Skip to main content

ORIGINAL RESEARCH article

Front. Built Environ., 06 March 2019
Sec. Earthquake Engineering

Simplified Formulations for Estimating the Main Frequencies of Ancient Masonry Churches

\r\nSaulo Lopez*Saulo Lopez1*Michele D&#x;Amato*Michele D'Amato1*Luis RamosLuis Ramos2Michelangelo Laterza&#x;Michelangelo Laterza1Paulo B. LourenoPaulo B. Lourenço2
  • 1DICEM, Department of European and Mediterranean Cultures (Architecture, Environment and Cultural Heritage), University of Basilicata, Matera, Italy
  • 2Department of Civil Engineering, ISISE, University of Minho, Guimarães, Portugal

This paper proposes simplified formulations for estimating the main frequencies of ancient masonry churches. The formulations are derived starting from the results of numerical analyses with finite elements models, whose geometric parameters are assigned in accordance with specific relationships established on a set of 50 existing churches. The so-obtained formulations are also compared with the results of a series of experimental dynamic identification tests chosen from literature. Finally, starting from these experimental results, through numerical regressions, formulas for predicting the main frequencies of ancient masonry churches are proposed, too.

Introduction

The knowledge of the dynamic properties of a structure in the linear range is fundamental, because they influence the response evolution within the non-linear field. If the seismic lateral excitation is concerned, modal response characteristics, such as shape and frequency of vibration modes and damping ratios, are important not only for predicting the seismic performance (Ramos et al., 2013; D'Amato et al., 2017; Laterza et al., 2017), but also for diagnosing the current condition of a structure (Ramos et al., 2010; Ranieri and Fabbrocino, 2011). In fact, modal dynamic properties allow evaluating the effective connection among the parts, as well as allow obtaining progressive or sudden damage occurring while the structure is in service or after an exceptional action such as an earthquake. Moreover, from a computational point of view, the fundamental period is very important in order to apply analytical methods having a different level of refinement for estimating the response of masonry structures/elements. A recent discussion and application of such methods, with a particular reference to ancient masonry structures, may be found for instance, among the others, in Lagomarsino and Resemini (2009); Lourenço et al. (2013); Caprili et al. (2017); Formisano and Marzo (2017); D'Amato et al. (2018); Fuentes et al. (2019). More in general, a discussion of the significance of in-situ tests on ancient masonry structures may be found in Krstevska et al. (2010); Formisano et al. (2018), and in Luchin et al. (2018).

From a conceptual point of view the dynamic behavior of a structure may be studied using two different approaches: an analytical approach, in which starting from geometry, damping, distribution of mass and stiffness it is possible to calculate in a closed form the modal characteristics of the system; and an experimental approach, in which starting from the experimental structural response under a certain excitation it is possible to estimate the dynamic properties of a structure, such as frequencies, vibration modes, and damping by applying dynamic identification techniques. The analytical approach, known as direct problem, requires the definition of a numerical model. The experimental approach, also known as indirect problem since it starts from measurements data for estimating system properties, requires the availability of an equipment for monitoring structures. The first applications of dynamic structural identification were carried out in the 1970s for performing damage identification of aerospace structures and offshore platforms. Also, it should be mentioned the pioneer activity carried out by Ellis and BRE (1998) in order to evaluate the integrity of 534 stone pinnacles on the Westminster Palace. Nowadays, this technique is widespread also for civil engineering purposes, aiming at the evaluation of the structural behavior along the time (Douglas and Reid, 1982) also in the case of historical constructions (among the others Casarin and Modena, 2007; Ranieri et al., 2013; De Luca et al., 2014).

Starting from these premises, the present paper focuses on the estimation, through an analytical approach, of the main natural frequencies of ancient masonry churches, which are useful for seismic assessment purposes. First, equations indicated in national codes to estimate the main frequencies of a structure are examined and compared. Then, a series of parametric numerical simulations are carried out in order to propose new equations for estimating the main vibration modes frequencies of ancient masonry churches. The equations are derived by considering two different churches typologies, having one or three naves. For each typology, four possible different configurations are defined as function of roof and bell tower configuration. The parametric analyses are performed by varying the defined fundamental geometric parameters of the considered numerical models. Based on the obtained results, exponential regressions with multiple variables are proposed for the transversal and longitudinal main frequencies of vibration modes, taking into account geometric parameters and Young's modulus. The obtained correlations are also compared with the results of dynamic identifications tests performed in several case studies, whose results are available in literature. Finally, a correction of the proposed equations numerically derived for the first main frequency is discussed on the basis of the comparison with the experimental results.

The proposed formulas are particularly useful since they are proposed for ancient churches structural typologies, while the existing national code formulations are referred, on the contrary, to generic buildings. They also represent a practical tool for revealing potential hidden damages or for identifying the actual connections among the parts, since their results may be compared with the ones obtained through on site dynamic identification tests.

Estimation of Main Modal Frequency With Existing National Codes Equations

Generally, national codes provide a simplified equation for estimating the main frequency of a structure. These formulas are useful for instance for static seismic analyses, in which the distribution of static lateral forces is determined in a simplified way, avoiding to perform a modal linear analysis.

In this work three different formulas are analyzed and compared. In particular, they are taken into account formulas indicated in the American (ASCE 07-16, 2017), the Italian (NTC-2008, 2008), and the Spanish (NCSE-2002, 2002). It should be noted that these are established through empirical correlations primarily depending on the structure building height, reflecting the principle that, if mass and stiffness are kept constant, the higher the height the lower the frequency of the first vibration mode. Moreover, the considered formulations are referred to a general masonry building typology, and not specifically to the ancient churches typology (Goel and Chopra, 1997).

ASCE 07-16 (2017) provides a general expression for calculating the fundamental frequency of a structure. For masonry typology, the following equation is given:

f(H)=10.0488H3/4(H in meters)    (1)

where f is the natural frequency, H is the structural height of the roof above from the base, not including any parapet or penthouse.

