef Full Text | Google Scholar

Yalcin, O. F., and Dicleli, M. (2020). Effect of the high frequency components of near-fault ground motions on the response of linear and nonlinear SDOF systems: A moving average filtering approach. Soil Dyn. Earthq. Eng. 129, 105922. doi:10.1016/j.soildyn.2019.105922

CrossRef Full Text | Google Scholar

Yang, D., and Zhou, J. (2015). A stochastic model and synthesis for near-fault impulsive ground motions. Earthq. Eng. Struct. Dyn. 44, 243–264. doi:10.1002/eqe.2468

CrossRef Full Text | Google Scholar

Keywords: reinforced concrete building, steel damper column (SDC), pulse-like ground motion, energy input, pushover analysis

Citation: Fujii K (2023) Energy-based response prediction of reinforced concrete buildings with steel damper columns under pulse-like ground motions. Front. Built Environ. 9:1219740. doi: 10.3389/fbuil.2023.1219740

Received: 09 May 2023; Accepted: 16 June 2023;
Published: 27 June 2023.

Edited by:

Fabrizio Mollaioli, Sapienza University of Rome, Italy

Reviewed by:

Giuseppe Quaranta, Sapienza University of Rome, Italy
Onur Merter, İzmir University of Economics, Türkiye

Copyright © 2023 Fujii. This is an open-access article distributed under the terms of the Creative Commons Attribution License (CC BY). The use, distribution or reproduction in other forums is permitted, provided the original author(s) and the copyright owner(s) are credited and that the original publication in this journal is cited, in accordance with accepted academic practice. No use, distribution or reproduction is permitted which does not comply with these terms.

*Correspondence: Kenji Fujii, a2VuamkuZnVqaWlAcC5jaGliYWtvdWRhaS5qcA==

Disclaimer: All claims expressed in this article are solely those of the authors and do not necessarily represent those of their affiliated organizations, or those of the publisher, the editors and the reviewers. Any product that may be evaluated in this article or claim that may be made by its manufacturer is not guaranteed or endorsed by the publisher.