The Italian (NTC-2008, 2008) recommends the following equation to estimate the fundamental frequency of a masonry structure, substantially similar to the (ASCE 07-16, 2017) one:

f(H)= 10.05H3/4(H in meters)    (2)

specifying that the equation is used for buildings lower than 40 meters having a uniform mass distributed along the height. It is worthy of note that in the recent updated Italian Design code (NTC-2018, 2018) it is proposed the relationship f=1(2d), where d is the lateral elastic displacement of the highest point of the structure under the seismic action. This expression presumes that d is known through, at least, a seismic static equivalent analysis, allowing of differentiating the oscillation frequency along the two principal directions. Although it is more complete, in this study it is considered only the Equation (2) since, similarly to the other ones considered, the formula refers directly to geometric properties of the investigated structure.

The Spanish Design Code (NCSE-2002, 2002) suggests a more complete formula, capable of estimating the fundamental frequency in the two principal directions, and also useful for estimating the second and the third natural frequency in the same direction of the first one. The proposed formula takes into account the plan dimension L along the direction of oscillation, as well as the structure height H:

f1= L0.06HH2L+H , f2=3f1, f3=5f1    (3)

For completeness, Figure 1 graphically illustrates the formulas here considered. In particular, Figure 1A depicts the predicted frequencies (fpred) obtained with the (ASCE 07-16, 2017) and (NTC-2008, 2008) formulas. Whereas, Figure 1B shows some iso-frequency curves obtained by varying H and L in according to the (NCSE-2002, 2002) equation.

FIGURE 1
www.frontiersin.org

Figure 1. Estimation of the fundamental frequency with the (A) formulations proposed by ASCE 07-16 and NTC-08 and (B) with the formulation proposed by NCSE-2002.

It should be remarked that the previous equations may be applied with particular regard to masonry buildings. They are not specific for ancient masonry churches that should require adequate formulas due to their particular structural typology. A similar approach, for instance, may be found in the recent studied of Shakya et al. (2016); Bartoli et al. (2017); Diaferio et al. (2018); and Sarhosis et al. (2018) where appropriate empirical and semiempirical formulations for predicting the main frequency of slender masonry towers have been proposed.

Simplified Formulations for Estimating Ancient Masonry Churches Modal Frequencies

In order to propose a simplified formulation for estimating the modal frequencies of ancient masonry churches, a set of 50 existing Portuguese case studies having Romanesque, Manueline (Portuguese late Gothic) and Baroque styles are taken into consideration. The location and the architectural style of the each considered church may be found in the Annex. While, Figure 2A shows the geographical location of the 50 sampled churches with the corresponding identification number. As it is possible to note, most of churches are located in the northwest, due to the fact that this area was in the past the most influential religious place of the Country. Additionally, in this area it is also possible to find the great nucleus of national Romanesque architecture. Commonly, the masonry encountered consists of local granite blocks due to its abundance, with very thin mortar joints. The texture of the masonry is always really regular and no significant damage is present for each church of the chosen data set.

FIGURE 2
www.frontiersin.org

Figure 2. (A,B) Location of 50 sampled churches in the Table 1 and typological classification of the considered reference churches.

The chosen churches are identified by typology, considering the plan and spatial composition, the main structural elements and the range of structural measures. They have one or three naves with a Latin cross plan, where the central nave is taller than the lateral ones. Commonly, they have a bell tower adjacent to the main building and, only in some cases, such structures present two towers. The roof system usually consists of masonry vaults or wooden roofs connected by timber beams embedded in the longitudinal walls. In both the cases, roof tiles are placed on these elements. Figure 2B summarizes the classification for single or three naves typology, considering for each of them four sub-cases, as follows: case Simple (S) associated to churches having nave(s), a main chapel and timber roof; case Bell Tower (T) corresponding to churches with nave(s), main chapel, timber roof and bell tower; case Vault (V) for churches with nave(s), main chapel, and vault; and case Vault and Bell Tower (VT) for churches with nave(s), main chapel, vault and bell tower. Therefore, by considering the combinations of these four major elements found within the considered database 8 reference typologies, in total, have been individuated.

After classified the considered 50 existing churches in according to the 8 considered reference typologies, the following relationships have been derived through linear regressions between the main geometrical properties, namely, width, length, and height:

Single Nave Typology

{LNV = 2.53·WNV  1.61 (R2=0.70)LMAX=1.33·LNV+2.51 (R2=0.96)WMC=0.62·WNV+0.83 (R2=0.74)LNV=1.49·HNV+2.84 (R2=0.71)HNV=9.90·Thickness+2.04 (R2=0.51)HNVmin not applicableWBT=0.28·WNV+0.80 (R2=0.61)HBT=1.7·HNV (R2 not calculable)    (4)

Three Naves Typology

{LNV = 2.02· WNV  1.64 (R2=0.61)LMAX=1.45· LNV4.95 (R2=0.89)WMC=0.85· WNV6.09 (R2=0.74)LNV=1.37· HNV+16.37 (R2=0.32)HNV=9.49· Thickness+3.00 (R2=0.57)HNVmin =0.72·HN0.83 (R2=0.69)WBT=0.60·WNV+4.58 (R2=0.75)HBT=1.4·HNV (R2 not calculable)    (5)

Where the considered geometric parameters are (Figures 3A,B): LMAX: maximum plan length; LNV: length of the nave(s); WNV: width of the nave(s); WBT: width of the bell tower(s); WMC: width of main chapel, HBT: height of the bell tower, HNVmin: height of the lateral naves; HNV: height of the main nave. For completeness, for each geometrical relationship found among it is reported also the resulting coefficient of correlation (R2).

FIGURE 3
www.frontiersin.org

Figure 3. Geometric parameters in (A) plan and (B) in elevation, and views of the implemented numerical models for (C) single nave type and (D) three naves type.

Once the relationships among the main churches geometrical properties have been derived, a series of numerical simulations are carried out in order to numerically predict the natural frequencies of these church models. The simulations are performed by referring to the eight identified reference typologies, whose geometric parameters are assigned considering the relationships reported in the Equation (4) and in the Equation (5). The numerical models are implemented within iDiana 10.1 (TNO, 2016), a finite element software for advanced structural analysis. The following assumptions are adopted for the numerical models: homogeneous masonry material in all elements of the structure, having the following mechanical properties for granite masonry (Oliveira et al., 2012): material density equal to 2,000 kg/m3, Young's modulus and Poisson's ratio equal to 1 GPa and 0.2, respectively. The vertical walls have the same thickness in each model and, for simplicity, the external wall openings (windows, small doors, etc.) are not considered in the numerical models. Finally, a rigid ground foundation (all elements are fixed at the base) is assumed. Figures 3C,D illustrates the implemented numerical models of the eight church reference typologies. The assigned geometric dimensions for performing the analyses are in accordance with the proposed Equation (4, 5), by varying them into the ranges summarized in Table 1. It must be noted that the minimum height (HNV) considered for single and three naves models (7.2 and 6.5 m, respectively) corresponds to the lowest values found within the 50 Portuguese churches in the sample.

TABLE 1
www.frontiersin.org

Table 1. Range of parameters for the model of single nave and three naves.

The parametric analyses are conducted using a code implemented in MatLab R2013 (MATLAB Statistics Toolbox Release, 2013), together with iDiana 10.1 to define the different models and to compute the natural frequencies through modal analysis. Eight-node quadrilateral isoparametric curved shell elements have been used for modeling the walls of churches and of the bell tower, six-node triangular isoparametric curved shell element for the vaults, and three-dimensional beams with three-node elements for columns. Eleven and thirteen base models are implemented in order to perform, in total, 44 and 52 numerical models for single and three naves typology, respectively. In particular, the analyses consider the variation at the same time up to nine geometrical parameters in the case of more complex-base models. Furthermore, 55 additional models are implemented to study the influence of the Young's modulus on the response of churches type 1N-S, too.

Finally, by performing modal analyses, the main modes of vibration and frequencies of the numerical models are identified and compared. In particular, it has been observed for all the implemented models that the first vibration mode (indicated as mode 1_TY) is related to a global translation with simple curvature in the structure transversal direction. While, the second mode (mode 2_TY) corresponds to a global translation of the structure having a double curvature in the transversal direction. Finally, the third mode (mode_TX) represents a global translation with simple curvature in the longitudinal direction of the structure, with an overturning mechanism of the main façade. Figure 4 shows the first transverse natural frequency mode 1_TY obtained for single (1N) and three (3N) naves models. It clearly illustrates that, in the case of single nave (1N models), the typologies with towers (T), vaults or both (V or VT), have always the first frequency higher than the simple model (1N-S). The comparisons confirm that the models with towers and vaults (1N-VT) are stiffer than the other ones, because the vaults significantly decrease the lateral flexibility. Moreover, it is observed that the higher the nave height, the lower the scatter among the results. In the case of three naves models (3N models) the mode 1_TY frequencies of models with towers (3N-T), vaults (3N-V), and both (3N-VT) do not vary significantly among them, but the result are remarkably different with respect to the simple model (3N-S).

FIGURE 4
www.frontiersin.org

Figure 4. First transversal frequency Mode 1_TY: (A) single nave and (B) three naves churches models.

From the obtained frequencies with the numerical analyses it is possible to propose formulas correlating the found frequencies with the main geometrical parameters of the investigated church typologies. These formulas, developed by multivariable regression analysis and separately derived for churches having a single or three naves, allow estimating the first three frequencies, that are two transversal and one longitudinal. An analytical exponential form for the proposed equations is adopted in the Equation (4), reproducing the form proposed by several international codes for calculating the fundamental period of a structure:

f(H,Typ,E)=a(H)b(Typ)c(E)0.5(Hz)

where a, b and c are numerical coefficients; H is the nave height in meters (equal to HNV or HNVmin depending on the church typology); Typ is a coefficient related to the church type (that is S, T, V, and VT), ranging from 1 to 4, as follows: 1 for churches without towers or vaults (S typology), 2 for churches with only towers (T typology), 3 for churches having only vaults (V typology), and 4 in the case of churches with towers and vaults (VT typology); E is the average Young's modulus of the masonry (in GPa). With the form of the Equation (6), three relationships are proposed to estimate the three main frequencies of the two considered church types (Equations 7, 8). They refer to the first two transversal global mode shapes (indicated as Transversal 1 and Transversal 2) and to the first longitudinal global mode shape (Longitudinal 1). For the proposed equation the resulting correlation coefficient R2 is reported, too. As it is possible to note, for all the proposed formulas a very good correlation with the numerical results is obtained. For sake of completeness, Figure 5 compares the first frequencies f_trans1 numerically derived with the proposed equations, in the case of single nave simple model (1N-S) and when varying the Young's modulus E.

Single Nave

{Transversal 1:     f_trans1=18.509·HNV-0.985·Typ0.178·E0.5 (R2=0.99)Transversal 2:     f_trans2=34.234·HNV-0.929·Typ-0.203·E0.5 (R2=0.91)Longitudinal 1: f_long1=18.509·HNV-0.985·Typ0.178·E0.5 (R2=0.85)    (7)

Three Naves

{Transversal 1:     f_trans1=2.437·HNV-0.743·Typ1.101·E0.5 (R2=0.94)Transversal 2:     f_trans2=11.468·HNV-0.821·Typ-0.368·E0.5 (R2=0.89)Longitudinal 1: f_long1=15.461·HNV-0.836·Typ0.197·E0.5 (R2=0.87)    (8)
FIGURE 5
www.frontiersin.org

Figure 5. First transversal frequency f_trans1: comparison between the numerical data and the proposed equation in the case of single nave churches (1N-S).

Comparison With Experimental Results

Once simplified formulations for estimating the modal frequencies of some typologies of churches has been proposed, a database of case studies is collected in order to compare the experimental results with the ones obtained with the proposed relationships. In this scope, a set of 19 ancient masonry churches is defined through a literature review in order to define a database of experimental tests results. The experimental tests have been performed with the aim of determining the dynamic properties and material characteristics of churches, for detecting damages and also for assessing their seismic performances. Table 2 reports the list of the chosen case studies with the related location and literature reference. For completeness, Figure 6 reports three of the selected masonry churches located, respectively, in Italy, Portugal, and Peru, as representative of the considered churches. Figure 6A shows the Matera Cathedral in Southern Italy built in the thirteenth century, which is an example of the Apulian Romanesque architecture. It is constituted by three naves, having a Latin cross plan covered with a timber roof, and also a tall bell tower. The church was built with stone masonry, using the local calcarenite rock (Ramirez et al., 2019). Figure 6B illustrates the main façade of the Saint Torcato church in Guimarães (Northern Portugal), an example of the so-called Neo-Manueline style built at the end of the nineteenth century. The church structure is composed by different materials, such as granite stone in most of the elements and concrete in the apse. It presents the typical Latin cross plan with a single nave covered by a barrel vault, and a transept having a dome in the center. In the past, the church presented significant structural problems, such as cracks in the main and lateral façade and leaning towers due the settlement of the foundation. Recently, the church has been equipped with a monitoring system to evaluate the strengthening interventions applied (Ramos et al., 2013). Lastly, Figure 6C depicts the San Juan Bautista of Huaro located in Cusco (Southern Peru). The church belongs to the Andean baroque style and its construction dates back to the sixteenth century. It consists of adobe masonry walls for the main structural system, having a single nave with a bell tower. The foundations are in stone masonry and the roofing system is made using timber collar trusses (Aguilar et al., 2016).

TABLE 2
www.frontiersin.org

Table 2. Database of ancient masonry churches compiled from a literature review.

FIGURE 6
www.frontiersin.org

Figure 6. Three examples of masonry churches from the literature review: (A) Matera Cathedral (Italy, Ramirez et al., 2019), (B) Saint Torcato Church (Portugal, Ramos et al., 2013), and (C) San Juan Bautista of Huaro (Perú, Aguilar et al., 2016), and (D) statistical data of the location and structural characteristics of all the studied churches.

Figure 6D illustrates the geographical distribution of the 19 chosen churches, all built between the ninth and the nineteenth centuries having comparable construction technology and types of materials. It can be observed that the majority of the studied churches are located in Portugal (37%) and Italy (21%), but there are also churches located in Peru, Cyprus, Chile, Spain and Brazil. Figure 6D depicts as well the chosen churches grouped in terms of construction materials (such as stone, adobe, clay brick, stone, or adobe with clay brick), configuration and number of naves. It is worth to note that the most common material is stone, that was a material largely used in the monumental construction. As far as the structural configuration is concerned, the chosen churches are almost equally divided in those without tower (type WT), having a single (type 1T) or two towers (2T). In terms of naves, within the chosen group it is possible to find eight churches having a single nave and 13 with three naves.

Table 3 provides, for each examined church, the identified geometrical parameters and the resulting main frequencies obtained by the means of dynamic identification tests. In detail, it is reported the main nave height (H), the lateral naves height (Hmin), the maximum length (Lmax), and width (W) in plan, as illustrated in Figure 7. As far as the obtained experimental results are concerned, Table 3 lists all the found frequencies collected in literature, namely fexp_trans1 and fexp_trans2 corresponding to first and second main frequency in the transversal direction, and fexp_long1, which is the first frequency in the longitudinal direction.

TABLE 3
www.frontiersin.org

Table 3. Main geometrical characteristics and collected frequencies from the published literature.

FIGURE 7
www.frontiersin.org

Figure 7. Main geometric features of the churches in plan and frontal view.

The found frequencies have been experimentally measured through dynamic identification tests carried out acquiring, depending on the case, ambient vibrations or artificial excitation (instrumented hammer or vibrodyne). All the churches have been instrumented with accelerometers, whose locations have been defined starting from preliminary modal analyses obtained with FE models. Uniaxial or triaxial accelerometers sensors have been used recording signals in a variable interval from 10 to 30 min in the case of ambient vibrations tests, with a sample rate of 100-−200 SPS (Samples per second). The accelerometers have been placed on the churches elements considered more representative from a dynamic point of view (e.g., façade, nave, etc.).

Comparative Assessment

This section compares the collected experimental frequencies, summarized in the Table 3 with the ones empirically estimated with the formulas of (ASCE 07-16, 2017) (Equation 1), (NTC-2008, 2008) (Equation 2), (NCSE-2002, 2002) (Equation 3). Moreover, also the new proposed equations are considered. In particular, Figures 8A,B compare the frequencies predicted with the code equations with the ones corresponding to the first experimental transverse frequency fexp_trans1. As it is possible to observe, the scatter among data is not negligible and only in few cases the considered code formulations approximate the experimental frequencies. Most likely, this is due to the fact that the frequencies of the churches do not only depend on the structures height, but also on the other geometrical characteristics and mechanical properties. As for the (NCSE-2002, 2002) formulation, it leads to considerable frequency overestimations because of, while the experimental values are ranging from 1 to 6 Hz, the predicted ones result from 5 to 30 Hz. The remarkable gap among the experimental and predicted frequencies is probably due to the fact that the (NCSE-2002, 2002) formula has been calibrated starting from masonry structures stiffer than the churches. Moreover, the comparison experimental values fexp_trans1 against the predicted ones with proposed equations (Equations 7, 8) in Figure 8C is reported.

FIGURE 8
www.frontiersin.org

Figure 8. Comparisons among the experimental fexp_trans1 and the predicted fpred, by referring to the formulation adopted by: (A) ASCE 07-16 (2017), (B) NTC-2008 (2008), and NCSE-2002 (2002), (C) proposed formulation.

For all the comparisons considered, the resulting errors among the predicted and experimental values are measured in this study through two statistics parameters, that are Root Mean Squared Error (RMSE) and R-squared (R2), calculated as follows:

1. The RMSE parameter, representing the square root of the variance of the residuals, given by the expression [Equation (5)]:

RMSE=i=1n(fexp,if1,i)2n    (9)

where fexp, i and f1, i are the experimental and predicted frequencies, and n is the number of data points. The lower the RMSE parameter the higher the accuracy in prediction of the experimental frequencies.

2. The R2 factor, calculated as follows:

R2=1i=1n(fexp,if1,i)2j=1n(fexp,ji=1nfexp,in)2    (10)

Where with the same symbols of the previous Equation (9). Therefore, the higher values of R2 indicate that the regression model fits the data better.

The numerical values of the RMSE and R2 obtained in the analyzed cases are reported in Table 4. As far as the first transverse frequency fexp_trans1 is concerned, it is clear that all the considered formulations, with exception for the proposed one, have a scarce accuracy in predicting the experimental values due, most likely, to the fact that these formulations, as already remarked, have been proposed for generic masonry buildings and not specifically for churches. Moreover, although the (NCSE-2002, 2002) formulation should result more accurate because it considers two parameters, this code standard provides the worst prediction. In contrast, the proposed formulation fits better the experimental data (R2 = 0.52 and RMSE = 1.26). For sake of completeness, Table 4 also reports the resulting errors RMSE and R2 among the predicted and experimental values in the case of the second transverse (fexp_trans2) and first longitudinal (fexp_long1) frequency. In these cases, the errors are calculated by referring only to the analytical formulations where it has been possible to calculate the predicted values, that are the (NCSE-2002, 2002) formulation and the proposed one. As it is possible to note, an acceptable accuracy with the proposed formulation (Equations 7, 8) is also obtained in these cases.

TABLE 4
www.frontiersin.org

Table 4. RMSE and R2 coefficients obtained comparing the experimental fexp_trans1, fexp_trans2, and fexp_long1 with the predicted values (Equations 7, 8).

Formulations Based on Experimental Data

In addition to the proposed equations (Equations 7, 8) derived from numerical simulations with finite element models, in this paragraph simplified formulations for the first transverse frequency are also proposed, directly derived from the set of the considered experimental results. In particular, three different types of equations are proposed having an exponential form including, respectively, one, two and three variables. They are derived with regression analysis by using the software CurveExpert Professional (Hyams, 2011).

The simplest proposed formula has the following exponential form:

f_trans1=aVb      (Hz)    (11)

That is the usual formulation adopted by design codes, where V represents a geometrical parameter (given in meters) such as, for instance, H (height of the main nave), or W (width in plan) or Lmax (maximum length in plan), as shown in the Figure 7; a and b are regression coefficients, for a confidence level equal to 95%.

Table 5 reports the proposed formulas having a single variable form of the Equation (11) with the resulting R2 factor. The same formulas are graphically reported in Figures 9A,B, and compared with the collected experimental values. Each of the proposed formulation considers separately the most important factors influencing the first transverse frequency of a church, that is the height (H) for the Formula 1 and Formula 2, the transverse dimension in plan (W) for the Formula 3, and the length in plan (Lmax) for the Formula 4. In particular, the Formula 2 is similar to the Formula 1, where the variable H is also chosen as principal geometrical parameter for defining the dynamic behavior of a church. In this last formula its exponent b is assumed equal to −0.75 in order to maintain the same analytical structure of the fundamental period equation proposed by the considered national codes (Equations 1, 2). Finally, by comparing the different one-variable formulations proposed, it is easy to note that, in terms of scatter (Table 5), the lower errors are obtained in the cases of Formula 1 and the Formula 3 confirming that, for predicting the first natural frequency of a structure the significant parameters are the height H and transverse dimension W along which the oscillation occurs.

TABLE 5
www.frontiersin.org

Table 5. Results of the regression analysis for estimate the first frequency using one-variable, two-variable and three-variable formulas.

FIGURE 9
www.frontiersin.org

Figure 9. Performances of the three proposed equations for the first natural frequency f_trans1 with the one-variable formulas (A,B), and correlation between the first main frequency in the transversal direction and the others one: (C) f_trans1 vs. f_trans2 and (D) f_trans1 vs. f_long1.

As for the two-variable models (Table 5), the considered parameters are, again, H, W, Lmax and the further Young's modulus E. It is easy to note that the proposed formulations considering the parameter length in plan Lmax (such as the formulas 1, 5, and 7) provide the lowest matching with the experimental data. On the other hand, the models including the parameter E, either considering the height H (Formula 3) or W (Formula 6) provide the best correlation (R2 equal to 0.55 and 0.51, respectively).

For completeness, also three-variable models are suggested starting from the regression analyses on the experimental data collected (Table 5). For these formulas the chosen variables are the height and the width in plan (H and W), and the material Young's Modulus (E). Among the formulations proposed, Formula 1 allows us to obtain a better match with the experimental results (R2 = 0.57), also with respect to the Formula 1 with having two variables. The Formula 2, although is similar to the Formula 1, differs for the fact that the third coefficient d is fixed to 0.50, for establishing a formula similar to the proposed in Table 4. Finally, as it is clear to see, the best model to predict the first main frequency in the transversal direction is with three-variables is the following formula having the minor error and a value of R2 = 0.56:

f_trans1=16.41H0.4W0.3E0.2    (12)

Determination of the Two Subsequent Natural Frequencies

Starting from the collected experimental data of Table 5, a preliminary formula also for correlating the two subsequent natural frequencies (f_trans2 and f_long1) with the first one is presented (f_trans1). The correlations found between the second (f_trans2) and the first longitudinal (f_long1) frequencies with the first one (f_trans1) are reported in Equations (13, 14).

f_trans2 = 1.46 (f_trans1)    (13)
f_long1 = 1.42 (f_trans1)    (14)

The same correlations are plotted in the Figures 9C,D and compared with the experimental values. As it is clear to observe, in the cases analyzed the relationships of f_trans2 and f_long1 with f_trans1 may be both described with an acceptable error with linear formulations.

Conclusions

In this paper, simplified formulas for estimating the main frequencies of ancient masonry churches have been proposed. They represent also a practical tool for revealing potential hidden damages or the actual connections among the parts since the estimated values may be compared with the ones obtained through dynamic identification tests. The proposed formulations have been derived with multivariable regressions starting from the numerical results of analyses carried out with finite elements models. In these analyses the geometric parameters have been varied in accordance with specific relationships derived by studying the proportioning of 50 existing ancient churches. In particular, the numerical simulations addressed ancient churches having one or three naves with/without bell towers and vaults.

The proposed equations derived from numerical simulations, unlike the ones indicated in seismic design codes, have the characteristic of being particularly appropriate for the ancient churches typology, and not for general masonry buildings. Moreover, specific equations for estimating the second transverse frequency and the first longitudinal have been also derived. The comparisons with a set of experimental data collected in the published literature validate the simplified formulations, demonstrating that a better estimation of the frequency may be done by accounting, in the numerical proposed formulations, of simultaneously the nave height, the type of structure and the Young's modulus. It should be remarked that the considered design code formulations (NCSE-2002, 2002; NTC-2008, 2008; ASCE 07-16, 2017) tend to overestimate the main frequency of a structure and have a weak correlation with the actual values. On the contrary, as demonstrated the proposed formulations have a good accuracy in predicting the experimental frequencies.

Finally, preliminary numerical formulas are also proposed directly established with numerical regressions on the considered experimental data. These formulas have one-, two- or three-variables and conserve an exponential form, in analogy with the classic form adopted by seismic design codes. The best accuracy in predicting the experimental data is reached with a three-variables formulation considering the two dimensions in plan and a representative Young's modulus.

In future the proposed equations may be improved by considering also the actual damage of the elements/parts, as well as of considering interventions, existing or to be applied. In addition, it should be possible also to explicitly take into account the presence and efficiency of additional elements (such as buttress among the others) that, as known, significantly influence the transversal frequency of a structure. Finally, it should be remarked that the investigations performed in this paper are based on the key assumption that all the typologies considered exhibit a whole structural behavior. Therefore, before their application, one should carefully exclude partial responses of some element, by duly investigating through in-situ tests all the structural details.

ANNEX: List of the Sampled Churches Data

Table 6 reports the list of the sampled churches data.

TABLE 6
www.frontiersin.org

Table 6. List of the sampled churches data illustrated in Figure 2.

Author Contributions

All authors listed have made a substantial, direct and intellectual contribution to the work, and approved it for publication.

Conflict of Interest Statement

The authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest.

Acknowledgments

The research activity carried out by SL has been supported by the ELARCH scholarship and mobility, a project funded under the Erasmus Mundus Action 2 Partnership (EMA2) by the European Commission, and coordinated by the University of Basilicata (http://www.elarch.org). ELARCH project: Reference number 552129-EM-1-2014-1-IT-ERA MUNDUS-EMA21 funded with support of the European Commission. This document reflects the view only of the author, and the Commission cannot be held responsible for any use which may be made of the information contained therein.

References

Aguilar, R., Noel, M., Briceño, C., Arce, D., and Castañeda, B. (2016). “Geomatics' procedures and dynamic identification for the structural survey of the church of “San Juan Bautista de Huaro” in Perú,” in 16th International Brick and Block Masonry Conference, eds C. Modena, F. da Porto, and M. R. Valluzzi (Padova: CRC Press), 815–820.

Google Scholar

Antonacci, E., Beolchini, G. C., Di Fabio, F., and Gattulli, V. (2001). “The dynamic behavior of the Basilica S. Maria of Collemaggio,” in 2nd International Congress on Studies in Ancient Structures (Istanbul).

Google Scholar

Araújo, A. S., and Lourenço, P. B. (2011). “Avaliação Da Segurança Sísmica De Igrejas: Aplicação a Dois Casos De Estudo,” in Congresso de Métodos Numéricos em Engenharia 2011 (Coimbra: APMTAC).

Google Scholar

ASCE 07-16 (2017). Minimum Design Loads and Associated Criteria for Buildings and Other Structures American Society of Civil, Engineers. Virginia, NV: Reston.

Bartoli, G., Betti, M., Marra, A. M., and Monchetti, S. (2017). Semiempirical formulations for estimating the main frequency of slender masonry towers. J. Perform. Constr. Facilit. 31, 1–10. doi: 10.1061/(ASCE)CF.1943-5509.0001017

CrossRef Full Text | Google Scholar

Caprili, S., Mangini, F., Salvatore, W., Bevilacqua, M. G., Karwacka Codini, E., Squeglia, N., et al. (2017). A knowledge-based approach for the structural assessment of cultural heritage, a case study: La Sapienza Palace in Pisa. Bull. Earthq. Eng. 15, 4851–4886. doi: 10.1007/s10518-017-0158-y

CrossRef Full Text | Google Scholar

Casarin, F., and Modena, C. (2007). “Dynamic identification of S. Maria Assunta Cathedral, Reggio Emilia, Italy,” in 2nd International Operational Modal Analysis Conference (Copenhagen), 637–644.

Google Scholar

D'Amato, M., Laterza, M., and Casamassima, V. M. (2017). Seismic performance evaluation of a multi-span existing masonry arch bridge. Open Constr. Build. Technol. J. 11(Suppl. 5), 1191–1207. doi: 10.2174/1874149501711011191

CrossRef Full Text | Google Scholar

D'Amato, M., Laterza, M., and Diaz Fuentes, D. (2018). Simplified seismic analyses of ancient churches in matera's landscape. Int. J. Archit. Heritage. doi: 10.1080/15583058.2018.1511000. [Epubh ahead of print].

CrossRef Full Text | Google Scholar

De Luca, F., Verderame, G. M., and Manfredi, G. (2014). Eurocode-based seismic assessment of modern heritage RC structures: The case of the Tower of the Nations in Naples (Italy). Eng. Struct. 74, 96–110. doi: 10.1016/j.engstruct.2014.05.015

CrossRef Full Text | Google Scholar

Diaferio, M., Foti, D., and Potenza, F. (2018). Prediction of the fundamental frequencies and modal shapes of historic masonry towers by empirical equations based on experimental data. Eng. Struct. 156, 433–442. doi: 10.1016/j.engstruct.2017.11.061

CrossRef Full Text | Google Scholar

Douglas, B., and Reid, W. (1982). Dynamic test and system identification of bridges. J. Struct. Div. 108, 2295–2312.

Google Scholar

Ellis, B. R. and BRE. (1998). Non-destructive dynamic testing of stone pinnacles on the Palace of Westmister. Proc. Instit. Civil Eng. Struct. Build. 128, 300–307.

Google Scholar

Elyamani, A., Caselles, O., Roca, P., and Clapes, J. (2017). Dynamic investigation of a large historical cathedral. Struct. Control Health Monitor. 24:e1885. doi: 10.1002/stc.1885

CrossRef Full Text | Google Scholar

Formisano, A., and Marzo, A. (2017). Simplified and refined methods for seismic vulnerability assessment and retrofitting of an Italian cultural heritage masonry building. Comput. Struct. 180, 13–26. doi: 10.1016/j.compstruc.2016.07.005

CrossRef Full Text | Google Scholar

Formisano, A., Vaiano, G., Fabbrocino, F., and Milani, G. (2018). Seismic vulnerability of Italian masonry churches: The case of the Nativity of Blessed Virgin Mary in Stellata of Bondeno. J. Build. Eng. 20, 179–200. doi: 10.1016/j.jobe.2018

CrossRef Full Text | Google Scholar

Fuentes, D. D., Laterza, M., and D'Amato, M. (2019). “Seismic vulnerability and risk assessment of historic constructions: the case of masonry and adobe churches in italy and chile,” in Proceedings of SAHC 2018, 11th International Conference on Structural Analysis of Historical Constructions (Cusco), 1127–1137.

Google Scholar

Goel, R. K., and Chopra, A. K. (1997). Period formulas for moment-resisting frame buildings. J. Struct. Eng. 11, 1454–1461.

Google Scholar

Granda, S., López, S., Navia, F., Ramirez, E., Ramirez, R., Ramos, L. F., et al. (2019). “Diagnosis and structural assessment of the fortress and convent of Ínsua de São Isidro BT,” in Proceedings of SAHC 2018, 11th International Conference on Structural Analysis of Historical Constructions (Cusco). 2386–2394.

Hyams, D. G. (2011). CurveExpert Professional. V. 2.6.3. Available online at: https://www.curveexpert.net/

Krstevska, L., Tashkov, L., Naumovski, N., Florio, G., Formisano, A., Fornaro, A., et al. (2010). “In-situ experimental testing of four historical buildings damaged during the 2009 L'Aquila earthquake,” in COST ACTION C26: Urban Habitat Constructions under Catastrophic Events - Proceedings of the Final Conference (Naples), 427–432.

Google Scholar

Lagomarsino, S., and Resemini, S. (2009). The assessment of damage limitation state in the seismic analysis of monumental buildings. Earthq. Spectra 25, 323–346. doi: 10.1193/1.3110242

CrossRef Full Text | Google Scholar

Laterza, M., D'Amato, M., and Casamassima, V. M. (2017). “Seismic performance evaluation of multi-span existing masonry arch bridge,” in Proceedings of the 14th International Conference of Numerical Analysis and Applied Mathematics - ICNAAM 2016 (Rhodes).

Google Scholar

Lourenço, P. B., Karanikoloudis, G., and Greco, F. (2016). “In situ testing and modeling of cultural heritage buildings in Peru, proceedings of SAHC 2016,” in 10th International Conference on Structural Analysis of Historical Constructions (Leuven), 850–857.

Google Scholar

Lourenço, P. B., Oliveira, D. V., Leite, J. C., Ingham, J. M., Modena, C., and da Porto, F. (2013). Simplified indexes for the seismic assessment of masonry buildings: international database and validation. Eng. Fail. Anal. 34, 585–605. doi: 10.1016/j.engfailanal.2013.02.014

CrossRef Full Text | Google Scholar

Luchin, G., Ramos, L. F., and D'Amato, M. (2018). Sonic tomography for masonry walls characterization. Int. J. Architect. Heritage. doi: 10.1080/15583058.2018.1554723. [Epubh ahead of print].

CrossRef Full Text | Google Scholar

MATLAB and Statistics Toolbox Release (2013). The MathWorks, Inc., Natick, MA.

PubMed Abstract

Mendes, N., Lourenço, P. B., Besca, M., Trufelli, E., and Barontini, A. (2016a). Diagnosis and seismic analysis of the Our Lady of Conception Church, Portugal. Case studies of building pathology in cultural heritage. Build. Pathol. Rehab. 1, 1–21. doi: 10.1007/978-981-10-0639-5_10

CrossRef Full Text

Mendes, N., Zanotti, S., Lourenço, P. B., and Lemos, J. (2016b). “Análise sísmica da Igreja de Kuño Tambo,” in 10° Congresso Nacional de Sismologia e Engenharia Sismica (Ponta Delgada).

Google Scholar

Mendes, P., Baptista, M. A., Agostinho, L., Lagomarsino, S., and Costa, J. P. (2005). “Structural and dynamic analysis of N. Sra. do Carmo church, Lagos Portugual,” in Proceedings EURODYN2005 (Paris). 311–318.

Google Scholar

Mesquita, E., Brandão, F., Diogenes, A., Antunes, P., and Varum, H. (2017). Ambient vibrational characterization of the Nossa Senhora das Dores Church. Eng. Struct. Technol. 9, 170–182. doi: 10.3846/2029882X.2017.1416311

CrossRef Full Text | Google Scholar

NCSE-2002 (2002). Norma de ConstrucciònSismorresistente. Parte General y Edificaciòn (Spanish Standard)- Ministerio de Fomento.

NTC-2008 (2008). Norme Tecniche per le Costruzioni. D.M. 14/01/2008, S.O. n. 30 of the Official Gazette of the Italian Republic 2008.

NTC-2018 (2018). Aggiornamento delle Norme Tecniche per le Costruzioni. D.M. 17/01/2018, S.O. n. 42 of the Official Gazette of the Italian Republic 2018.

Oliveira, D. V., Silva, R. A., Garbin, E., and Lourenço, P. B. (2012). Strengthening of three-leaf stone masonry walls: an experimental research. Mater. Struct. 45, 1259–1276. doi: 10.1617/s11527-012-9832-3

CrossRef Full Text | Google Scholar

Ramirez, E., Lourenco, P. B., and D'Amato, M (2019). “Seismic assessment of the Matera Cathedral,” in Proceedings of SAHC 2018, 11th International Conference on Structural Analysis of Historical Constructions (Cusco) 1346–1354.

Ramirez, R. (2016). Structural Analysis of the Church of the Monastery of São Miguel de Refojos. Guimaraes: University of Minho.

Google Scholar

Ramos, L. F., Aguilar, R., Lourenço, P. B., and Moreira, S. (2013). Dynamic structural health monitoring of Saint Torcato church. Mech. Syst. Signal Process. 35, 1–15. doi: 10.1016/j.ymssp.2012.09.007

CrossRef Full Text | Google Scholar

Ramos, L. F., Marques, L., Lourenço, P. B., De Roeck, G., Campos-Costa, A., and Roque, J. (2010). Monitoring historical masonry structures with operational modal analysis: Two case studies. Mech. Syst. Signal Process. 24, 1291–1305. doi: 10.1016/j.ymssp.2010.01.011

CrossRef Full Text | Google Scholar

Ranieri, C., and Fabbrocino, G. (2011). “Predictive correlations for the estimation of the elastic period of masonry towers masonry towers,” in 4th International Conference on Experimen- tal Vibration Analysis for Civil Engineering Structures (Varenna). Available online at: https://www.researchgate.net

Google Scholar

Ranieri, C., Fabbrocino, G., and Verderame, G. M. (2013). Non-destructive characterization and dynamic identification of a modern heritage building for serviceability seismic analyses. NDT E Int. 60, 17–31. doi: 10.1016/j.ndteint.2013.06.003

CrossRef Full Text | Google Scholar

Sarhosis, V., Milani, G., Formisano, A., and Fabbrocino, F. (2018). Evaluation of different approaches for the estimation of the seismic vulnerability of masonry towers. Bull. Earthq. Eng. 16 1511–1545. doi: 10.1007/s10518-017-0258-8

CrossRef Full Text | Google Scholar

Shakya, M., Varum, H., Vicente, R., and Costa, A. (2016). Empirical formulation for estimating the fundamental frequency of slender masonry structures. Int. J. Architect. Heritage 10, 55–66. doi: 10.1080/15583058.2014.951796

CrossRef Full Text | Google Scholar

TNO (2016). DIsplacement method ANAlyser- DIANA FEA BV- iDiana Release 10.1.

Torres, W., Almazán, J. L., Sandoval, C., and Boroschek, R. (2017). Operational modal analysis and FE model updating of the Metropolitan Cathedral of Santiago, Chile. Eng. Struct. 143, 168–188. doi: 10.1016/j.engstruct.2017.04.008

CrossRef Full Text | Google Scholar

Ulloque, E. (2017). Seismic Assessment of the Church San Giovanni Battista. Matera: University of Minho.

Votsis, R. A., Kyriakides, N., Chrysostomou, C. Z., Tantele, E., and Demetriou, T. (2012). Ambient vibration testing of two masonry monuments in Cyprus. Soil Dyn. Earthq. Eng. 43, 58–68. doi: 10.1016/j.soildyn.2012.07.015

CrossRef Full Text | Google Scholar

Keywords: churches, cultural heritage, masonry, numerical models, vibration frequency

Citation: Lopez S, D'Amato M, Ramos L, Laterza M and Lourenço PB (2019) Simplified Formulations for Estimating the Main Frequencies of Ancient Masonry Churches. Front. Built Environ. 5:18. doi: 10.3389/fbuil.2019.00018

Received: 13 December 2018; Accepted: 07 February 2019;
Published: 06 March 2019.

Edited by:

Solomon Tesfamariam, University of British Columbia, Canada

Reviewed by:

Michele Betti, Università degli Studi di Firenze, Italy
Antonio Formisano, University of Naples Federico II, Italy

Copyright © 2019 Lopez, D'Amato, Ramos, Laterza and Lourenço. This is an open-access article distributed under the terms of the Creative Commons Attribution License (CC BY). The use, distribution or reproduction in other forums is permitted, provided the original author(s) and the copyright owner(s) are credited and that the original publication in this journal is cited, in accordance with accepted academic practice. No use, distribution or reproduction is permitted which does not comply with these terms.

*Correspondence: Michele D'Amato, bWljaGVsZS5kYW1hdG9AdW5pYmFzLml0
Saulo Lopez, c2F1bG8ubG9wZXptQHB1Y3AucGU=

Michelangelo Laterza was the coordinator of the ELARCH mobility network. He had a true passion for research and conservation of historic buildings, and left us unexpectedly in August 2018

Disclaimer: All claims expressed in this article are solely those of the authors and do not necessarily represent those of their affiliated organizations, or those of the publisher, the editors and the reviewers. Any product that may be evaluated in this article or claim that may be made by its manufacturer is not guaranteed or endorsed by the publisher.